GENERAL NOTES
<br />1. PROVIDE WARRANTY TO INCLUDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE
<br />PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR AFTER SUBSTANTIAL COMPLETION OR
<br />OWNER ACCEPTANCE OF COMPLETED PROJECT, WHICHEVER IS LATER.
<br />2. COMPLETED INSTALLATION SHALL CONFORM TO APPLICABLE LOCAL, STATE, AND FEDERAL
<br />CODES AND ORDINANCES, INCLUDING NFPA-90A, NFPA-96 AND NFPA-101.
<br />3. DUCTWORK SHALL BE MANUFACTURED AND INSTALLED PER SMACNA 1" PRESSURE CLASS
<br />GUIDELINES AND DETAILS. DUCTWORK SIZES SHOWN INDICATE INSIDE CLEAR DIMENSIONS.
<br />CONCEALED DUCTWORK SHALL BE INSULATED WITH 2" THICK DUCT WRAP (R-8 MIN). INSULATE
<br />CEILING MOUNTED DIFFUSER BACKS. VAPOR BARRIER SHALL BE MAINTAINED CONTINUOUS AND
<br />SEAMS SHALL BE SEALED. DUCTWORK SHALL BE INSTALLED ABOVE SUSPENDED CEILING
<br />WHERE PROVIDED. EXPOSED DUCTWORK SHALL BE G90 GALVANIZED STEEL. CLEAN OFF
<br />MARKS, APPLIED STICKERS AND RESIDUAL OIL. VINEGAR WASH BEFORE PAINTING OF DUCT.
<br />4. CONNECT DUCTS TO FANS AND OTHER AIR DISTRIBUTION EQUIPMENT USING MECHANICAL
<br />FASTENERS WITH SEALS, MASTIC OR GASKETS.
<br />5. SUPPLY AND RETURN AIR DUCT DROPS FROM HVAC EQUIPMENT SHALL BE ISOLATED FROM
<br />UNIT VIBRATION WITH FLEXIBLE DUCT CONNECTORS.
<br />6. INSULATED FLEXIBLE DUCT MAY BE USED IN MAXIMUM LENGTHS AS SPECIFIED FROM RIGID
<br />METAL DUCT TO DIFFUSER CONNECTION. FLEXIBLE DUCT SHALL BE CLASS 1 FLEXIBLE AIR DUCT
<br />WITH INSULATION AND VAPOR BARRIER, AND SHALL MEET UL 181.
<br />7. WHERE PLENUM DIFFUSERS ARE CHOSEN WITH INTEGRAL BALANCING DAMPERS SPIN -IN
<br />CONNECTIONS MAY EXCLUDE DAMPERS.
<br />8. CONTRACTOR SHALL RECEIVE AND INSTALL ROOF MOUNTED CONDENSING UNITS. PROVIDE
<br />MOUNTING RAILS. REFER TO STRUCTURAL PLANS FOR LOCATIONS OF ROOF MOUNTED
<br />EQUIPMENT, CURB, AND RAIL DETAILS. EQUIPMENT SHALL BE MECHANICALLY FASTENED TO
<br />RAILS. RAILS SHALL BE FASTENED TO STRUCTURE. STRUCTURE, CONNECTIONS, AND
<br />SUPPORTS SHALL MEET STRUCTURAL WIND LOAD REQUIREMENTS. CONSULT STRUCTURAL
<br />ENGINEER AS NEEDED TO DETERMINE REQUIREMENTS.
<br />9. CURBS SHALL BE ONE PIECE WELDED AND INSULATED 18 GAUGE STEEL, WITH RIGID
<br />INSULATION GLUED TO INSIDE OF CURB. REFER TO SHEET M2.0 FOR ADDITIONAL INFORMATION.
<br />10. RETURN DUCTWORK FROM HVAC EQUIPMENT AND RECTANGULAR GENERAL EXHAUST
<br />(RESTROOM) DUCTWORK SHALL BE LINED WITH 1" DUCT LINER.
<br />11. PROVIDE STENCIL LABELS ON HVAC EQUIPMENT AND EXHAUST FANS. LABELS SHALL HAVE 2"
<br />HIGH LETTERS ON UNIT SIDE ACCESS PANEL. EXPOSED GAS PIPING AND FITTINGS SHALL BE
<br />PAINTED WITH SAFETY YELLOW PAINT DESIGNED FOR BLACK IRON.
