Laserfiche WebLink
1. IF ANY OUTLETS CANNOT BE INSTALLED AS NOTED OR AS SHOWN ON PLANS DUE TO CONFLICTS WITH <br />STRUCTURAL, MECHANICAL OR ELECTRICAL CONDITIONS, CLARIFY WITH HENDY BEFORE PROCEEDING <br />WITH OUTLETS IN QUESTION OR RELATED OUTLETS IN AREA. <br />2. ARCHITECTURAL DRAWINGS GOVERN OUTLET LOCATIONS. VERIFY ANY DISCREPANCIES WITH HENDY. <br />3. CONTRACTOR TO REFER TO ELECTRICAL ENGINEERING DRAWINGS FOR CONDUIT SIZE & DEVICE <br />SPECIFICATIONS, NO DEVICE OR CONDUIT SUBSTITUTIONS OR SIZE REDUCTIONS ARE ACCEPTABLE. <br />4. FOR CIRCUITING INFORMATION AND PULL BOX LOCATIONS, REFER TO ELECTRICAL ENGINEERING <br />DRAWINGS. <br />5. ALL NEW CIRCUITS SHALL BE LABELED ON THE PROPER BUILDING ELECTRICAL PANEL DIRECTORIES. <br />6. PROVIDE ELECTRICAL REQUIREMENTS AS NEEDED FOR MECHANICAL AND PLUMBING EQUIPMENT SEE <br />ENGINEERING DRAWINGS. <br />7. NON-DIMENSIONED OUTLETS SHALL BE LOCATED AT THE NEAREST STUD. ALL OUTLET DIMENSIONS SHALL <br />BE CENTERLINE U.N.O. ALL OUTLET HEIGHTS NOTED ARE TO THE CENTERLINE OF THE RECEPTACLE, <br />U.N.O. (SEE TYPICAL POWER AND COMMUNICATION LOCATIONS DIAGRAM). <br />8. WHERE OUTLETS ARE GROUPED TOGETHER, THEY SHALL BE NO MORE THAN 2 INCHES APART. GANG <br />WITH COMMON MOUNTING BRACKET AND/OR FACEPLATE WHENEVER POSSIBLE. <br />9. PROVIDE CODE REQUIRED PROTECTION AT ALL OUTLETS AND SWITCHES LOCATED IN RATED PARTITIONS. <br />10. ALL WALL OUTLETS LOCATED IN PRIVATE OFFICES & CONFERENCE ROOMS SHALL HAVE SOUND PADS, <br />SEE TYPICAL WALL OUTLET SPACING DIAGRAM. <br />11. MARK LOCATIONS OF ALL FLOOR MOUNTED RECEPTACLES AND REVIEW WITH HENDY PRIOR TO <br />PROCEEDING WITH CORING/TRENCHING. <br />12. SCHEDULE THE CORING OF ANY FLOOR OUTLETS WITH LANDLORD TO PREVENT DISTURBANCE OR <br />DAMAGE TO OTHER TENANT SPACES. <br />13. CONTRACTOR TO VERIFY WITH LANDLORD IF X-RAY IS REQUIRED PRIOR TO CORE DRILLING. <br />14. ALL CONDUITS INSTALLED FROM A FLOOR POKE THROUGH FOR VOICE/DATA CABLING SHALL BE RUN TO 6" <br />ABOVE THE SUSPENDED CEILING AT THE NEAREST WALL/COLUMN IN THE DIRECTION OF THE <br />APPROPRIATE MDF/IDF ROOM EXCEPT AS WHERE IMPOSSIBLE DUE TO CEILING <br />RESTRICTIONS/BLOCKAGES. <br />15. PROVIDE CONDUITS OVER HARD LID CEILING & THRU-RATED WALLS FOR TENANT CABLING, LOCATIONS & <br />SIZES SHALL BE VERIFIED WITH ELECTRICAL ENGINEERING DRAWINGS & TENANT CABLING INSTALLER. <br />16. CONDUIT ABOVE CEILING SHALL BE SELF-SUPPORTED AND HELD TIGHT TO STRUCTURE A MINIMUM OF 6" <br />ABOVE GRID, COORDINATE WITH LIGHT FIXTURE AND EQUIPMENT REQUIRED CLEARANCES. <br />17. GENERAL CONTRACTOR SHALL COORDINATE WORK WITH TENANT'S CABLING