Laserfiche WebLink
GENERAL NOTES <br />1. PROVIDE WARRANTY TO INCLUDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE <br />PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR AFTER SUBSTANTIAL COMPLETION OR <br />OWNER ACCEPTANCE OF COMPLETED PROJECT, WHICHEVER IS LATER. <br />2. COMPLETED INSTALLATION SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND FEDERAL <br />CODES AND ORDINANCES, INCLUDING NFPA-90A, NFPA-96 AND NFPA-101. <br />3. DUCTWORK SHALL BE MANUFACTURED AND INSTALLED PER SMACNA 1" PRESSURE CLASS <br />GUIDELINES AND DETAILS. DUCTWORK SIZES SHOWN INDICATE INSIDE CLEAR DIMENSIONS. <br />CONCEALED DUCTWORK SHALL BE INSULATED WITH 2" THICK DUCT WRAP (R-8 MIN). INSULATE <br />CEILING MOUNTED DIFFUSER BACKS. VAPOR BARRIER SHALL BE MAINTAINED CONTINUOUS AND <br />SEAMS SHALL BE SEALED. DUCTWORK SHALL BE INSTALLED ABOVE SUSPENDED CEILING <br />WHERE PROVIDED. EXPOSED DUCTWORK SHALL BE G90 GALVANIZED STEEL. CLEAN OFF <br />MARKS, APPLIED STICKERS AND RESIDUAL OIL. VINEGAR WASH BEFORE PAINTING OF DUCT. <br />4. CONNECT DUCTS TO FANS AND OTHER AIR DISTRIBUTION EQUIPMENT USING MECHANICAL <br />FASTENERS WITH SEALS, MASTIC OR GASKETS. <br />5. SUPPLY AND RETURN AIR DUCT DROPS FROM HVAC EQUIPMENT SHALL BE ISOLATED FROM <br />UNIT VIBRATION WITH FLEXIBLE DUCT CONNECTORS. <br />6. INSULATED FLEXIBLE DUCT MAY BE USED IN MAXIMUM LENGTHS AS SPECIFIED FROM RIGID <br />METAL DUCT TO DIFFUSER CONNECTION. FLEXIBLE DUCT SHALL BE CLASS 1 FLEXIBLE AIR DUCT <br />WITH INSULATION AND VAPOR BARRIER, AND SHALL MEET UL 181. <br />7. WHERE PLENUM DIFFUSERS ARE CHOSEN WITH INTEGRAL BALANCING DAMPERS SPIN -IN <br />CONNECTIONS MAY EXCLUDE DAMPERS. <br />8. CONTRACTOR SHALL RECEIVE AND INSTALL ROOF MOUNTED CONDENSING UNITS. PROVIDE <br />MOUNTING RAILS. REFER TO STRUCTURAL PLANS FOR LOCATIONS OF ROOF MOUNTED <br />EQUIPMENT, CURB, AND RAIL DETAILS. EQUIPMENT SHALL BE MECHANICALLY FASTENED TO <br />RAILS. RAILS SHALL BE FASTENED TO STRUCTURE. STRUCTURE, CONNECTIONS, AND <br />SUPPORTS SHALL MEET STRUCTURAL WIND LOAD REQUIREMENTS. CONSULT STRUCTURAL <br />ENGINEER AS NEEDED TO DETERMINE REQUIREMENTS. <br />9. CURBS SHALL BE ONE PIECE WELDED AND INSULATED 18 GAUGE STEEL, WITH RIGID <br />INSULATION GLUED TO INSIDE OF CURB. REFER TO SHEET M2.0 FOR ADDITIONAL INFORMATION. <br />10. RETURN DUCTWORK FROM HVAC EQUIPMENT AND RECTANGULAR GENERAL EXHAUST <br />(RESTROOM) DUCTWORK SHALL BE LINED WITH 1" DUCT LINER. <br />11. PROVIDE STENCIL LABELS ON HVAC EQUIPMENT AND EXHAUST FANS. LABELS SHALL HAVE 2" <br />HIGH LETTERS ON UNIT SIDE ACCESS PANEL. EXPOSED