Laserfiche WebLink
13.High Efficient Motors listed shall meet section 313 of the Energy Independence and Security Act of 2007; (EISA 2007). <br />23 81 19.13.B Delivery, Storage, and Handling <br />1.Unit shall be stored and handled per manufacturer’s recommendations. <br />23 81 19.13.E Project Conditions <br />1.As specified in the contract. <br />23 81 19.13.F Operating Characteristics <br />1.Unit shall be capable of starting and running at 125°F (52°C)ambient outdoor temperature, meeting maximum load <br />criteria of AHRI Standard 210/240 or 340/360 at ± 10% voltage. <br />2.Compressor with standard controls shall be capable of operation down to 0°F (2°C), ambient outdoor temperatures.See <br />below for head pressure control package or winter start kit. <br />3.Unit shall discharge supply air vertically or horizontally as shown on contract drawings. <br />4.Unit shall be factory configured for vertical supply & return configurations. <br />5.Unit shall be field convertible from vertical to horizontal airflow on all models. <br />6.Unit shall be capable of mixed operation: vertical supply with horizontal return or horizontal supply with vertical return. <br />23 81 19.13.G Electrical Requirements <br />1.Main power supply voltage, phase, and frequency must match those required by the manufacturer. <br />23 81 19.13.H Unit Cabinet <br />1.Unit cabinet shall be constructed of galvanized steel with exterior surfaces coated with a non-chalking, powder <br />paint finish, certified at 750 hour salt spray test per ASTM-B117 standards. <br />2.Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or 340/360 minimum <br />exterior sweat criteria. Interior surfaces shall be insulated with a minimum 1/2- in. thick, 1 1/2 lb density, flexible <br />fiberglass insulation, neoprene coated on the air side. Aluminum foil- faced fiberglass insulation shall be used in the <br />gas heat compartment. Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site <br />selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the service factor (Only <br />premium efficiency motors have hp rating on the nameplate). Units shall be designed to operate within the service <br />factor. Fan wheel shall be double inlet type with forward curve blades, dynamically balanced to operate smoothly <br />throughout the entire range of operation. Airflow design shall be constant volume. Bearings shall be sealed and <br />permanently lubricated for longer life and no maintenance. <br /> Condenser Fan Assembly: The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum <br />blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for smooth operation. The <br />outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and <br />staged independently. <br />3.Base of unit shall have a minimum of four locations for thru-the-base gas and electrical connections (factory installed or <br />field installed), standard. <br />4.Base Rail <br />a.Unit shall have base rails on a minimum of 4 sides. <br />b.Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging. <br />c.Holes shall be provided in the base rail for moving the rooftop by fork truck.. <br />d.Base rail shall be a minimum of 16 gauge thickness. <br />5.Condensate pan and connections <br />a.Shall be an internally sloped condensate drain pan made of a non-corrosive material. <br />b.Shall comply with ASHRAE Standard 62. <br />c.Shall use a 3/4” - 14 NPT drain connection, possible either through the bottom or side of the drain pan. Connection <br />shall be made per manufacturer’s recommendations. <br />6.Top panel <br />a.Shall be a single piece top panel. <br />7.Gas Connections <br />a.All gas piping connecting to unit gas valve shall enter the unit cabinet at a single location on side of unit <br />b.Thru-the-base capability <br />(1.)Standard unit shall have a thru-the-base gas- line location using a raised, embossed portion of the unit <br />basepan. <br />Guide Specification for <br />York® Sun™ Core <br />Page: 15 <br />3925 S Bristol <br />St-HVAC12/23/2024