CONTRACTORS. <br />18. CABLING SHALL BE PLENUM RATED AND SUPPORTED INDEPENDENT OF THE SUSPENDED CEILING. ALL <br />CABLING SHALL BE PROVIDED AND INSTALLED BY TENANT'S VENDOR. <br />19. WHERE ELECTRICAL WORK IS SPECIFIED IN CONJUNCTION W ITH MILLWORK, ALL OUTLETS, CONDUITS ND <br />FIXTURES SHALL BE PROVIDED BY GENERAL CONTRACTOR. CUT OUTS FOR SWITCHES, OUTLETS, ETC. <br />SHALL BE PROVIDED BY THE MILLWORK CONTRACTOR AND SHALL BE COORDINATED WITH THE <br />ELECTRICAL CONTRACTOR, U.N.O. <br />20. FURNITURE SYSTEMS SHALL BE SUPPLIED AND INSTALLED BY TENANT'S VENDOR. ELECTRICAL <br />CONTRACTOR SHALL MAKE FINAL HARDWIRE CONNECTION AND IS RESPONSIBLE FOR ALL REQUIRED <br />PERMITS/INSPECTIONS. <br />21. ISOLATED GROUND RECEPTACLE SHALL BE ORANGE WITH BUILDING STANDARD COVER PLATES. <br />22. TELEPHONE DATA CONTRACTOR SHALL COORDINATE DEVICE LOCATION WITH HENDY PRIOR TO <br />INSTALLATION. <br />1. REFER TO IA-9.1 SHEET FOR RESTROOM PLUMBING REQUIREMENTS. <br />2. REFER TO MILLWORK ELEVATIONS FOR EXACT PLUMBING LOCATIONS. <br />3. KITCHEN SINKS SHALL HAVE A LEVER, PUSH TYPE OR ELECTRONICALLY OPERATED FAUCETS, WITH A 5 <br />LBS. MAXIMUM OPENING FORCE. SELF CLOSING FAUCETS SHALL REMAIN OPEN 10 SECONDS MINIMUM. <br />1. ALL EQUIPMENT IN PLENUM SHALL BE LOCATED AWAY FROM GYP. BD. CEILINGS WHENEVER <br />POSSIBLE. NO ACCESS HATCHES IN GYP. BD. CEILING WITHOUT PRIOR APPROVAL BY ARCHITECT. <br />ACCESS HATCHES SHALL BE A TRIMLESS TYPE. SUBMIT CUT SHEET FOR APPROVAL. <br />2. PROVIDE AND INSTALL CONDUITS OVER GYP. BD. CEILINGS, THROUGH FULL HEIGHT WALLS AND <br />THROUGH RATED CORRIDORS TO NEAREST ACCESSIBLE CEILING FOR TENANT'S CABLING. CONDUIT <br />SIZE AND LOCATION SHALL BE VERIFIED PRIOR TO INSTALLATION. <br />3. EXCEPT WHERE RIGID BRACES ARE USED TO LIMIT LATERAL DEFLECTIONS, SPRINKLER HEADS AND <br />OTHER PENETRATIONS SHALL HAVE A 2 INCH OVERSIZE RING SLEEVE OR ADAPTER THROUGH THE <br />CEILING TILE TO ALLOW FOR FREE MOVEMENT OF AT LEAST 1 INCH IN ALL HORIZONTAL DIRECTIONS. <br />ALTERNATIVELY, A SWING JOINT THAT CAN ACCOMMODATE 1 INCH OF CEILING MOVEMENT IN ALL <br />HORIZONTAL DIRECTIONS IS PERMITTED SHALL BE PROVIDED AT THE TOP OF THE SPRINKLER HEAD <br />EXTENSION. <br />4. INSTALL SUSPENDED CEILING SYSTEMS IN ACCORDANCE WITH CBC CHAPTERS 8 AND 25. <br />5. SUSPENDED CEILING FRAMING SYSTEMS SHALL BE DESIGNED TO RESIST A LATERAL FORCE OF 20% <br />OF THE WEIGHT OF THE CEILING ASSEMBLY AND ANY LOADS TRIBUTARY TO THE SYSTEM. FOR THE <br />PURPOSES OF DETERMINING THE LATERAL FORCE, A MINIMUM CEILING WEIGHT OF 5 LBS PER <br />SQUARE FOOT SHALL BE USED. WHERE THE CEILING