GAS PIPING AND FITTINGS SHALL BE <br />PAINTED WITH SAFETY YELLOW PAINT DESIGNED FOR BLACK IRON. <br />12. ENSURE GAS LINES AND CONDENSATE DRAIN LINES DO NOT IMPEDE HVAC EQUIPMENT <br />DOORS/PANELS. FOLLOW MANUFACTURER GUIDELINES FOR REQUIRED CLEARANCES. <br />13. REFER TO "H" AND "W" SHEETS FOR SPECIFIC HOOD AND FAN INFORMATION AND FIELD WIRING <br />DIAGRAMS. CONTRACTOR SHALL PROVIDE LOW VOLTAGE WIRING FROM FAN CONTROL PANEL <br />TO HVAC EQUIPMENT, REMOTE SENSORS AND SMOKE DETECTORS. CONTRACTOR SHALL <br />PROGRAM THERMOSTAT FOLLOWING WENDY'S STANDARDS. REFER TO PROGRAMMING <br />INSTRUCTIONS PROVIDED WITH MODULAR PANEL SYSTEM. <br />14. CONTRACTOR SHALL TEST, CHECK, AND BALANCE HVAC EQUIPMENT, EXHAUST HOODS, AND <br />EXHAUST FANS. SET EXHAUST FANS AND DIFFUSERS TO SPECIFIED AIR FLOW RATES. <br />CONTRACTOR SHALL COMPLETE WENDY'S REQUIRED TEST FORMS FOR HVAC EQUIPMENT, <br />HOODS, AND FAN CONTROL SYSTEM. REFER TO M4.0 FOR TESTING AND BALANCE <br />REQUIREMENTS. <br />15. CONTRACTOR SHALL COMPLETE ROOFTOP UNIT START UP HVAC EQUIPMENT FORMS AND <br />RETURN TO MANUFACTURER TO SCHEDULE EQUIPMENT OPERATION CHECK (EOC). CONSULT <br />CONTACT OR ALLOW 5 BUSINESS DAYS TO SCHEDULE EOC. CONTRACTOR IS RESPONSIBLE FOR <br />CORRECTING DEFICIENCIES NOTED IN EOC PRIOR TO START OF TESTING AND BALANCING. <br />16. CONTRACTOR SHALL VERIFY THAT BUILDING IS WEATHER TIGHT, HVAC EQUIPMENT POWERED <br />AND CALIBRATED, THERMOSTATS PROGRAMMED, FANS OPERATIONAL, EOC COMPLETE, <br />DIFFUSERS AND CEILING TILE INSTALLED, EXHAUST FAN SPEEDS CALIBRATED, AND NEW <br />FILTERS INSTALLED IN HVAC EQUIPMENT PRIOR TO TESTING AND BALANCING. CONTRACTOR <br />SHALL CORRECT OPERATIONAL OR PERFORMANCE DEFICIENCIES FOUND DURING TESTING AND <br />BALANCING. <br />17. COMPLETE SMOKE CAPTURE TEST(S), AS REQUIRED, IN ACCORDANCE WITH INTERNATIONAL <br />MECHANICAL CODE IMC 507, ASHRAE 154 VENTILATION FOR COMMERCIAL COOKING <br />OPERATIONS, AND HOOD MANUFACTURER STANDARDS. KITCHEN EQUIPMENT SHALL BE AT <br />OPERATING TEMPERATURES WITH HVAC EQUIPMENT OPERATIONAL. TEST USING SMOKE <br />CANDLES OR SMOKE PUFFERS. SMOKE BOMBS SHALL NOT BE USED. <br />18. EQUIPMENT WITH SYMBOL TAGS ON PLANS, REFER TO ASSOCIATED EQUIPMENT SCHEDULES <br />FOR REQUIREMENTS. TAGGED EQUIPMENT IS RESPONSIBILITY OF CONTRACTOR TO PROVIDE <br />UNLESS OTHERWISE NOTED. <br />19. CONTRACTOR IS RESPONSIBLE FOR PROVIDING MANUAL BALANCE DAMPERS IN DUCT <br />BRANCHES IN ACCESSIBLE LOCATION ABOVE CEILING. <br />GREASE DUCTS NOTES: <br />1. FIELD APPLIED OR FACTORY BUILT GREASE DUCT ENCLOSURE SHALL BE