<br />12. ENSURE GAS LINES AND CONDENSATE DRAIN LINES DO NOT IMPEDE HVAC EQUIPMENT
<br />DOORS/PANELS. FOLLOW MANUFACTURER GUIDELINES FOR REQUIRED CLEARANCES.
<br />13. REFER TO "H" AND "W" SHEETS FOR SPECIFIC HOOD AND FAN INFORMATION AND FIELD WIRING
<br />DIAGRAMS. CONTRACTOR SHALL PROVIDE LOW VOLTAGE WIRING FROM FAN CONTROL PANEL
<br />TO HVAC EQUIPMENT, REMOTE SENSORS AND SMOKE DETECTORS. CONTRACTOR SHALL
<br />PROGRAM THERMOSTAT FOLLOWING WENDY'S STANDARDS. REFER TO PROGRAMMING
<br />INSTRUCTIONS PROVIDED WITH MODULAR PANEL SYSTEM.
<br />14. CONTRACTOR SHALL TEST, CHECK, AND BALANCE HVAC EQUIPMENT, EXHAUST HOODS, AND
<br />EXHAUST FANS. SET EXHAUST FANS AND DIFFUSERS TO SPECIFIED AIR FLOW RATES.
<br />CONTRACTOR SHALL COMPLETE WENDY'S REQUIRED TEST FORMS FOR HVAC EQUIPMENT,
<br />HOODS, AND FAN CONTROL SYSTEM. REFER TO M4.0 FOR TESTING AND BALANCE
<br />REQUIREMENTS.
<br />15. CONTRACTOR SHALL COMPLETE ROOFTOP UNIT START UP HVAC EQUIPMENT FORMS AND
<br />RETURN TO MANUFACTURER TO SCHEDULE EQUIPMENT OPERATION CHECK (EOC). CONSULT
<br />CONTACT OR ALLOW 5 BUSINESS DAYS TO SCHEDULE EOC. CONTRACTOR IS RESPONSIBLE FOR
<br />CORRECTING DEFICIENCIES NOTED IN EOC PRIOR TO START OF TESTING AND BALANCING.
<br />16. CONTRACTOR SHALL VERIFY THAT BUILDING IS WEATHER TIGHT, HVAC EQUIPMENT POWERED
<br />AND CALIBRATED, THERMOSTATS PROGRAMMED, FANS OPERATIONAL, EOC COMPLETE,
<br />DIFFUSERS AND CEILING TILE INSTALLED, EXHAUST FAN SPEEDS CALIBRATED, AND NEW
<br />FILTERS INSTALLED IN HVAC EQUIPMENT PRIOR TO TESTING AND BALANCING. CONTRACTOR
<br />SHALL CORRECT OPERATIONAL OR PERFORMANCE DEFICIENCIES FOUND DURING TESTING AND
<br />BALANCING.
<br />17. COMPLETE SMOKE CAPTURE TEST(S), AS REQUIRED, IN ACCORDANCE WITH INTERNATIONAL
<br />MECHANICAL CODE IMC 507, ASHRAE 154 VENTILATION FOR COMMERCIAL COOKING
<br />OPERATIONS, AND HOOD MANUFACTURER STANDARDS. KITCHEN EQUIPMENT SHALL BE AT
<br />OPERATING TEMPERATURES WITH HVAC EQUIPMENT OPERATIONAL. TEST USING SMOKE
<br />CANDLES OR SMOKE PUFFERS. SMOKE BOMBS SHALL NOT BE USED.
<br />18. EQUIPMENT WITH SYMBOL TAGS ON PLANS, REFER TO ASSOCIATED EQUIPMENT SCHEDULES
<br />FOR REQUIREMENTS. TAGGED EQUIPMENT IS RESPONSIBILITY OF CONTRACTOR TO PROVIDE
<br />UNLESS OTHERWISE NOTED.
<br />19. CONTRACTOR IS RESPONSIBLE FOR PROVIDING MANUAL BALANCE DAMPERS IN DUCT
<br />BRANCHES IN ACCESSIBLE LOCATION ABOVE CEILING.
<br />GREASE DUCTS NOTES:
<br />1. FIELD APPLIED OR FACTORY BUILT GREASE DUCT ENCLOSURE SHALL BE INSTALLED PER THE
<br />LATEST MANUFACTURER'S INSTALLATION INSTRUCTIONS AND IN COMPLIANCE WITH TERMS OF
<br />ITS LISTING.
