© 2020 IRONRIDGE, INC. VERSION 3.2 FLUSH MOUNT INSTALLATION MANUAL - 19 <br />MICROINV e RT e R KITS <br />SYST e MS USING e NPHAS e MICROINV e RT e RS OR SUNPOW e R AC MOD- <br />IronRidge systems using approved Enphase products or SunPower modules eliminate the need for lay-in lugs and field <br />installed equipment grounding conductors (EGC). This solution meets the requirements of UL 2703 for bonding and <br />grounding and is included in this listing. <br />COMPATIBL e PRODUCTS <br />Sunpower <br />Modules with model identifier Ab-xxx-YY and InvisiMount (G5) 46mm frame; where “A” is either E, or X; “b” can be 17, 18, 19, 20, 21, or 22; <br />and “YY” can be C-AC, D-AC, BLK-C-AC, or BLK-D-AC. <br />enphase <br />Microinverters M250-72, M250-60, M215-60, C250-72, and engage cables eTXX-240, eTXX-208, eTXX-277. <br /> ➢A minimum of two inverters mounted to the same rail and connected to the same engage cable are required. <br /> ➢The microinverters or Sunpower AC modules must be used with a maximum 20 A branch rated overcurrent protection device (OCPD). <br /> ➢If an AC module is removed from a circuit for maintenance, you must first disconnect AC power and then install a temporary EGC to <br />bridge the gap by inserting an AC extension cable (or via other NEC-compliant means), in order to maintain effective ground continuity <br />to subsequent modules. <br />One Microinverter <br /> Kit Required <br />(80 in-lbs) <br />Use IronRidge's Microinverter Kit to bond compatible <br />microinverters and power optimizers to the racking system. <br />Insert Microinverter Kit T-bolt into top rail slot. Place <br />compatible microinverter or power optimizer into position <br />and tighten hex nut to 80 in-lbs. <br /> ➢If installing in areas with ground snow loads greater than 40 psf, <br />install MLPe devices directly next to module frame edge <br />On AP systems equipment, <br /> remove Grounding Washer <br />COMPATIBL e PRODUCTS <br />enphase <br />M250-72, 250-60, M215-60, C250-72, S230, S280, IQ 6, IQ 6+, IQ <br />IQ7, IQ 7A, IQ 7+, IQ7 PD, IQ 7X, Q Aggregator <br />Darfon <br />MIG240, MIG300, G320, G640 <br />Solar edge <br />M1600, P300, P320, P340, P370, P400, P401, P405, P485, P505, <br />P600, P700, P730, P800p, P800s, P801, P850, P860, P950, <br />P960, P1100 <br />SMA <br />RoofCommKit-P2-US, TS4-R Module Retrofit Kits (TS4-R-S, <br />TS4-R-O, TS4-R-F) <br />Tigo <br />Tigo Access Point (TAP) <br />TS4-R-X (where X can be F, M, O, or S) <br />TS4-R-X-DUO (where X can be M, O, or S) <br />TS4-A-X (where X can be F, 2F, O, O-DUO, or S) <br />AP Systems <br />QS1, YC600 <br /> ➢Remove Grounding Washer on AP Systems QS1 and YC600 <br />inverters before installing to XR rails. <br /> ➢Remove the Stainless Steel Clip on Tigo-”A” MLPe Devices <br />before attaching to XR rails. <br /> ➢Use the number of IronRidge Microinverter kits allowed <br />by the MLPE mounting flange. Some will require 1 kit and <br />others 2 kits. <br />Two Microinverter <br />Kits Required <br />(80 in-lbs) <br />3000 S Sycamore St Unit# <br />A- 201822724/29/2024