INSTALLED PER THE <br />LATEST MANUFACTURER'S INSTALLATION INSTRUCTIONS AND IN COMPLIANCE WITH TERMS OF <br />ITS LISTING. <br />2. ALL END CUTS OR CUTS IN THE FOIL JACKET OF FIELD APPLIED GREASE DUCT ENCLOSURE <br />SHALL BE SEALED PER THE MANUFACTURER'S RECOMMENDATIONS. <br />3. ALL INSTALLATIONS SHALL BE COMPLETELY ACCESSIBLE FOR VISUAL INSPECTION. <br />4. AT TIME OF INSPECTION, THE FIELD APPLIED OR FACTORY BUILT GREASE DUCT ENCLOSURE <br />INSTALLATION INSTRUCTIONS SHALL BE MADE AVAILABLE AT THE JOB SITE. <br />FIRE NOTES: <br />1. FIRE DEPARTMENT APPROVAL SHALL BE REQUIRED ON FIRE PROTECTION SYSTEM FOR GREASE <br />HOODS AND DUCTS AS REQUIRED BY SECTION 513 OF THE CALIFORNIA MECHANICAL CODE AND <br />AS REQUIRED BY THE FIRE CODE. <br />2. ALL FIRE -EXTINGUISHING SYSTEMS SHALL BE INTERCONNECTED TO THE FUEL OR CURRENT <br />SUPPLY SO THAT THE FUEL OR CURRENT IS AUTOMATICALLY SHUT OFF TO ALL EQUIPMENT <br />UNDER THE HOOD WHEN THE SYSTEM IS ACTIVATED. <br />3. OWNER OF ESTABLISHMENT SHALL BE RESPONSIBLE FOR CLEANLINESS, MAINTENANCE, AND <br />INSPECTION OF KITCHEN EXHAUST SYSTEM, FIRE PROTECTION, AND COOKING EQUIPMENT. <br />4. A DRAWING OF THE EXHAUST SYSTEM(S) INSTALLATION ALONG WITH A COPY OF OPERATING <br />INSTRUCTIONS FOR SUBASSEMBLIES AND COMPONENTS USED IN THE EXHAUST SYSTEM(S), <br />INCLUDING ELECTRICAL SCHEMATICS, SHALL BE AVAILABLE ON THE PREMISES. <br />5. ALL SEAMS, JOINTS, AND PENETRATIONS OF THE HOOD ENCLOSURE THAT DIRECT AND <br />CAPTURE GREASE -LADEN VAPORS AND EXHAUST GASES SHALL HAVE A LIQUID TIGHT <br />CONTINUOUS EXTERNAL WELD TO THE LOWER OUTERMOST PERIMETER OF THE HOOD. <br />6. PRIOR TO THE USE OR CONCEALMENT OF A PORTION OF A GREASE DUCT SYSTEM, A LEAKAGE <br />TEST SHALL BE PERFORMED TO DETERMINE THAT ALL WELDED JOINTS AND SEAMS ARE LIQUID <br />TIGHT. <br />7. PERFORMANCE, CAPTURE AND CONTAINMENT TESTS SHALL BE PERFORMED UPON <br />INSTALLATION BEFORE FINAL. TEST DATA AND PERFORMANCE TEST RESULTS SHALL BE <br />DISPLAYED AND BE AVAILABLE UPON REQUEST. <br />8. HOOD EXHAUST FAN SHALL CONTINUE TO OPERATE AFTER THE EXTINGUISHING SYSTEM HAS <br />BEEN ACTIVATED, UNLESS FAN SHUTDOWN IS REQUIRED BY A LISTED COMPONENT OF THE <br />VENTILATION SYSTEM. <br />9. TYPE I HOODS SHALL BEAR A LABEL INDICATING THE EXHAUST FLOW RATE IN CUBIC FEET PER <br />MINUTE PER LINEAL FOOT. <br />10. LICENSED AIRFLOW CONTRACTOR SHALL PROVIDE GREASE EXHAUST SYSTEM AIR BALANCE <br />REPORT TO INSPECTOR PRIOR TO FINAL. <br />SYMBOLS & ABBREVIATIONS <br />LEGEND <br />OT <br />THERMOSTAT <br />AFF <br />O <br />TEMPERATURE/HUMIDITY SENSOR <br />AHJ <br />RT <br />REMOTE TEST STATION <br />CFM <br />® <br />DUCT SMOKE DETECTOR <br />EA <br />® <br />SUPPLY DUCT <br />ESP <br />RETURN DUCT <br />FCLC <br />® <br />EXHAUST DUCT <br />HZ <br />J <br />MANUAL BALANCE DAMPER <br />MOCP <br />NFPA <br />NC <br />SUPPLY DIFFUSER <br />OA <br />RETURN GRILLE <br />OAU <br />EXHAUST GRILLE <br />FTU <br />DUMP BOX DIFFUSER <br />SA <br />TYP <br />`EEET <br />SIDE WALL MOUNTED SUPPLY REGISTER <br />WC <br />ROOFTOP UNIT SCHEDULE HVC n <br />OUTSIDEAIR TEMPERATURE: 95°FSUMMER <br />S/A FAN <br />HEATING <br />HEATING <br />AFUE <br />COOLING <br />CA <br />WEIGHT <br />MANUFACTURER <br />UNIT <br />MODEL NO. <br />TONS <br />VOLT <br />INPUT <br />OUTPUT <br />% <br />OUTPUT <br />EER <br />IEER <br />MCA <br />MOCP <br />CFM <br />LBS <br />NOTES <br />BHP <br />CFM <br />ESP <br />TRANE <br />ALL AS <br />GAS HEAT <br />RTU-1 <br />YHK090 <br />7.5 <br />1.2 <br />3000 <br />1.0 <br />208/3/60 <br />120 MBH <br />97.2 MBH <br />81 <br />90 MBH <br />12.1 <br />17.7 <br />43 <br />50 <br />1200 <br />1400 <br />APPLICABLE <br />TRANE <br />ALL AS <br />GAS HEAT <br />RTU-2 <br />YHK120 <br />10 <br />1.9 <br />4000 <br />1.0 <br />208/3/60 <br />150 MBH <br />121.5 MBH <br />81 <br />120 MBH <br />11.6 <br />16.3 <br />57 <br />80 <br />1700 <br />1700 <br />APPLICABLE <br />UNITS ARE TO BE COMPLETE WITH THE FOLLOWING: <br />1. FACTORY CURBS FOR CONTRACTOR TO INSTALL. CURB HEIGHTS SHALL PROVIDE FOR LOCAL SNOW ACCUMULATION, <br />CURBS SHALL BE 14 INCHES HIGH MINIMUM. CONTRACTOR TO CONFIRM CURB HEIGHTS AND STRENGTH WITH <br />STRUCTURAL ENGINEER TO CONFORM TO LOCAL SNOW ACCUMULATION, SEISMIC AND WIND LOADS, INCLUDING <br />FASTENER CONSTRUCTION AND INSTALLATION METHODS. <br />2. FACTORY MOUNTED AND WIRED NON -FUSED DISCONNECT. <br />3. WEATHER HOOD WITH BIRD SCREEN AT UNIT OUTDOOR AIR INLET. <br />4. SET MINIMUM OUTDOOR AIR AS SPECIFIED ABOVE. OUTDOOR AIR DAMPER SHALL FULLY CLOSE ON UNIT SHUTDOWN. <br />5. VFD SUPPLY FAN WITH SINGLE ZONE VARIABLE AIR VOLUME CONTROL WITH OUTDOOR AIR CFM COMPENSATION. <br />6. FACTORY MOUNTED AND WIRED DRAIN PAN CONDENSATE OVERFLOW SWITCH. <br />7. OUTDOOR AIR ECONOMIZER WITH SINGLE ENTHALPY CONTROL AND ECONOMIZER FAULT DETECTION AND <br />DIAGNOSTICS. PROVIDE UNIT WITH BAROMETRIC RELIEF. PROVIDE POWER RELIEF WHERE LOCAL AHJ REQUIRES. <br />8. FACTORY INSTALLED NON POWERED CONVENIENCE OUTLET. <br />9. STAINLESS STEEL HEAT EXCHANGERS AND FULLY MODULATING GAS BURNERS. <br />10. LOUVERED CONDENSER COIL HAIL GUARD. <br />11. FACTORY INSTALLED HOT GAS REHEAT