<br />2. ALL END CUTS OR CUTS IN THE FOIL JACKET OF FIELD APPLIED GREASE DUCT ENCLOSURE
<br />SHALL BE SEALED PER THE MANUFACTURER'S RECOMMENDATIONS.
<br />3. ALL INSTALLATIONS SHALL BE COMPLETELY ACCESSIBLE FOR VISUAL INSPECTION.
<br />4. AT TIME OF INSPECTION, THE FIELD APPLIED OR FACTORY BUILT GREASE DUCT ENCLOSURE
<br />INSTALLATION INSTRUCTIONS SHALL BE MADE AVAILABLE AT THE JOB SITE.
<br />FIRE NOTES:
<br />1. FIRE DEPARTMENT APPROVAL SHALL BE REQUIRED ON FIRE PROTECTION SYSTEM FOR GREASE
<br />HOODS AND DUCTS AS REQUIRED BY SECTION 513 OF THE CALIFORNIA MECHANICAL CODE AND
<br />AS REQUIRED BY THE FIRE CODE.
<br />2. ALL FIRE -EXTINGUISHING SYSTEMS SHALL BE INTERCONNECTED TO THE FUEL OR CURRENT
<br />SUPPLY SO THAT THE FUEL OR CURRENT IS AUTOMATICALLY SHUT OFF TO ALL EQUIPMENT
<br />UNDER THE HOOD WHEN THE SYSTEM IS ACTIVATED.
<br />3. OWNER OF ESTABLISHMENT SHALL BE RESPONSIBLE FOR CLEANLINESS, MAINTENANCE, AND
<br />INSPECTION OF KITCHEN EXHAUST SYSTEM, FIRE PROTECTION, AND COOKING EQUIPMENT.
<br />4. A DRAWING OF THE EXHAUST SYSTEM(S) INSTALLATION ALONG WITH A COPY OF OPERATING
<br />INSTRUCTIONS FOR SUBASSEMBLIES AND COMPONENTS USED IN THE EXHAUST SYSTEM(S),
<br />INCLUDING ELECTRICAL SCHEMATICS, SHALL BE AVAILABLE ON THE PREMISES.
<br />5. ALL SEAMS, JOINTS, AND PENETRATIONS OF THE HOOD ENCLOSURE THAT DIRECT AND
<br />CAPTURE GREASE -LADEN VAPORS AND EXHAUST GASES SHALL HAVE A LIQUID TIGHT
<br />CONTINUOUS EXTERNAL WELD TO THE LOWER OUTERMOST PERIMETER OF THE HOOD.
<br />6. PRIOR TO THE USE OR CONCEALMENT OF A PORTION OF A GREASE DUCT SYSTEM, A LEAKAGE
<br />TEST SHALL BE PERFORMED TO DETERMINE THAT ALL WELDED JOINTS AND SEAMS ARE LIQUID
<br />TIGHT.
<br />7. PERFORMANCE, CAPTURE AND CONTAINMENT TESTS SHALL BE PERFORMED UPON
<br />INSTALLATION BEFORE FINAL. TEST DATA AND PERFORMANCE TEST RESULTS SHALL BE
<br />DISPLAYED AND BE AVAILABLE UPON REQUEST.
<br />8. HOOD EXHAUST FAN SHALL CONTINUE TO OPERATE AFTER THE EXTINGUISHING SYSTEM HAS
<br />BEEN ACTIVATED, UNLESS FAN SHUTDOWN IS REQUIRED BY A LISTED COMPONENT OF THE
<br />VENTILATION SYSTEM.
<br />9. TYPE I HOODS SHALL BEAR A LABEL INDICATING THE EXHAUST FLOW RATE IN CUBIC FEET PER
<br />MINUTE PER LINEAL FOOT.
<br />10. LICENSED AIRFLOW CONTRACTOR SHALL PROVIDE GREASE EXHAUST SYSTEM AIR BALANCE
<br />REPORT TO INSPECTOR PRIOR TO FINAL.
