Laserfiche WebLink
R905.2.2 SLOPE <br />ASPHALT SHINGLES SHALL BE USED ONLY ON ROOF SLOPES OF TWO UNITS VERTICAL IN 12 UNITS <br />HORIZONTAL (17-PERCENT SLOPE) OR GREATER. FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN <br />12 UNITS HORIZONTAL (17-PERCENT SLOPE) UP TO FOUR UNITS VERTICAL IN 12 UNITS <br />HORIZONTAL (33-PERCENT SLOPE), DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED IN <br />ACCORDANCE WITH SECTION R905.1.1. <br />ROOF SLOPE <br />PER TABLE R905.1.1(2) <br />FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12), UP TO FOUR <br />UNITS VERTICAL IN 12 UNITS HORIZONTAL (4:12), UNDERLAYMENT SHALL BE TWO LAYERS APPLIED IN <br />THE FOLLOWING MANNER: APPLY A 19-INCH STRIP OF UNDERLAYMENT FELT PARALLEL TO AND <br />STARTING AT THE EAVES. STARTING AT THE EAVE, APPLY 36-INCH- WIDE SHEETS OF UNDERLAYMENT, <br />OVERLAPPING SUCCESSIVE SHEETS 19 INCHES. DISTORTIONS IN THE UNDERLAYMENT SHALL NOT <br />INTERFERE WITH THE ABILITY OF THE SHINGLES TO SEAL. END LAPS SHALL BE 4 INCHES AND SHALL <br />BE OFFSET BY 6 FEET. FOR ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL <br />(4:12) OR GREATER, UNDERLAYMENT SHALL BE ONE LAYER APPLIED IN THE FOLLOWING MANNER: <br />UNDERLAYMENT SHALL BE APPLIED SHINGLE FASHION, PARALLEL TO AND STARTING FROM THE EAVE <br />AND LAPPED 2 INCHES, DISTORTIONS IN THE UNDERLAYMENT SHALL NOT INTERFERE WITH THE <br />ABILITY OF THE SHINGLES TO SEAL. END LAPS SHALL BE 4 INCHES AND SHALL BE OFFSET BY 6 FEET <br />UNDERLAYMENT NOTES <br />ALL NEW SHINGLE ROOF SHALL MATCH COLOR, SHAPE AND TEXTURE <br />OF EXISTING IN MAIN HOUSE. <br />ROOF FINISHING NOTE <br />EACH VENT= 100 SQ. IN. AS PER VERDE INDUSTRIES <br /> 1. DORMER ATTIC VENTS 38" X 26" <br /> MODEL NO. 100ASD WWW.VERDEINDUSTRIES.COM <br />ROOF VENT NOTES <br /> 2. MIN 1" BETWEEN PLYWOOD AND INSULATION <br />AND EAVE VENTS. PER R806.3 CRC <br />3. MIN 1/16" MAX 1/4" MESH AT VENTS, INCLUDING CONTINUOUS VENTS <br />4. OPENING FOR VENTILATION SHALL BE COVERED WITH CORROSION- <br />RESISTANT METAL MESH WITH MESH OPENINGS OF 1/4" IN DIMENSION. <br />20'-0" MAX. <br />F.C.U. <br />30"x30" ATTIC ACCESS <br />CORROSION-RESISTANT PAN <br />SHT. MTL. <br />SET 0/ 26 GA <br />COLD AIR RETURN <br />ROOF RAFTER <br />PLYWOOD PLATFORM BY TRUSS <br />ATTIC - MOUNTED <br />DOUBLE - WALLED <br />VENT CONNECTORS <br />FRONT OF CONTROL <br />SIDE OF UNIT <br />2x PLATFORM <br />12" INSOLATION DAM <br />TILE 24 CALC'S <br />ISULATION PER <br />FRAMING <br />WALKWAY (un-obstructed) <br />24" WIDE CONT. PLYWOOD <br />MANUFACTURER <br />12 <br />" <br /> <br />M <br />I <br />N <br />. <br />LIGHT <br />1" CLR. MIN <br />WORKSPACE IN <br />30' CLEAR <br />CLASS "B" VENT W/ 26 GA. <br />GALV. FLASHING COLLAR <br />PROVIDED W/ 1/4" SCREENING <br />PROVIDE GAS & OUTLET AT IN <br />ATTIC FOR F.C.U. <br />COMBUSTION & SUPPLY AIR <br />PROVIDE SEPARATE DUCT <br />OPENINGS FOR UPPER & LOWER <br />PROVIDE CIRCULATING AIR SUPPLY <br />OPENINGS OR DUCT W/ 2 SQ. IN. <br />PER 1000 BTU (100 SQ. IN. MIN.) <br />TO COMPARTMENT TO BE <br />NOTES : <br />COMBUSTION AIR FORM OUTSIDE <br />A MINIMUM 22"x30" ATTIC ACCESS <br />SHALL BE PROVIDED INTO ALL ATTIC <br />AREAS. <br />ACCESS SHALL BE LOCATED WITHIN 20' <br />OF ATTIC MOUNTED EQUIPMENT. <br />CATWALK FROM ACCESS OPENING TO <br />EQUIPMENT SHALL BE UNOBSTRUCTED <br />BY TRUSS MEMBERS OR OTHER <br />FEATURES. <br />MINIMUM 30" HEADROOM SHALL BE <br />MAINTAINED AT ACCESS, CATWALK AND <br />WORK AREA. <br />OUTLET <br />SWITCH <br />1.SHINGLE ROOF CLASS "A", DURATION PRODUCT LINE, OVER <br />2 LAYERS OF 30# ASTM D 226 TYPE I FELT PAPER MIN. <br />UNDERLAYMENT TO BE INSTALLED IN COMPLIANCE WITH <br />2022 CRC SECTION R905.2.7 ICC-ESR 1475 <br /> NOTES <br />ALL MANUFACTURED EQUIPMENT AND MATERIAL SHALL BE INSTALLLED <br />AS PER MANUFATURES'S SPECIFICATION AND DIMENSIONS VERIFIED <br />WITH INSTALLATION REQUIREMENTS ON SITE. <br />1.ROOFING PRODUCTS SHALL BE LISTED WITH CURRENT <br />CRRC PRODUCT ID NUMBER AND MUST BEAR THE <br />FOLLOWING RATING: A. LOW SLOPED ROOF (LESS THAN <br />2:12 SLOPE), A MINIMUM AGED SOLAR REFLECTANCE OF <br />0.63 AND THERMAL EMITTANCE OF 0.75, OR A MINIMUM <br />SRI OF 75. B. HIGH SLOPED ROOF (2:12 OR STEEPER <br />SLOPE), A MINIMUM AGED SOLAR REFLECTANCE OF 0.10 <br />AND THERMAL EMITTANCE OF 0.85 (SEE T-24 CALC'S) <br /> ROOF NOTES <br />ALL MANUFACTURED EQUIPMENT AND MATERIAL SHALL BE INSTALLLED <br />AS PER MANUFATURES'S SPECIFICATION AND DIMENSIONS VERIFIED <br />WITH INSTALLATION REQUIREMENTS ON SITE. <br />10 : 12 PITCH <br />SHINGLE. ROOFING W/15 FELT <br />OVER 1/2 CDX. PLYWD. SHEATHING <br />COMP. ROOFING <br />2.DORMER ATTIC VENTS (GALVANIZED IRON W/ 1 <br />4" <br />OPENINGS 12" X 24" TYPICAL). SEE ROOF PLAN <br />FOR LOCATIONS. <br />3. 6" WOOD FASCIA. <br />1 WWW.CERTAINTEED.COM <br /> -GABLE END ATTIC VENTS 12" X 18" <br />2.784 <br />1.77 <br />0 <br />4.4 <br />EACH VENT= 100 SQ. IN. AS PER VERDE INDUSTRIES <br />= SQ.FT <br />150 S.F. <br />VENTILATION NEEDED <br /> = -EAVE BLOCKS <br />= SQ.FT <br /> - DORMER ATTIC VENTS 38" X 26" <br />144 <br /> X 9.42 <br /> LINEAR FT. OF EAVE <br />EACH BLOCK = 9.42" <br />TOTAL