LOADS DO NOT EXCEED 5 LBS PER SQUARE <br />FOOT AND WHERE PARTITIONS ARE NOT CONNECTED TO THE CEILING SYSTEM, THE FOLLOWING <br />BRACING METHOD MAY BE EMPLOYED: <br />a.LATERAL SUPPORT MAY BE PROVIDED BY FOUR WIRES OF MINIMUM NO. 8 GAUGE SPLAYED IN <br />FOUR DIRECTIONS 90 DEGREES APART, AND CONNECTED TO THE MAIN RUNNER WITHIN 2'' OF <br />THE CROSS RUNNER AND TO THE STRUCTURE ABOVE AT AN ANGLE NOT EXCEEDING 45 <br />DEGREES FROM THE PLANE OF THE CEILING. THESE LATERAL SUPPORT POINTS SHALL BE <br />PLACED 12 FT. O.C. IN EACH DIRECTION WITH THE FIRST POINT WITHIN 6 FT. FROM EACH <br />WALL. <br />b.ALLOWANCE SHALL BE MADE FOR LATERAL MOVEMENT OF THE SYSTEM WITH CLEARANCE <br />BETWEEN THE WALL AND THE RUNNERS MAINTAINED AT THE OTHER TWO WALLS. <br />c.VERTICAL SUPPORT SHALL BE PROVIDED AS REQUIRED IN CBC CHAPTER 8 WITH THE ADDED <br />REQUIREMENT THAT DISCONTINUOUS ENDS OF CROSS RUNNERS AND MAIN RUNNERS BE <br />VERTICALLY SUPPORTED WITHIN 8'' OF SUCH DISCONTINUITIES AS MAY OCCUR WHERE THE <br />CEILING IS DISRUPTED BY A WALL. <br />d.A STRUT FASTENED TO THE MAIN RUNNER SHALL EXTEND TO AND FASTENED TO THE <br />STRUCTURAL MEMBERS SUPPORTING THE ROOF OR FLOOR ABOVE AT 12'-0”O.C. IN BOTH <br />DIRECTIONS AND WITHIN 6'-0”FROM WALLS. <br />6. SUSPENDED ACOUSTICAL CEILING SYSTEM PERIMETER SUPPORTING CLOSURE ANGLE SHALL BE NOT <br />LESS THAN 2 INCHES IN EACH ORTHOGONAL HORIZONTAL DIRECTION. ONE END OF THE CEILING GRID <br />SHALL BE ATTACHED TO THE CLOSURE ANGLE. THE OTHER END IN EACH HORIZONTAL DIRECTION <br />SHALL HAVE A 3/4 INCH CLEARANCE FROM THE WALL AND SHALL REST UPON AND BE FREE TO SLIDE <br />ON A CLOSURE ANGLE. <br />7. REMOVE AND REPLACE EXISTING CEILING GRID AND TILES AS REQUIRED FOR INSTALLATION OF VAV <br />BOXES, MECHANICAL DUCTS, AND/OR AC UNITS. <br />1. SPRINKLER HEADS LOCATED IN GYP. BD. CEILINGS SHALL BE FULLY RECESSED AND FACTORY <br />PAINTED TO MATCH CEILING. DISTRIBUTION OF HEADS MUST MEET GOVERNING CODES. <br />2. SPRINKLER HEADS LOCATED IN SUSPENDED ACOUSTICAL CEILING SYSTEMS SHALL BE SEMI- <br />RECESSED ADJUSTABLE HEADS. DISTRIBUTION OF HEADS MUST MEET GOVERNING CODES. <br />HEADS SHALL BE LOCATED IN CENTER OF CEILING TILE, U.N.O. (EXCEPT AS CODE REQUIRED NEAR <br />SOFFIT). CONFIRM EXISTING SPRINKLER HEAD LOCATIONS. <br />1. LOCATE RECESSED DOWNLIGHTS, WALL WASHERS, PENDANTS, AND ACCENT LIGHTS IN THE CENTER OF <br />CEILING TILES, U.N.O. <br />2. LIGHT SENSOR AND LIGHT SWITCH LOCATIONS SHALL BE APPROVED BY ARCHITECT PRIOR TO INSTALLATION. <br />3. ALL STROBES SHALL BE LOCATED IN CEILING WHERE ALLOWABLE BY CODE. COLOR SHALL BE APPROVED BY <br />ARCHITECT. <br />4. THE COLOR AND DESIGN OF LETTERING, ARROWS AND OTHER SYMBOLS ON THE EXIT SIGN SHALL BE IN HIGH <br />CONTRAST WITH THEIR BACKGROUND. WORDS ON THE SIGN SHALL BE IN BLOCK LETTERS 6 INCHES IN <br />HEIGHT WITH A STROKE OF NOT LESS THAN 3/4" INCH. MATCH BUILDING STANDARD, UNLESS NOTED <br />OTHERWISE. <br />5. THE MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE LESS THAN 1 FOOT-CANDLE AT THE WALKING <br />SURFACE LEVEL. <br />6. THE EMERGENCY POWER SYSTEM SHALL PROVIDE POWER FOR A DURATION NOT LESS THAN 90 MINUTES <br />AND SHALL CONSIST OF STORAGE BATTERIES, UNIT EQUIPMENT OR AN ON-SITE GENERATOR. THE <br />INSTALLATION OF THE EMERGENCY POWER SYSTEM SHALL BE IN ACCORDANCE WITH CBC 2702 AND <br />ILLUMINATE THE FOLLOWING AREAS: <br />A.AISLES AND UNENCLOSED EGRESS STAIRWAYS IN ROOMS AND SPACES THAT REQUIRE TWO OR <br />MORE MEANS OF EGRESS. <br />B.CORRIDORS, EXIT ENCLOSURES AND EXIT PASSAGEWAYS IN BUILDINGS REQUIRED TO HAVE TWO OR <br />MORE EXITS. <br />C.EXTERIOR EGRESS COMPONENTS AT ALL LEVELS OTHER THAN THE LEVEL OF EXIT DISCHARGE UNTIL <br />EXIT DISCHARGE IS ACCOMPLISHED FOR BUILDINGS REQUIRED TO HAVE TWO OR MORE EXITS. <br />D.INTERIOR EXIT DISCHARGE ELEMENTS, AS REQUIRED BY CBC SECTION 1028.1, IN BUILDINGS <br />REQUIRED TO HAVE TWO OR MORE EXITS. <br />E.EXTERIOR LANDINGS FOR EXIT DISCHARGE DOORWAYS IN BUILDINGS REQUIRED TO HAVE TWO OR <br />MORE EXITS. <br />7. LIGHTING FIXTURES SHALL BE SUPPORTED DIRECTLY BY WIRES TO THE STRUCTURE ABOVE. RECESSED <br />LIGHTING FIXTURES NOT OVER 56 LBS IN WEIGHT AND PENDANT HUNG FIXTURES NOT OVER 20 LBS IN <br />WEIGHT MAY BE SUPPORTED AND ATTACHED DIRECTLY TO THE CEILING SYSTEM RUNNERS BY A POSITIVE <br />ATTACHMENT SUCH AS SCREWS OR BOLTS. THESE REQUIREMENTS ARE BASED ON CURRENT CALIFORNIA <br />BUILDING CODES. OTHER METHODS MAY BE USED PROVIDED THEY ARE SUBSTANTIATED BY DESIGN <br />CALCULATIONS USING THE LOADS SPECIFIED IN CBC CHAPTER 25. <br />1. ELEVATORS SHALL COMPLY WITH ALL CURRENT CALIFORNIA BUILDING CODE SECTIONS. <br />2. ELEVATOR SHALL OPERATE AUTOMATICALLY. <br />3. CAB SHALL BE SELF-LEVELING TO A TOLERANCE OF 1/2" VERTICAL WITH A MAXIMUM GAP BETWEEN <br />PLATFORM SILL AND EDGE OF HOISTWAY OF 1-1/4" HORIZONTAL BETWEEN CAR AND LANDING. <br />4. CALL BUTTONS SHALL BE CENTERED AT 42 INCHES A.F.F. WITH BUTTONS A MINIMUM OF 3/4" DIA. AND <br />RAISED 1/8". <br />5. VISUAL INDICATOR TO SHOW EACH CALL REGISTERED AND ANSWERED. <br />6. VISUAL SIGNALS AT EACH HOISTWAY ENTRANCE SHOWING CAR ARRIVAL AND DIRECTION SHALL BE 2-1/2" <br />AND CENTERLINE AT 6'-0”MINIMUM ABOVE FLOOR AND VISIBLE FROM