<br />SYMBOLS & ABBREVIATIONS
<br />LEGEND
<br />OT
<br />THERMOSTAT
<br />AFF
<br />O
<br />TEMPERATURE/HUMIDITY SENSOR
<br />AHJ
<br />RT
<br />REMOTE TEST STATION
<br />CFM
<br />®
<br />DUCT SMOKE DETECTOR
<br />EA
<br />®
<br />SUPPLY DUCT
<br />ESP
<br />RETURN DUCT
<br />FCLC
<br />®
<br />EXHAUST DUCT
<br />HZ
<br />J
<br />MANUAL BALANCE DAMPER
<br />MOCP
<br />NFPA
<br />NC
<br />SUPPLY DIFFUSER
<br />OA
<br />RETURN GRILLE
<br />OAU
<br />EXHAUST GRILLE
<br />FTU
<br />DUMP BOX DIFFUSER
<br />SA
<br />TYP
<br />`EEET
<br />SIDE WALL MOUNTED SUPPLY REGISTER
<br />WC
<br />ROOFTOP UNIT SCHEDULE HVC n
<br />OUTSIDEAIR TEMPERATURE: 95°FSUMMER
<br />S/A FAN
<br />HEATING
<br />HEATING
<br />AFUE
<br />COOLING
<br />CA
<br />WEIGHT
<br />MANUFACTURER
<br />UNIT
<br />MODEL NO.
<br />TONS
<br />VOLT
<br />INPUT
<br />OUTPUT
<br />%
<br />OUTPUT
<br />EER
<br />IEER
<br />MCA
<br />MOCP
<br />CFM
<br />LBS
<br />NOTES
<br />BHP
<br />CFM
<br />ESP
<br />TRANE
<br />ALL AS
<br />GAS HEAT
<br />RTU-1
<br />YHK090
<br />7.5
<br />1.2
<br />3000
<br />1.0
<br />208/3/60
<br />120 MBH
<br />97.2 MBH
<br />81
<br />90 MBH
<br />12.1
<br />17.7
<br />43
<br />50
<br />1200
<br />1400
<br />APPLICABLE
<br />TRANE
<br />ALL AS
<br />GAS HEAT
<br />RTU-2
<br />YHK120
<br />10
<br />1.9
<br />4000
<br />1.0
<br />208/3/60
<br />150 MBH
<br />121.5 MBH
<br />81
<br />120 MBH
<br />11.6
<br />16.3
<br />57
<br />80
<br />1700
<br />1700
<br />APPLICABLE
<br />UNITS ARE TO BE COMPLETE WITH THE FOLLOWING:
<br />1. FACTORY CURBS FOR CONTRACTOR TO INSTALL. CURB HEIGHTS SHALL PROVIDE FOR LOCAL SNOW ACCUMULATION,
<br />CURBS SHALL BE 14 INCHES HIGH MINIMUM. CONTRACTOR TO CONFIRM CURB HEIGHTS AND STRENGTH WITH
<br />STRUCTURAL ENGINEER TO CONFORM TO LOCAL SNOW ACCUMULATION, SEISMIC AND WIND LOADS, INCLUDING
<br />FASTENER CONSTRUCTION AND INSTALLATION METHODS.
<br />2. FACTORY MOUNTED AND WIRED NON -FUSED DISCONNECT.
<br />3. WEATHER HOOD WITH BIRD SCREEN AT UNIT OUTDOOR AIR INLET.
<br />4. SET MINIMUM OUTDOOR AIR AS SPECIFIED ABOVE. OUTDOOR AIR DAMPER SHALL FULLY CLOSE ON UNIT SHUTDOWN.
<br />5. VFD SUPPLY FAN WITH SINGLE ZONE VARIABLE AIR VOLUME CONTROL WITH OUTDOOR AIR CFM COMPENSATION.
<br />6. FACTORY MOUNTED AND WIRED DRAIN PAN CONDENSATE OVERFLOW SWITCH.
<br />7. OUTDOOR AIR ECONOMIZER WITH SINGLE ENTHALPY CONTROL AND ECONOMIZER FAULT DETECTION AND
<br />DIAGNOSTICS. PROVIDE UNIT WITH BAROMETRIC RELIEF. PROVIDE POWER RELIEF WHERE LOCAL AHJ REQUIRES.
<br />8. FACTORY INSTALLED NON POWERED CONVENIENCE OUTLET.
<br />9. STAINLESS STEEL HEAT EXCHANGERS AND FULLY MODULATING GAS BURNERS.
<br />10. LOUVERED CONDENSER COIL HAIL GUARD.
<br />11. FACTORY INSTALLED HOT GAS REHEAT COIL FOR DEHUMIDIFICATION CONTROL.