COIL FOR DEHUMIDIFICATION CONTROL. <br />12. REFER TO DRAWINGS G2.1 FOR MANUFACTURER CONTACT INFORMATION. <br />13. PROVIDE MERV-13 FILTERS. <br />FAN SCHEDULE (3-PLATEN GRILLE <br />SETUP) <br />ACCESSORIES <br />MARK <br />AIRFLOW <br />STATIC <br />PRESSURE <br />MOTOR <br />HORSEPOWER <br />ELECTRICAL <br />(VOLTAGE / <br />MODEL <br />WEIGHT <br />REMARKS <br />BACK <br />(CFM) <br />(IN.WC.) <br />(HP) <br />PHASE) <br />DRAFT <br />BIRD <br />DISCONNECT <br />SPEED <br />DIRECT <br />LBS <br />DAMPER <br />SCREEN <br />SWITCH <br />CONTROL <br />DRIVE <br />EF-1 <br />1100 <br />1.25 <br />3/4 <br />208/1 <br />X <br />X <br />X <br />DU85HFA <br />90 <br />1-3 <br />EF-2 <br />1500 <br />1.25 <br />3/4 <br />208/1 <br />X <br />X <br />X <br />DU85HFA <br />90 <br />1-3 <br />EF-3 <br />300 <br />0.340 <br />1/6 <br />115/1 <br />X <br />I X <br />I X <br />X <br />X <br />DU10HFA <br />49 <br />1A <br />1. FANS, CURBS, AND NFPA FAN HINGES AS APPLICABLE SHALL BE SUPPLIED AS PART OF EXHAUST HOOD PACKAGE. <br />2. PROVIDE UL APPROVED GREASE RATING. <br />3. EXHAUST FAN IS CONNECTED TO HOOD ON SWITCH. FAN SHALL <br />OPERATE AT ALL TIMES WHILE RESTAURANT IS OPEN. <br />4. FAN TO OPERATE FROM SMART BREAKER IN FCLC SYSTEM. <br />ABOVE FINISHED FLOOR <br />AUTHORITY HAVING JURISDICTION <br />CUBIC FEET PER MINUTE <br />EXHAUST AIR <br />EXTERNAL STATIC PRESSURE <br />FAN CONTROL LIGHTING CONTROL <br />FREQUENCY <br />MAXIMUM OVERCURRENT PROTECTION <br />NATIONAL FIRE PROTECTION ASSOCIATION <br />NOISE CRITERIA <br />OUTSIDE AIR <br />OUTDOOR AIR UNIT <br />FAN TERMINAL UNIT <br />SUPPLY AIR <br />TYPICAL <br />WATER COLUMN <br />AIR CURTAIN SCHEDULE <br />ELECTRICAL <br />MANUFACTURER <br />AND <br />CFM <br />MAX <br />WEIGHT <br />NOTES <br />MODEL NUMBER <br />FPM <br />VOLTS <br />PHASE <br />MAX <br />AMPS <br />HP <br />LBS <br />WATTS <br />MARS <br />AC-1 <br />1418 <br />4865 <br />120 <br />1 <br />510 <br />5.1 <br />1/2 <br />70 <br />1 AND 2 <br />STD242 <br />MARS <br />AC-2 <br />1200 <br />1800 <br />120 <br />1 <br />- <br />2.4 <br />1/6 <br />40 <br />1 AND 2 <br />LPV248 <br />NOTE: 1. INTERLOCK AIR CURTAIN WITH LIMIT SWITCH ON DOOR TO ACTIVATE THE AIR CURTAIN <br />WHEN DOOR OPENS. BY ELECTRICAL CONTRACTOR. <br />2. AIR CURTAIN SHALL PROVIDE AIR AT A VELOCITY OF AT LEAST 750 FEET PER <br />MINUTE MEASURED AT 3'-0" ABOVE THE FLOOR. <br />AIR DEVICE SCHEDULE <br />SYMBOLS & ABBREVIATIONS LEGEND <br />OT <br />THERMOSTAT <br />AFF <br />O <br />TEMPERATURE/HUMIDITY SENSOR <br />AHJ <br />RT <br />REMOTE TEST STATION <br />CFM <br />® <br />DUCT SMOKE DETECTOR <br />EA <br />® <br />SUPPLY DUCT <br />ESP <br />RETURN DUCT <br />FCLC <br />® <br />EXHAUST DUCT <br />HZ <br />MOCP <br />J <br />MANUAL BALANCE DAMPER <br />NFPA <br />NC <br />SUPPLY DIFFUSER <br />CA <br />z <br />RETURN GRILLE <br />OAU <br />EXHAUST GRILLE <br />FTU <br />II„ Ih <br />DUMP BOX DIFFUSER <br />SA <br />lur <br />TYP <br />rE=P <br />SIDE WALL MOUNTED SUPPLY REGISTER <br />WC <br />COMMERCIAL KITCHEN NOTES <br />HVAC, FIRE PROTECTION AND PLUMBING <br />CITY OF SANTA ANA <br />�v <br />ABOVE FINISHED FLOOR <br />AUTHORITY HAVIN <br />JURISDICTION <br />CUBIC FEET PER MINUTE <br />EXHAUST AIR <br />R P <br />EXTERNAL STATIC F <br />RESS[JREO <br />FAN CONTROL LIGH <br />ING CONTROL <br />FREQUENCY <br />MAXIMUM OVERCUF <br />RENT <br />��PROTECTION <br />r <br />dlf <br />NATIONAL FIRE PR <br />EC�ImClSl�IA <br />NOISE CRITERIA <br />Date. <br />OUTSIDE AIR <br />OUTDOOR AIR UNIT <br />FAN TERMINAL UNIT <br />SUPPLY AIR <br />TYPICAL <br />WATER COLUMN <br />NEW EQUIPMENT, PIPING, ETC. SHALL BE INSPECTED AND LOCATED BEFORE AND AFTER NEW CONSTRUCTION. DETAILS OF <br />PERFORMANCE/CONDITION/SIZING AND LOCATION SHALL BE SUPPLIED TO ENGINEER AND OWNER. AIR CAPACITIES FOR <br />SUPPLY AND EXHAUST SYSTEMS SHALL BE MEASURED AT GRILLES TO DETERMINE IF DESIGN AIR FLOW RATES NOTED ON <br />PLANS CAN BE MET. EXTRA WORK REQUIRED TO ABOVE MENTIONED SHALL BE DETERMINED PRIOR TO NEW CONSTRUCTION <br />CONTRACTOR TO ALLOW FOR INSPECTION IN THEIR PRICE INCLUDING WELD INSPECTIONS, AIR FLOW RATE MEASUREMENT, <br />SCANNING AND CAMERA SCOPE TO EXISTING BURIED DRAINS. NO EXTRAS SHALL BE ALLOWED ONCE NEW CONSTRUCTION <br />STARTS. <br />CONTRACTOR SHALL OBTAIN LATEST SPREAD SHEETS/SHOP DRAWINGS FROM KITCHEN CONSULTANT FOR APPLIANCE AND <br />HVAC REQUIREMENTS PRIOR TO ROUGH -IN WORK. <br />CONTRACTOR SHALL PROVIDE WIRING AND CONTROLS AS NOTED ON WIRING NOTES IN EQUIPMENT SCHEDULE. <br />CONTRACTOR SHALL: <br />1. CONSTRUCT ENTIRE KITCHEN HOOD EXHAUST SYSTEM TO NFPA 96 STANDARDS. <br />2. REFER TO ARCHITECTURAL AND/OR INTERIOR DESIGN DRAWINGS FOR HOOD LOCATION AND APPROVED KITCHEN HOOD <br />SHOP DRAWINGS FOR EXACT LOCATION OF EXHAUST DUCT CONNECTIONS. <br />3. REFER TO LATEST KITCHEN EQUIPMENT DRAWINGS AND APPROVED SHOP DRAWINGS FOR FINAL GAS, PLUMBING AND <br />DRAINAGE HOOK UP SIZES AND LOCATIONS. CONTRACTOR TO REFER TO MANUFACTURERS INSTALLATION MANUALS AND <br />RECOMMENDATIONS AND PROVIDE NECESSARY EQUIPMENT, VALVES, PIPING, ETC. TO SUIT. EXACT LOCATION OF <br />EQUIPMENT ROUGH -INS SHALL