PROXIMITY OF CALL BUTTON. <br />7. AUDIBLE INDICATORS ANNOUNCING CAR ARRIVAL AND TRAVEL DIRECTION SHALL SOUND ONCE FOR UP <br />AND TWICE FOR DOWN. <br />8. BOTH HOISTWAY JAMBS AT EACH FLOOR SHALL HAVE SIGNAGE AT 5'-0" A.F.F. INDICATING FLOOR NUMBER IN <br />RAISED CHARACTERS THAT ARE MINIMUM 2 INCHES HIGH ON CONTRASTING BACKGROUND. PROVIDE 2 <br />INCHES DIA. FIVE POINT STAR TO LEFT OF CHARACTER ON MAIN ENTRY LEVEL. BRAILLE SHALL BE PLACED <br />BELOW CORRESPONDING CHARACTERS. <br />9. AUTOMATIC DOORS SHALL BE MINIMUM 36" WIDE. <br />10. CAR SIZE SHALL BE A MINIMUM OF 80”X 54”FOR CENTER OPENING DOORS AND 68”X 54”FOR SIDE-SLIDE <br />OPENING DOORS. <br />11. CAR CONTROL BUTTONS SHALL BE 48 INCHES A.F.F. FOR FRONT APPROACH OR 54 INCHES A.F.F. FOR SIDE <br />APPROACH WITH EMERGENCY CONTROLS NO LOWER THAN 35" A.F.F. AND ADJACENT TO OR IN BOTTOM OF <br />BUTTON PANEL. <br />12. EMERGENCY TWO-WAY COMMUNICATION SYSTEM SHALL BE NO MORE THAN 48 INCHES A.F.F. WITH THE <br />HANDSET CORD A MINIMUM OF 29" IN LENGTH. EMERGENCY INTERCOMMUNICATION SHALL NOT REQUIRE <br />VOICE COMMUNICATION. <br />13. HANDRAIL SHALL BE LOCATED ON ONE WALL, PREFERABLY REAR MOUNTED, AT 32”A.F.F. AND 1-1/2”FROM <br />WALL. <br />14. DOOR REOPENING DEVICE SHALL BE ACTIVATED WHEN OBSTRUCTION IS SENSED BETWEEN 5"-29" ABOVE <br />THE FLOOR WITHOUT CONTACT AND REMAIN EFFECTIVE FOR A MINIMUM OF 20 SECONDS. <br />15. DOOR DELAY TIME SHALL BE NOT LESS THAN CALCULATED BY T=D/(1.5 FT/S) WHERE “T”IS TIME IN SECONDS <br />AND “D”IS THE DISTANCE FROM A POINT IN THE LOBBY OR LANDING AREA 60 INCHES DIRECTLY IN FRONT OF <br />THE FARTHEST CALL BUTTON CONTROLLING THE CAR TO CENTERLINE OF ITS HOISTWAY DOOR. <br />16. MINIMUM ACCEPTABLE TIME FOR THE DOORS TO REMAIN FULL OPEN IS NOT LESS THAN FIVE SECONDS. <br />17. MINIMUM ILLUMINATION REQUIRED AT CAR CONTROLS THRESHOLD AND LANDING WHEN CAR AND LANDING <br />DOORS ARE OPEN IS 5 FOOTCANDLES. <br />18. PASSENGER ELEVATOR CAR CONTROL BUTTON SHALL BE ILLUMINATED, HAVE SQUARE SHOULDERS, BE <br />MINIMUM 3/4" IN DIMENSION AND RAISED 1/8". <br />19. CONTROL BUTTONS SHALL BE DESIGNATED BY 5/8" MINIMUM RAISED CHARACTERS AND STANDARD SYMBOL <br />IMMEDIATELY TO THE LEFT OF THE CONTROL BUTTON. GRADE 2 BRAILLE SHALL BE LOCATED IMMEDIATELY <br />BELOW THE CHARACTER OR SYMBOL. <br />1. PROVIDE HVAC DISTRIBUTION TO ACCOMMODATE PROPOSED LAYOUT, PEOPLE & EQUIPMENT LOADS AS REQUIRED. <br />2. VERIFY ALL THERMOSTAT LOCATIONS PRIOR TO INSTALLATION, LOCATIONS SHALL NOT CONFLICT WITH TENANT'S <br />FURNITURE. <br />3. PROVIDE SEPARATE ZONES WITH THERMOSTATS IN ALL CONFERENCE ROOMS SEATING MORE