<br />12. REFER TO DRAWINGS G2.1 FOR MANUFACTURER CONTACT INFORMATION.
<br />13. PROVIDE MERV-13 FILTERS.
<br />FAN SCHEDULE (3-PLATEN GRILLE
<br />SETUP)
<br />ACCESSORIES
<br />MARK
<br />AIRFLOW
<br />STATIC
<br />PRESSURE
<br />MOTOR
<br />HORSEPOWER
<br />ELECTRICAL
<br />(VOLTAGE /
<br />MODEL
<br />WEIGHT
<br />REMARKS
<br />BACK
<br />(CFM)
<br />(IN.WC.)
<br />(HP)
<br />PHASE)
<br />DRAFT
<br />BIRD
<br />DISCONNECT
<br />SPEED
<br />DIRECT
<br />LBS
<br />DAMPER
<br />SCREEN
<br />SWITCH
<br />CONTROL
<br />DRIVE
<br />EF-1
<br />1100
<br />1.25
<br />3/4
<br />208/1
<br />X
<br />X
<br />X
<br />DU85HFA
<br />90
<br />1-3
<br />EF-2
<br />1500
<br />1.25
<br />3/4
<br />208/1
<br />X
<br />X
<br />X
<br />DU85HFA
<br />90
<br />1-3
<br />EF-3
<br />300
<br />0.340
<br />1/6
<br />115/1
<br />X
<br />I X
<br />I X
<br />X
<br />X
<br />DU10HFA
<br />49
<br />1A
<br />1. FANS, CURBS, AND NFPA FAN HINGES AS APPLICABLE SHALL BE SUPPLIED AS PART OF EXHAUST HOOD PACKAGE.
<br />2. PROVIDE UL APPROVED GREASE RATING.
<br />3. EXHAUST FAN IS CONNECTED TO HOOD ON SWITCH. FAN SHALL
<br />OPERATE AT ALL TIMES WHILE RESTAURANT IS OPEN.
<br />4. FAN TO OPERATE FROM SMART BREAKER IN FCLC SYSTEM.
<br />ABOVE FINISHED FLOOR
<br />AUTHORITY HAVING JURISDICTION
<br />CUBIC FEET PER MINUTE
<br />EXHAUST AIR
<br />EXTERNAL STATIC PRESSURE
<br />FAN CONTROL LIGHTING CONTROL
<br />FREQUENCY
<br />MAXIMUM OVERCURRENT PROTECTION
<br />NATIONAL FIRE PROTECTION ASSOCIATION
<br />NOISE CRITERIA
<br />OUTSIDE AIR
<br />OUTDOOR AIR UNIT
<br />FAN TERMINAL UNIT
<br />SUPPLY AIR
<br />TYPICAL
<br />WATER COLUMN
<br />AIR CURTAIN SCHEDULE
<br />ELECTRICAL
<br />MANUFACTURER
<br />AND
<br />CFM
<br />MAX
<br />WEIGHT
<br />NOTES
<br />MODEL NUMBER
<br />FPM
<br />VOLTS
<br />PHASE
<br />MAX
<br />AMPS
<br />HP
<br />LBS
<br />WATTS
<br />MARS
<br />AC-1
<br />1418
<br />4865
<br />120
<br />1
<br />510
<br />5.1
<br />1/2
<br />70
<br />1 AND 2
<br />STD242
<br />MARS
<br />AC-2
<br />1200
<br />1800
<br />120
<br />1
<br />-
<br />2.4
<br />1/6
<br />40
<br />1 AND 2
<br />LPV248
<br />NOTE: 1. INTERLOCK AIR CURTAIN WITH LIMIT SWITCH ON DOOR TO ACTIVATE THE AIR CURTAIN
<br />WHEN DOOR OPENS. BY ELECTRICAL CONTRACTOR.
<br />2. AIR CURTAIN SHALL PROVIDE AIR AT A VELOCITY OF AT LEAST 750 FEET PER
<br />MINUTE MEASURED AT 3'-0" ABOVE THE FLOOR.