BE DETERMINED AT SITE. CHANGES TO KITCHEN EQUIPMENT LINE UP MUST BE REPORTED <br />TO ENGINEER, FOOD SERVICES VENDOR, AND ARCHITECT PRIOR TO INSTALLATION. <br />4. USE ONLY APPROVED (7APTIVFAIRF FAN AND HOOD PACKAGE. <br />5. ROOF MOUNTED FANS SHALL BE ACCESSIBLE ON SIDES ACCESSIBLE WITHOUT LADDER. REFER TO DETAILS. <br />ANSUL NOTES <br />THIS INSTALLATION SHALL BE PROVIDED IN ACCORDANCE WITH R-102 INSTALLATION MANUAL AND IN ACCORDANCE WITH <br />STATE AND LOCAL CODES. WIRE ROPE FOR DETECTOR AND REMOTE PULL STATION SHALL BE INSTALLED BY AN AUTHORIZED, <br />FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. THIS INSTALLATION SHALL BE INSPECTED, PUT INTO <br />OPERATION AND CERTIFIED BY AN AUTHORIZED, FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. <br />ELECTRICAL CONTACTS AND WIRING FOR APPLIANCE SHUT OFF SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR. ANSUL <br />R-102 RESTAURANT FIRE SUPPRESSION SYSTEMS HAVE BEEN TESTED AND ARE LISTED BY UNDERWRITERS' LABORATORIES <br />INC. AS PRE-ENGINEERED SYSTEMS; SHALL COMPLY WITH RELEVANT ANSUL INSTALLATION RECHARGE INSPECTION AND <br />MAINTENANCE MANUALS; SHALL COMPLY WITH NFPA 96 WHEN INSTALLED AND CERTIFIED BY AUTHORIZED TRAINED ANSUL <br />DISTRIBUTORS. AGENT DISTRIBUTION PIPING AND DETECTION CONDUIT HOOD PENETRATIONS SHALL BE PROPERLY SEALED <br />IN ACCORDANCE WITH NFPA 96. <br />TYPE <br />ACCESSORY <br />MOUNT <br />DUTY <br />DIFFUSER <br />TITUS <br />PRICE MOEL <br />NECK SIZE <br />FACE SIZE <br />PATTERN <br />NOTES <br />MARK <br />MODEL NO. <br />NO. <br />DIFFUSER <br />REGISTER <br />GRILLE <br />OBD <br />STIR <br />TRM <br />LAY -IN <br />SURFACE <br />SUPPLY <br />RETURN <br />EXHAUST <br />RG-1 <br />22"X22" <br />24"X24" <br />X <br />X <br />X <br />PERFORATED <br />X <br />PAR -AA <br />APDDR <br />1,2 <br />RG-2 <br />8" <br />12"X12" <br />X <br />X <br />X <br />X <br />PERFORATED <br />X <br />PAR -AA <br />APDDR <br />1,2 DRYWALL CEILING MOUNT EXHAUST <br />RG-3 <br />52"X14" <br />54"X16" <br />X <br />X <br />X <br />X <br />NONE <br />X <br />35ORL <br />530L <br />1 DINING RETURN <br />SD-1 <br />12"x12" <br />14"X14" <br />X <br />X <br />X <br />X <br />NONE <br />X <br />30ORL <br />600 <br />1 DINING SUPPLY <br />1,3,4 CEILING MOUNTED HOOD <br />SD-2 <br />22"X22" <br />24"X24" <br />X <br />X <br />PERFORATED <br />X <br />PAR -AA <br />APDDR <br />SUPPLY DUMP BOX <br />1,3 CEILING MOUNTED HOOD SUPPLY <br />SD-2a <br />22"X22" <br />24"X24" <br />X <br />X <br />PERFORATED <br />X <br />DUMP BOX (CAPTIVEAIRE MODEL DI-PSP) <br />1,3 