VENTILLATION PROVIDED = SQ. FT. <br />3 <br />0 <br />1 <br />0 <br /> X 144" <br />1 <br />144 <br /> X 100" <br />= SQ.FT <br />144 <br /> VENT SQ. IN. AS PER AIR VENT INC. (CERTAINTEED CO.) <br /> -GABLE END ATTIC VENTS 12" X 14" <br />5.55 <br />(3-2"DIA. HOLES) <br />2 <br />81 <br />660 <br />27 <br /> MODEL NO. 100ASD WWW.VERDEINDUSTRIES.COM <br />144 <br /> X 100" <br />27 <br /> S.F. <br />= SQ.FT. <br />VENTILATION PROVIDED <br /> S.F. OF VENTILATION REQUIRED <br />ROOF PLAN <br />1/4" = 1'-0" <br />ROOF NOTES : <br />1.-CLASS "A" LAMINATED SHINGLES ROOFING <br />MANUF: OWNES CORNING <br />STYLE: MATCH EXISTING / COLOR : MATCH EXISTING <br />INSTALL PER MANUF. SPECIFICATIONS & 2022 CBC, <br />SEC. 1507.2 <br />PROVIDE MIN. 30# ROOFING FELT UNDERLAYMENT <br />ROOF PITCH = 10: 12 <br />2.-EDGE OF ROOF /RAIN GUTTERS RAINGUTTERS: <br />SEAMLESS SHEET METAL (GALV.) SEE DETAILS <br />3.--- <br />4.- PROVIDE CLOTHES DRYER MOISTURE EXHAUST DUCT <br />(MIN. 4" DIA.) TO THE OUTSIDE & EQUIPPED WITH A <br />BACK-DRAFT DAMPER. EXHAUST DUCT LENGTH IS <br />LIMITED TO 14 FT. WITH 2 ELBOWS. [CMC 504.4.2] <br />5.- PROVIDE 100 SQ. IN. OF MAKEUP AIR TO <br />LAUNDRY ROOM PER CMC 205, 504.4.1 and 701.3. <br />6.-RADIANT BARRIERS: <br />A. PROVIDE NO LESS THAN 30% UPPER VENTS. <br />B. BE INSTALLED ON VERTICAL ATTIC SURFACES <br />AND GABLE ENDS. <br />C. WHEN INSTALLED IN ENCLOSED RAFTER <br />SPACES A MINIMUM AIR SPACE <br />OF 1' MUST BE PROVIDED AND VENTILATION BE <br />PROVIDED AT UPPER AND LOWER END OF EVERY <br />RAFTER BARRIER. <br />7.- FCU RETURN GRILL. <br />8.- G.I. WATER HEATER EXHAUST THRU ROOF. <br />9.- G.I. FAU EXHAUST THRU ROOF. <br />1 <br />TYP <br />10:12 SLOPE <br />ROOF SHINGLES <br />NEW <br />10:12 SLOPE <br />ROOF SHINGLES <br />NEW <br />1/2" x 4 x 8 OSB <br /> NO RADIANT BARRIER <br />(See T-24 calc's) <br />PLYWOOD W/8d <br />COMMON NAILS, <br />@ 12" O.C. ON FIELD <br /> & 6" O.C. IN THE EDGE. <br />2" X 10" X FASCIA <br />ROOF FRAMING PER <br />STRUCTURAL PLANS <br />2"X4"X STUDS <br />@ 24" O.C. <br />USED TO 24" <br />OVERHEAD <br />1-LAYER # 30 FELT, USE <br /> GALV.ROOFING NAILS <br /> # 11 OR # 12, 1" X 3/8" @ <br />12" O.C. <br /> FIELD & 6" O.C. ON THE <br />EDGE. <br />(FIRE RETARDANT). <br />FINISH ELEVATIONS <br />DETAILS <br />TYPE OF ROOF: SHINGLE <br />MANUFACTURER: OWENS CORNING <br />COLOR:SEE ELEVATIONS <br />SOLAR REFLECTANCE: 0.29 <br />THERMAL EMITTANCE: 0.87 <br />COLOR:SEE DETAIL <br />CLASS "A", ICC-ES AC438, DURATION <br />PRODUCT LINE, OVER 2-LAYERS OF 30# <br />ASTM D 226 TYPE I FELT PAPER MIN. <br />UNDERLAYMENT TO BE INSTALLED IN <br />COMPLIANCE WITH 2022 CRC SECTION <br />R905.2.7 <br />8 <br />4 <br />5 <br />END GABLE VENT <br />NEW <br />FCU IN ATTIC <br />SPACE <br />RIDGE <br />OWNER/CLIENT <br />PROJECT LOCATION <br />PROJECT TITLE <br />SHEET TITLE <br />DATE <br />AS SHOWN <br />SCALE <br />02 / 24 <br />D R A F T I N G S E R V I C E <br />TE <br />L <br /> <br />: <br /> <br /> <br /> <br />( <br />9 <br />5 <br />1 <br />) <br /> <br />9 <br />9 <br />2 <br />- <br />7 <br />2 <br />3 <br />4 <br />ju <br />a <br />n <br />. <br />g <br />o <br />n <br />z <br />a <br />l <br />e <br />z <br />. <br />1 <br />9 <br />7 <br />1 <br />@ <br />h <br />o <br />t <br />m <br />a <br />i <br />l <br />. <br />c <br />o <br />m <br />FI <br />N <br />. <br />G <br />. <br />S <br />& <br /> <br />P <br />WA <br />R <br />D <br />F. <br />M <br />. <br />C <br />. <br />FR <br />. <br /> <br />D <br />R <br />. <br /> <br />VL <br />. <br /> <br />S <br />L <br />. <br />KE <br />E <br />P <br /> <br />L <br />A <br />B <br />E <br />L <br /> <br />O <br />N <br /> <br />T <br />H <br />E <br /> <br />W <br />A <br />T <br />E <br />R <br /> <br />H <br />E <br />A <br />T <br />E <br />R <br />3. <br /> <br /> <br /> <br />W <br />A <br />T <br />E <br />R <br /> <br />T <br />O <br /> <br />B <br />E <br /> <br />5 <br />0 <br /> <br />G <br />A <br />L <br />L <br />O <br />N <br />S <br /> <br />M <br />I <br />N <br />. <br />1. <br /> <br /> <br /> <br />A <br />L <br />L <br /> <br />H <br />O <br />R <br />I <br />Z <br />O <br />N <br />T <br />A <br />L <br /> <br />C <br />E <br />I <br />L <br />I <br />N <br />G <br /> <br />D <br />R <br />Y <br />W <br />A <br />L <br />L <br /> <br />A <br />P <br />P <br />L <br />I <br />E <br />D <br /> <br />T <br />O <br /> <br />T <br />R <br />U <br />S <br />S <br />E <br />S <br />2. <br /> <br /> <br /> <br />A <br />L <br />L <br /> <br />E <br />X <br />T <br />E <br />R <br />I <br />O <br />R <br /> <br />W <br />I <br />N <br />D <br />O <br />W <br />S <br /> <br />T <br />O <br /> <br />B <br />E <br /> <br />W <br />H <br />I <br />T <br />E <br />. <br /> <br />R <br />E <br />F <br />E <br />R <br /> <br />T <br />O <br /> <br />P <br />L <br />A <br />N <br /> <br />FO <br />R <br /> <br />S <br />I <br />Z <br />E <br /> <br />A <br />N <br />D <br /> <br />E <br />X <br />T <br />E <br />R <br />I <br />O <br />R <br /> <br />E <br />L <br />E <br />V <br />A <br />T <br />I <br />O <br />N <br /> <br />F <br />O <br />R <br /> <br />A <br />L <br />L <br /> <br />B <br />R <br />E <br />A <br />K <br />- <br />U <br />P <br />S <br />SH <br />A <br />L <br />L <br /> <br />B <br />E <br /> <br />5 <br />/ <br />8 <br />" <br /> <br />G <br />Y <br />P <br />S <br />U <br />M <br /> <br />B <br />O <br />A <br />R <br />D <br />SI <br />N <br />G <br />L <br />E <br /> <br />H <br />U <br />N <br />G <br />OP <br />T <br />I <br />O <br />N <br />A <br />L <br />SL <br />I <br />D <br />E <br />R <br /> <br />O <br />R <br /> <br />S <br />L <br />I <br />D <br />I <br />N <br />G <br />FI <br />X <br />E <br />D <br /> <br />G <br />L <br />A <br />S <br />S <br />CE <br />I <br />L <br />I <br />N <br />G <br />EL <br />E <br />V <br />A <br />T <br />I <br />O <br />N <br />F. <br />G <br />. <br />S. <br />H <br />. <br />SL <br />. <br />OP <br />T <br />. <br />CL <br />' <br />G <br />. <br />EL <br />E <br />V <br />. <br />W/ <br />SH <br />E <br />L <br />F <br /> <br />& <br /> <br />P <br />O <br />L <br />E <br />FR <br />E <br />N <br />C <br />H <br /> <br />D <br />O <br />O <br />R <br />FL <br />O <br />O <br />R <br /> <br />M <br />A <br />T <br />E <br />R <br />I <br />A <br />L <br /> <br />C <br />H <br />A <br />N <br />G <br />E <br />FI <br />N <br />I <br />S <br />H <br /> <br />G <br />R <br />A <br />D <br />E <br />WI <br />T <br />H <br />WA <br />R <br />D <br />R <br />O <br />B <br />E <br />VI <br />N <br />I <br />L <br /> <br />S <br />L <br />I <br />D <br />E <br />R <br />G& <br />S <br /> <br />A <br />r <br />c <br />h <br />i <br />t <br />e <br />c <br />t <br />u <br />r <br />a <br />l <br /> <br />D <br />e <br />s <br />i <br />g <br />n <br /> <br />a <br />n <br />d <br /> <br />P <br />l <br />a <br />n <br />n <br />i <br />n <br />g <br />JU <br />A <br />N <br /> <br />G <br />O <br />N <br />Z <br />A <br />L <br />E <br />Z <br />12 <br />5 <br />9 <br />4 <br /> <br />M <br />i <br />c <br />h <br />i <br />g <br />a <br />n <br /> <br />S <br />t <br />, <br /> <br />G <br />r <br />a <br />n <br />d <br /> <br />T <br />e <br />r <br />r <br />a <br />c <br />e <br />, <br /> <br />C <br />A <br /> <br />9 <br />2 <br />3 <br />1 <br />3 <br />AB <br />B <br />R <br />E <br />V <br />I <br />A <br />T <br />I <br />O <br />N <br />S <br /> <br />TY <br />P <br />I <br />C <br />A <br />L <br /> <br /> <br />N <br />O <br />T <br />E <br />S <br />PL <br />A <br />N <br />S <br /> <br />P <br />R <br />E <br />P <br />A <br />R <br />E <br /> <br />B <br />Y <br />: <br />SHEET <br />Mailing address: <br />JC IMP EXP INC <br />14881 ALDER