<br />AIR DEVICE SCHEDULE
<br />SYMBOLS & ABBREVIATIONS LEGEND
<br />OT
<br />THERMOSTAT
<br />AFF
<br />O
<br />TEMPERATURE/HUMIDITY SENSOR
<br />AHJ
<br />RT
<br />REMOTE TEST STATION
<br />CFM
<br />®
<br />DUCT SMOKE DETECTOR
<br />EA
<br />®
<br />SUPPLY DUCT
<br />ESP
<br />RETURN DUCT
<br />FCLC
<br />®
<br />EXHAUST DUCT
<br />HZ
<br />MOCP
<br />J
<br />MANUAL BALANCE DAMPER
<br />NFPA
<br />NC
<br />SUPPLY DIFFUSER
<br />CA
<br />z
<br />RETURN GRILLE
<br />OAU
<br />EXHAUST GRILLE
<br />FTU
<br />II„ Ih
<br />DUMP BOX DIFFUSER
<br />SA
<br />lur
<br />TYP
<br />rE=P
<br />SIDE WALL MOUNTED SUPPLY REGISTER
<br />WC
<br />COMMERCIAL KITCHEN NOTES
<br />HVAC, FIRE PROTECTION AND PLUMBING
<br />CITY OF SANTA ANA
<br />�v
<br />ABOVE FINISHED FLOOR
<br />AUTHORITY HAVIN
<br />JURISDICTION
<br />CUBIC FEET PER MINUTE
<br />EXHAUST AIR
<br />R P
<br />EXTERNAL STATIC F
<br />RESS[JREO
<br />FAN CONTROL LIGH
<br />ING CONTROL
<br />FREQUENCY
<br />MAXIMUM OVERCUF
<br />RENT
<br />��PROTECTION
<br />r
<br />dlf
<br />NATIONAL FIRE PR
<br />EC�ImClSl�IA
<br />NOISE CRITERIA
<br />Date.
<br />OUTSIDE AIR
<br />OUTDOOR AIR UNIT
<br />FAN TERMINAL UNIT
<br />SUPPLY AIR
<br />TYPICAL
<br />WATER COLUMN
<br />NEW EQUIPMENT, PIPING, ETC. SHALL BE INSPECTED AND LOCATED BEFORE AND AFTER NEW CONSTRUCTION. DETAILS OF
<br />PERFORMANCE/CONDITION/SIZING AND LOCATION SHALL BE SUPPLIED TO ENGINEER AND OWNER. AIR CAPACITIES FOR
<br />SUPPLY AND EXHAUST SYSTEMS SHALL BE MEASURED AT GRILLES TO DETERMINE IF DESIGN AIR FLOW RATES NOTED ON
<br />PLANS CAN BE MET. EXTRA WORK REQUIRED TO ABOVE MENTIONED SHALL BE DETERMINED PRIOR TO NEW CONSTRUCTION
<br />CONTRACTOR TO ALLOW FOR INSPECTION IN THEIR PRICE INCLUDING WELD INSPECTIONS, AIR FLOW RATE MEASUREMENT,
<br />SCANNING AND CAMERA SCOPE TO EXISTING BURIED DRAINS. NO EXTRAS SHALL BE ALLOWED ONCE NEW CONSTRUCTION
<br />STARTS.
<br />CONTRACTOR SHALL OBTAIN LATEST SPREAD SHEETS/SHOP DRAWINGS FROM KITCHEN CONSULTANT FOR APPLIANCE AND
<br />HVAC REQUIREMENTS PRIOR TO ROUGH -IN WORK.
<br />CONTRACTOR SHALL PROVIDE WIRING AND CONTROLS AS NOTED ON WIRING NOTES IN EQUIPMENT SCHEDULE.
<br />CONTRACTOR SHALL:
<br />1. CONSTRUCT ENTIRE KITCHEN HOOD EXHAUST SYSTEM TO NFPA 96 STANDARDS.
<br />2. REFER TO ARCHITECTURAL AND/OR INTERIOR DESIGN DRAWINGS FOR HOOD LOCATION AND APPROVED KITCHEN HOOD
<br />SHOP DRAWINGS FOR EXACT LOCATION OF EXHAUST DUCT CONNECTIONS.
<br />3. REFER TO LATEST KITCHEN EQUIPMENT DRAWINGS AND APPROVED SHOP DRAWINGS FOR FINAL GAS, PLUMBING AND
<br />DRAINAGE HOOK UP SIZES AND LOCATIONS. CONTRACTOR TO REFER TO MANUFACTURERS INSTALLATION MANUALS AND
<br />RECOMMENDATIONS AND PROVIDE NECESSARY EQUIPMENT, VALVES, PIPING, ETC. TO SUIT. EXACT LOCATION OF
<br />EQUIPMENT ROUGH -INS SHALL BE DETERMINED AT SITE. CHANGES TO KITCHEN EQUIPMENT LINE UP MUST BE REPORTED
<br />TO ENGINEER, FOOD SERVICES VENDOR, AND ARCHITECT PRIOR TO INSTALLATION.