CEILING MOUNTED HOOD SUPPLY <br />SD-2b <br />22"X22" <br />24"X24" <br />X <br />X <br />PERFORATED <br />X <br />_ <br />DUMP BOX (HALTON MODEL KCD) <br />SD-3 <br />PER PLAN <br />24"X24" <br />X <br />X <br />4 WAY <br />X <br />PAS -AA <br />APDN <br />1,2 <br />S <br />lllSD-5 <br />P L <br />1 1 <br />Y <br />P A <br />APD <br />2 RY ALL CEILING MOUNTED SUPPLY <br />101, <br />24"0 <br />X <br />XI <br />X <br />X <br />TMRA AA <br />1,2 <br />ACCESSORY NOTE: OBD-OPPOSED BLADE DAMPER, STR-SQUARE TO ROUND TRANSITION, TRM- RAPID MOUNT SHEETROCK FRAME <br />AIR DEVICE SCHEDULE NOTES <br />1. WHITE <br />2. ROUND NECK <br />3. SUPPLY DIFFUSERS AT HOOD LOCATION USE SHOP OR FIELD FABRICATED DUMP BOXES, WHICH CONSIST OF PERFORATED DIFFUSER WITH NO PATTERN CONTROLLERS, AND <br />SQUARE PLENUM BOX THAT CAN ACCEPT ROUND DUCT CONNECTION. 4 WAY DIFFUSERS ARE PROHIBITED AROUND THE HOODS. <br />4. REFER TO DUMP BOX DETAIL ON DRAWING M2.0. <br />AIR FLOW SCHEMATIC <br />1100 CFM 1500 CFM <br />1700 CFM 300 CFM 1200 CFM <br />RTU-2 RTU-1 <br />EF-1 EF-2 EF-3 <br />2300 CFM 4000 CFM 1800 CFM 3000 CFM <br />AIR BALANCE SCHEDULE <br />MARK <br />SUPPLY <br />AIR <br />RETURN <br />AIR <br />EXHAUST <br />AIR <br />OUTSIDE <br />AIR <br />RESULTING <br />PRESSURE <br />EF-1 <br />1100 CFM <br />-1100 CFM <br />EF-2 <br />1500 CFM <br />-1300 CFM <br />EF-3 <br />300 CFM <br />-300 CFM <br />RTU-1 <br />3000 CFM <br />1800 CFM <br />1200 CFM <br />+1200 CFM <br />RTU-2 <br />4000 CFM <br />2300 CFM <br />1700 CFM <br />+1700 CFM <br />AIR BALANCE REPORT REQUIRED. SEE SPECIFICATIONS. +200 CFM <br />BASE MDL: GLOBAL NEXT GEN 30 <br />ASSET TYPE: FREESTANDING <br />nrlmraf] NEW <br />WNER: COMPANY/FRANCHISE <br />kw99 V R O : q <br />UPGRADE CLASSIFICATION: <br />NEW BUILD <br />PROJECT YEAR: XXXX <br />DESIGN TYPE: GLOBAL <br />DRAWING RELEASE: SPRING 2023 <br />ARMED DAVIS NEWLOVE & <br />ASSOCIATES, AIA ARCHITECTS <br />1330 OLYMPIC BLVD. <br />SANTA MONICA, CALIFORNIA 90404 <br />PH 310 452-5533 FAX 310 450-4742 <br />L & D ENGINEERING <br />ENERGY &MECHANICAL SYSTEM CONSULTANT <br />1330 OLYMPIC BOULEVARD, #8 <br />SANTA MONICA, CA. 90404 <br />TEL: (310) 452-0575 <br />FAX: (310) 450-4742 <br />EMAIL: KAVEH@LANDDENGINEERING.COM <br />PROJECT TYPE: NEW <br />GLOBAL NEXT GEN 30 <br />O <br />REV. DATE DESCRIPTION <br />1 02-27-25 REVISIONS <br />2 04-09-25 REVISIONS <br />ISSUE <br />DATE: 09-27-24 <br />PROJECT NUMBER: -- 240902 <br />DRAWN BY: <br />CHECKED BY: <br />SEAL <br />SHEET NAME <br />MECHANICAL SCHEDULESmi <br />SHEET NUMBER <br />00 <br />