LN, TUSTIN, <br />CA 92780-6742 <br />PROPOSED ROOF PLAN <br />2 <br />TYP 2'-0" <br />2' <br />- <br />0 <br />" <br />2 <br />TYP <br />2'-0" <br />2' <br />- <br />0 <br />" <br />END GABLE VENT <br />NEW <br />2'-0" <br />2' <br />- <br />0 <br />" <br />2'-0" <br />2' <br />- <br />0 <br />" <br />9 <br />8 <br />4 <br />5 <br />FCU IN ATTIC <br />SPACE <br />UNIT # 100 <br />1 WWW.CERTAINTEED.COM <br /> -GABLE END ATTIC VENTS 12" X 18" <br />2.784 <br />1.77 <br />0 <br />4.4 <br />EACH VENT= 100 SQ. IN. AS PER VERDE INDUSTRIES <br />= SQ.FT <br />150 S.F. <br />VENTILATION NEEDED <br /> = -EAVE BLOCKS <br />= SQ.FT <br /> - DORMER ATTIC VENTS 38" X 26" <br />144 <br /> X 9.42 <br /> LINEAR FT. OF EAVE <br />EACH BLOCK = 9.42" <br />TOTAL VENTILLATION PROVIDED = SQ. FT. <br />3 <br />0 <br />1 <br />0 <br /> X 144" <br />1 <br />144 <br /> X 100" <br />= SQ.FT <br />144 <br /> VENT SQ. IN. AS PER AIR VENT INC. (CERTAINTEED CO.) <br /> -GABLE END ATTIC VENTS 12" X 14" <br />5.55 <br />(3-2"DIA. HOLES) <br />2 <br />81 <br />660 <br />27 <br /> MODEL NO. 100ASD WWW.VERDEINDUSTRIES.COM <br />144 <br /> X 100" <br />27 <br /> S.F. <br />= SQ.FT. <br />VENTILATION PROVIDED <br /> S.F. OF VENTILATION REQUIRED <br />UNIT # 101 <br />DORMER ATTIC VENT <br />38" X 26" <br />NEW <br />DORMER ATTIC VENT <br />38" X 26" <br />NEW <br />RI <br />D <br />G <br />E <br />RI <br />D <br />G <br />E <br />DORMER ATTIC VENT <br />38" X 26" <br />NEW <br />DORMER ATTIC VENT <br />38" X 26" <br />NEW <br />DORMER ATTIC VENT <br />38" X 26" <br />NEW <br />DORMER ATTIC VENT <br />38" X 26" <br />NEW <br />DORMER ATTIC VENT <br />38" X 26" <br />NEW <br />DORMER ATTIC VENT <br />38" X 26" <br />NEW 9 <br />10:12 SLOPE <br />ROOF SHINGLES <br />NEW <br />10:12 SLOPE <br />ROOF SHINGLES <br />NEW <br />10 <br />: <br />1 <br />2 <br /> <br />S <br />L <br />O <br />P <br />E <br />RO <br />O <br />F <br /> <br />S <br />H <br />I <br />N <br />G <br />L <br />E <br />S <br />NE <br />W <br />10 <br />: <br />1 <br />2 <br /> <br />S <br />L <br />O <br />P <br />E <br />RO <br />O <br />F <br /> <br />S <br />H <br />I <br />N <br />G <br />L <br />E <br />S <br />NE <br />W <br />RIDGE <br />10 <br />: <br />1 <br />2 <br /> <br />S <br />L <br />O <br />P <br />E <br />RO <br />O <br />F <br /> <br />S <br />H <br />I <br />N <br />G <br />L <br />E <br />S <br />NE <br />W <br />10 <br />: <br />1 <br />2 <br /> <br />S <br />L <br />O <br />P <br />E <br />RO <br />O <br />F <br /> <br />S <br />H <br />I <br />N <br />G <br />L <br />E <br />S <br />NE <br />W <br />1 <br />TYP <br />1' <br />- <br />6 <br />" <br />2'-0" <br />1' <br />- <br />6 <br />" <br />5:12 SLOPE <br />ROOF SHINGLES <br />NEW <br />2'-0"2'-0" <br />5:12 SLOPE <br />ROOF SHINGLES <br />NEW <br />HEADER / BEAM <br />PER STRUCT PLANS <br />COVER PATIO CEILING <br />PER R337.7.6 <br />PORCH CEILINGS SHALL HAVE FIRE RESISTIVE RATING OF ONE HOUR ON THE UNDERSIDE. <br />(2)5/8" TYPE X GYPSUM BOARD <br /> PER TABLE 722.2.1.4(2) CBC-2022 <br />2 LAYERS OF GRADE <br />"D" PAPER <br />PLYWOOD SHEATHING <br />STUCCO FINISH O/ <br />CEMENT PLASTER O/ <br />(WHERE OCCURS) (1)5/8" TYPE X GYPSUM BOARD <br /> PER TABLE 72222.1.4(2) CBC-2022 <br />(2)5/8" TYPE X GYPSUM BOARD <br /> PER TABLE 722.2.1.4(2) CBC-2022 <br />HARDY FIBERGLASS CEMENT <br />1" <br />4" <br />FLASHING PROFILE <br />2 LAYERS OF 15LB <br />FELT PAPER <br />DRIP FLASHING <br />CLASS "A" ASPHALT SHINGLE ROOF <br />PLYWOOD SHEATHING <br />2 <br />A7 <br />2 <br />A7 <br />DOWNSPOUT <br />GUTTER AND <br />GLAVANIZED <br />SHEET METAL <br />2 LAYERS OF 15LB <br />FELT PAPER <br />INSULATION PER T-24 CALC's <br />1/2" DRYWALL <br />2 LAYERS OF GRADE "D" PAPER <br />PLYWOOD SHEATHING <br />STUCCO FINISH O/ <br />CEMENT PLASTER O/ <br />(WHERE OCCURS) <br />R-XX BATT <br />INSULATION SEE T-24 CLC's <br />R-XX BATT <br />DRIP FLASHING <br />(PAINTED) <br />EAVE & EXTERIOR WALLS DETAIL <br />1" <br />4" <br />FLASHING PROFILE <br />Roof gutters shall <br />be designed to <br />prevent the <br />accumulation of <br />leaves and debris <br />(1)5/8" TYPE X GYPSUM BOARD <br /> PER TABLE 722.2.1.4(2) CBC-2022 <br />CLASS "A" ASPHALT SHINGLE ROOF <br />PLYWOOD SHEATHING <br />2 LAYERS OF GRADE <br />"D" PAPER <br />STUCCO FINISH O/ <br />CEMENT PLASTER O/ <br />HARDY FIBERGLASS CEMENT <br />HARDY FIBERGLASS CEMENT <br />CRC TABLE R302.1 (1) <br />EAVES WITHIN 5' OF PROPERTY LINE SHALL HAVE FIRE RESISTIVE RATING OF ONE HOUR ON THE UNDERSIDE. <br />1 <br />A7 <br />1 <br />A7 <br />PROPOSED (2) TWO NEW <br />ADU's. <br />5:12 SLOPE <br />ROOF SHINGLES <br />NEW <br />5:12 SLOPE <br />ROOF SHINGLES <br />NEW <br />1' <br />- <br />6 <br />" <br />1' <br />- <br />6 <br />" <br />B <br />A-10 <br />A <br />A-10 <br />2010 AND 2012 N BUSH <br />AVE #100 AND #101, SANTA <br />ANA, CA 92706-2818 <br />01-A-7 <br />RE <br />G <br />I <br />STERED PROF E S S IONAL ENGI <br />NE <br />ER <br />STATE OF CA L IFORNIA <br />NO. C-31397 <br />EXP. 12/31/2024 <br />C I V I L <br />LEO A . A GUILERA <br />READY SOLAR ZONEREADY SOLAR ZONE <br />2010 & 2012 N Bush Ave, <br />#100 and #1012/21/2025