<br />4. USE ONLY APPROVED (7APTIVFAIRF FAN AND HOOD PACKAGE.
<br />5. ROOF MOUNTED FANS SHALL BE ACCESSIBLE ON SIDES ACCESSIBLE WITHOUT LADDER. REFER TO DETAILS.
<br />ANSUL NOTES
<br />THIS INSTALLATION SHALL BE PROVIDED IN ACCORDANCE WITH R-102 INSTALLATION MANUAL AND IN ACCORDANCE WITH
<br />STATE AND LOCAL CODES. WIRE ROPE FOR DETECTOR AND REMOTE PULL STATION SHALL BE INSTALLED BY AN AUTHORIZED,
<br />FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE. THIS INSTALLATION SHALL BE INSPECTED, PUT INTO
<br />OPERATION AND CERTIFIED BY AN AUTHORIZED, FACTORY TRAINED DISTRIBUTOR OR SERVICE REPRESENTATIVE.
<br />ELECTRICAL CONTACTS AND WIRING FOR APPLIANCE SHUT OFF SHALL BE PROVIDED BY ELECTRICAL CONTRACTOR. ANSUL
<br />R-102 RESTAURANT FIRE SUPPRESSION SYSTEMS HAVE BEEN TESTED AND ARE LISTED BY UNDERWRITERS' LABORATORIES
<br />INC. AS PRE-ENGINEERED SYSTEMS; SHALL COMPLY WITH RELEVANT ANSUL INSTALLATION RECHARGE INSPECTION AND
<br />MAINTENANCE MANUALS; SHALL COMPLY WITH NFPA 96 WHEN INSTALLED AND CERTIFIED BY AUTHORIZED TRAINED ANSUL
<br />DISTRIBUTORS. AGENT DISTRIBUTION PIPING AND DETECTION CONDUIT HOOD PENETRATIONS SHALL BE PROPERLY SEALED
<br />IN ACCORDANCE WITH NFPA 96.
<br />TYPE
<br />ACCESSORY
<br />MOUNT
<br />DUTY
<br />DIFFUSER
<br />TITUS
<br />PRICE MOEL
<br />NECK SIZE
<br />FACE SIZE
<br />PATTERN
<br />NOTES
<br />MARK
<br />MODEL NO.
<br />NO.
<br />DIFFUSER
<br />REGISTER
<br />GRILLE
<br />OBD
<br />STIR
<br />TRM
<br />LAY -IN
<br />SURFACE
<br />SUPPLY
<br />RETURN
<br />EXHAUST
<br />RG-1
<br />22"X22"
<br />24"X24"
<br />X
<br />X
<br />X
<br />PERFORATED
<br />X
<br />PAR -AA
<br />APDDR
<br />1,2
<br />RG-2
<br />8"
<br />12"X12"
<br />X
<br />X
<br />X
<br />X
<br />PERFORATED
<br />X
<br />PAR -AA
<br />APDDR
<br />1,2 DRYWALL CEILING MOUNT EXHAUST
<br />RG-3
<br />52"X14"
<br />54"X16"
<br />X
<br />X
<br />X
<br />X
<br />NONE
<br />X
<br />35ORL
<br />530L
<br />1 DINING RETURN
<br />SD-1
<br />12"x12"
<br />14"X14"
<br />X
<br />X
<br />X
<br />X
<br />NONE
<br />X
<br />30ORL
<br />600
<br />1 DINING SUPPLY
<br />1,3,4 CEILING MOUNTED HOOD
<br />SD-2
<br />22"X22"
<br />24"X24"
<br />X
<br />X
<br />PERFORATED
<br />X
<br />PAR -AA
<br />APDDR
<br />SUPPLY DUMP BOX
<br />1,3 CEILING MOUNTED HOOD SUPPLY
<br />SD-2a
<br />22"X22"
<br />24"X24"
<br />X
<br />X
<br />PERFORATED
<br />X
<br />DUMP BOX (CAPTIVEAIRE MODEL DI-PSP)
<br />1,3 CEILING MOUNTED HOOD SUPPLY
<br />SD-2b
<br />22"X22"
<br />24"X24"
<br />X
<br />X
<br />PERFORATED
<br />X
<br />_
<br />DUMP BOX (HALTON MODEL KCD)
<br />SD-3
<br />PER PLAN
<br />24"X24"
<br />X
<br />X
<br />4 WAY
<br />X
<br />PAS -AA
<br />APDN
<br />1,2
<br />S
<br />lllSD-5
<br />P L
<br />1 1
<br />Y
<br />P A
<br />APD
<br />2 RY ALL CEILING MOUNTED SUPPLY
<br />101,
<br />24"0
<br />X
<br />XI
<br />X
<br />X
<br />TMRA AA
<br />1,2
<br />ACCESSORY NOTE: OBD-OPPOSED BLADE DAMPER, STR-SQUARE TO ROUND TRANSITION, TRM- RAPID MOUNT SHEETROCK FRAME
<br />AIR DEVICE SCHEDULE NOTES
<br />1. WHITE
<br />2. ROUND NECK
<br />3. SUPPLY DIFFUSERS AT HOOD LOCATION USE SHOP OR FIELD FABRICATED DUMP BOXES, WHICH CONSIST OF PERFORATED DIFFUSER WITH NO PATTERN CONTROLLERS, AND
<br />SQUARE PLENUM BOX THAT CAN ACCEPT ROUND DUCT CONNECTION. 4 WAY DIFFUSERS ARE PROHIBITED AROUND THE HOODS.
<br />4. REFER TO DUMP BOX DETAIL ON DRAWING M2.0.
<br />AIR FLOW SCHEMATIC
<br />1100 CFM 1500 CFM
<br />1700 CFM 300 CFM 1200 CFM
<br />RTU-2 RTU-1
<br />EF-1 EF-2 EF-3
<br />2300 CFM 4000 CFM 1800 CFM 3000 CFM
<br />AIR BALANCE SCHEDULE
<br />MARK
<br />SUPPLY
<br />AIR
<br />RETURN
<br />AIR
<br />EXHAUST
<br />AIR
<br />OUTSIDE
<br />AIR
<br />RESULTING
<br />PRESSURE
<br />EF-1
<br />1100 CFM
<br />-1100 CFM
<br />EF-2
<br />1500 CFM
<br />-1300 CFM
<br />EF-3
<br />300 CFM
<br />-300 CFM
<br />RTU-1
<br />3000 CFM
<br />1800 CFM
<br />1200 CFM
<br />+1200 CFM
<br />RTU-2
<br />4000 CFM
<br />2300 CFM
<br />1700 CFM
<br />+1700 CFM
<br />AIR BALANCE REPORT REQUIRED. SEE SPECIFICATIONS. +200 CFM
<br />BASE MDL: GLOBAL NEXT GEN 30
<br />ASSET TYPE: FREESTANDING
<br />nrlmraf] NEW
<br />WNER: COMPANY/FRANCHISE
<br />kw99 V R O : q
<br />UPGRADE CLASSIFICATION:
<br />NEW BUILD
<br />PROJECT YEAR: XXXX
<br />DESIGN TYPE: GLOBAL
<br />DRAWING RELEASE: SPRING 2023
<br />ARMED DAVIS NEWLOVE &
<br />ASSOCIATES, AIA ARCHITECTS
<br />1330 OLYMPIC BLVD.
<br />SANTA MONICA, CALIFORNIA 90404
<br />PH 310 452-5533 FAX 310 450-4742
<br />L & D ENGINEERING
<br />ENERGY &MECHANICAL SYSTEM CONSULTANT
<br />1330 OLYMPIC BOULEVARD, #8
<br />SANTA MONICA, CA. 90404
<br />TEL: (310) 452-0575
<br />FAX: (310) 450-4742
<br />EMAIL: KAVEH@LANDDENGINEERING.COM
<br />PROJECT TYPE: NEW
<br />GLOBAL NEXT GEN 30
<br />O
<br />REV. DATE DESCRIPTION
<br />1 02-27-25 REVISIONS
<br />2 04-09-25 REVISIONS
<br />ISSUE
<br />DATE: 09-27-24
<br />PROJECT NUMBER: -- 240902
<br />DRAWN BY:
<br />CHECKED BY:
<br />SEAL
<br />SHEET NAME
<br />MECHANICAL SCHEDULESmi
<br />SHEET NUMBER
<br />00