THAN 6 PEOPLE AND ALL <br />ROOMS WITH EXTERIOR GLAZING ON TWO SIDES. <br />4. PROVIDE A DEDICATED 24/7 HVAC UNIT IN IDF ROOM. REFER TO MECHANICAL ENGINEERING PLANS FOR MORE <br />INFORMATION. HVAC UNIT SHALL BE OUTSIDE OF ROOM & DUCTED IN. <br />5. PROVIDE FIRE DAMPERS AT PENETRATIONS TO ALL FIRE RATED PARTITIONS. <br />6. PROVIDE SOUND BOOTS ON ALL RETURN AIR DUCTS IN FULL HEIGHT WALLS. <br />7. ALL SUPPLY & RETURN AIR DIFFUSERS SHALL MATCH BUILDING STANDARD. <br />8. PROVIDE LINEAR DIFFUSERS IN GYPSUM BOARD LOCATIONS. ALL LINEAR DIFFUSERS SHALL BE TRIMLESS TYPE. <br />PROVIDE CUT SHEET FOR REVIEW. <br />9. WHERE EXPOSED CEILINGS OCCUR, EXISTING VAV BOXES SHALL BE RELOCATED TO NEAREST SUSPENDED <br />ACOUSTICAL CEILING AREA. <br />1. ADHESIVES, GENERAL: DO NOT USE ADHESIVES THAT CONTAIN UREA FORMALDEHYDE. <br />2. WOOD GLUE: PROVIDE ALIPHATIC-RESIN, POLYURETHANE, OR RESORCINOL WOOD GLUE RECOMMENDED BY <br />MANUFACTURER FOR GENERAL CARPENTRY USE. VOC CONTENT SHALL NOT EXCEED 30 G/L WHEN <br />CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24). <br />3. MULTIPURPOSE CONSTRUCTION ADHESIVE: PROVIDE FORMULATION COMPLYING WITH ASTM D3498 THAT IS <br />RECOMMENDED FOR INDICATED USE BY ADHESIVE MANUFACTURER. VOC CONTENT SHALL NOT EXCEED 70 G/L <br />WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24). <br />4. CONTACT ADHESIVE: PROVIDE PRODUCT RECOMMENDED FOR INDICATED USE BY MANUFACTURER. VOC <br />CONTENT SHALL NOT EXCEED 250 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA <br />METHOD 24). <br />5. VOC CONTENT OF INTERIOR SEALANTS; PROVIDE SEALANTS AND SEALANT PRIMERS FOR USE INSIDE THE <br />WEATHERPROOFING SYSTEM THAT COMPLY WITH THE FOLLOWING LIMITS FOR VOC CONTENT WHEN <br />CALCULATED ACCORDING TO CFR 40 59, SUBPART D (EPA METHOD 24): <br />A. ARCHITECTURAL SEALANTS: VOC LIMIT NOT MORE THAN 250 G/L. <br />B. SEALANT PRIMERS FOR NON-POROUS SUBSTRATES: NOT MORE 250 G/L. <br />C. SEALANT PRIMERS FOR POROUS SUBSTRATES: NOT MORE THAN 775 G/L. <br />1. NO FINISH SUBSTITUTIONS MAY BE MADE WITHOUT PRIOR W RITTEN AUTHORIZATION BY HENDY. <br />2. ALL FINISHES SHALL BE APPLIED IN STRICT ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS, <br />UNLESS NOTED OTHERWISE, AND SHALL CONFORM TO CHAPTER 8 OF THE CALIFORNIA BUILDING CODE. <br />3. APPLICATION OF CONTROLLED INTERIOR FINISHES SHALL BE IN ACCORDANCE WITH SECTIONS 803 AND <br />804 OF THE CALIFORNIA BUILDING CODE. <br />4. MAXIMUM FLAME SPREAD CLASSIFICATION OF FINISH MATERIALS USED ON INTERIOR WALLS AND <br />CEILINGS SHALL NOT EXCEED THAT SET FORTH IN TABLE 803.9 OF THE CALIFORNIA BUILDING CODE. <br />5. SMOKE DENSITY OF MATERIALS SHALL BE NO GREATER THAN 450 WHEN TESTED IN ACCORDANCE WITH <br />SECTION 803 OF THE CALIFORNIA BUILDING CODE. <br />1. FIELD VERIFY EXISTING CONDITION OF FLOORS RECEIVING FINISHES. ALL FLOORS SHALL BE CLEAN, <br />DRY, FREE OF DUST, GREASE, WAX, CURING AGENTS, EXCESSIVE ALKALINITY, PAINT, OLD ADHESIVE <br />AND ANY FOREIGN SUBSTANCE THAT WOULD PROHIBIT PROPER BONDING OF ANY FLOOR COVERING <br />MATERIAL. CONTRACTOR SHALL INCLUDE ALL REQUIRED FLOOR PREPARATION IN BID. PROVIDE PRICE <br />TO FLOAT FLOOR WHERE NECESSARY TO ACHIEVE TOLERANCE OF 1/4'' MAX. IN 10'-0'' SPAN. <br />2. PREPARE ALL FLOORS TO RECEIVE FINISHES. PROVIDE CALCIUM CHLORIDE TESTING IN SEVERAL AREAS <br />OF TENANT FLOOR AREA AND PROVIDE TEST RESULTS TO HENDY. <br />3. ALL CONCRETE SUBFLOORS SHALL BE TREATED FOR MOISTURE PRIOR TO INSTALLATION OF ANY <br />FLOOR COVERING. RATINGS SHALL BE IN ACCORDANCE WITH THOSE AS CONSIDERED ACCEPTABLE BY <br />THE MANUFACTURER FOR THE SPECIFIED PRODUCTS. PROVIDE CORRECTIVE MEASURES AT <br />SUBFLOORS EXCEEDING THESE MOISTURE RATINGS. <br />4. SUBMIT SEAMING DIAGRAM WITH FLOORING SUBMITTAL. <br />5. FLOORING SHALL EXTEND TO BACK WALL WHERE ACCESSIBLE SINK CABINETS OCCUR. <br />6. FLOORING SHALL MEET ALL CURRENT NON-SLIP STANDARDS AND APPLICABLE CODES AND/OR <br />AUTHORITY'S REQUIREMENTS. PROVIDE NON-SLIP COATINGS AS NECESSARY TO MEET THESE <br />REQUIREMENTS. <br />7. AFTER CLEANING, THE FLOORING CONTRACTOR SHALL PROVIDE (2) APPLICATIONS OF AN APPROVED <br />NON-SLIP WAX TO ALL RESILIENT TILE FLOOR, WHICH SHALL BE THOROUGHLY MACHINE-BUFFED AND IN <br />CONDITION ACCEPTABLE TO HENDY. <br />8. ALL VINYL COMPOSITION TILES SHALL BE INSTALLED WITH FULL TILE FROM TRANSITION AT DOOR AND <br />FULL TILE FROM WALL PERPENDICULAR TO DOOR, U.N.O. <br />9. PROVIDE CORK RUBBER FLOOR TILE MADE WITH ADHESIVES AND BINDERS THAT DO NOT CONTAIN <br />UREA-FORMALDEHYDE RESINS. <br />10. PROVIDE CORK RUBBER FLOOR TILE WATER-RESISTANT ADHESIVE AS RECOMMENDED BY <br />MANUFACTURER TO SUIT CORK RUBBER FLOORING AND SUBSTRATE CONDITIONS INDICATED. USE <br />ADHESIVES THAT HAVE A VOC CONTENT OF NOT MORE THAN 50 G/L WHEN CALCULATED ACCORDING TO <br />40 CFR 59, SUBPART D (EPA 24). <br />11. PROVIDE SHEET VINYL FLOOR COVERING WATER RESISTANT ADHESIVE RECOMMENDED BY <br />MANUFACTURER TO SUIT SUCH MATERIALS AND SUBSTRATE CONDITIONS. USE ADHESIVES THAT HAVE <br />A VOC CONTENT OF NOT MORE THAN 50 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D <br />(EPA 24). <br />12. PROVIDE STATIC-CONTROL ADHESIVE PRODUCT THAT PRODUCES CONDUCTIVE CONTINUITY OF VCT <br />AND ASPHALT TILE FLOOR COVERING SYSTEM WITH VOC CONTENT OF NOT MORE THAN 50 G/L WHEN <br />CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). <br />13. FLOAT FLOOR AT TILE TO CARPET TRANSITIONS, RAMP IN DIRECTION OF CARPET. <br />14. THE MAXIMUM PILE HEIGHT OF CARPET SHALL BE 1/4 INCH. EXPOSED EDGES OF CARPET SHALL BE <br />FASTENED TO FLOOR SURFACES AND HAVE TRIM ALONG THE ENTIRE LENGTH OF THE EXPOSED EDGE. <br />15. CARPET SHALL BE INSTALLED IN ACCORDANCE WITH GUIDELINES SET FORTH BY THE CARPET AND RUG <br />INSTITUTE'S CURRENT STANDARD FOR INSTALLATION OF COMMERCIAL TEXTILE FLOOR COVERING <br />MATERIALS. ALL SEAMS MUST BE PROPERLY SEALED USING A CONTINUOUS BEAD OF SEAM ADHESIVE <br />LARGE ENOUGH TO COVER THE PRIMARY BACKING, YARN BUNDLES AND SECONDARY BACKING. <br />16. PROVIDE CARPET TILE AND CUSHION PRODUCTS PER SPECIFICATION THAT COMPLY WITH TESTING AND <br />PRODUCT REQUIREMENTS OF CARPET AND RUG INSTITUTE'S “GREEN LABEL PLUS”PROGRAM. <br />17. PROVIDE CARPET ADHESIVES THAT ARE WATER RESISTANT, MILDEW RESISTANT, NON-STAINING, TYPE <br />THAT SUIT PRODUCTS AND SUBFLOOR CONDITIONS INDICATED, THAT COMPLIES WITH FLAMMABILITY <br />REQUIREMENTS FOR INSTALLED CARPET AND THAT IS RECOMMENDED BY THE MANUFACTURER. USE <br />CARPET ADHESIVE WITH VOC CONTENT OF NOT MORE THAN 50 G/L L WHEN CALCULATED ACCORDING <br />TO 40 CFR 59, SUBPART D (EPA 24). <br />18. ALL CARPET INSTALLATION SHALL BE ACCOMPLISHED BY A FLOOR COVERING FIRM OR INSTALLER <br />CERTIFIED BY THE FCIB, FCICA OR CFI; AND SHALL BE INSTALLED IN ACCORDANCE WITH THE <br />MANUFACTURER'S INSTALLATION INSTRUCTIONS. <br />19. PROVIDE TRANSITION STRIPS AS SPECIFIED AT ALL FLOORING TRANSITIONS. SUBMIT TRANSITION <br />SAMPLE TO HENDY FOR REVIEW AND COLOR SELECTION. <br />20. ALL TRANSITIONS AT DOORS TO OCCUR UNDER CENTERLINE OF DOOR IN CLOSED POSITION, U.N.O. <br />TRANSITIONS AT CASED OPENINGS SHALL BE VERIFIED WITH HENDY. <br />21. INSTALL WALL FINISH FOR THE FULL HEIGHT OF THE PARTITION WITHOUT BASE. THERE SHALL BE NO <br />UNFINISHED GAPS OF GYP. BD. AT THE BASE. <br />22. PROVIDE MINIMUM 2" WIDE X LENGTH OF STEP WARNING STRIPE IN CONTRASTING COLOR OF <br />COORDINATING FLOORING AT FIRST AND LAST STAIR TREADS AS REQUIRED BY CODE. <br />1. PAINT AND WALLCOVERING SUBCONTRACTORS SHALL EXAMINE WALLS PRIOR TO FINISH <br />APPLICATION. BEGINNING WORK IMPLIES ACCEPTANCE OF THEIR CONDITION. <br />2. ALL EXISTING WALLS SHALL BE PAINTED, U.N.O. <br />3. PAINT AND PRIMERS SHALL BE APPLIED IN ACCORDANCE WITH THE MANUFACTURER'S <br />SPECIFICATION FOR THAT PARTICULAR SURFACE. <br />4. PROVIDE INTERIOR PAINT PRODUCTS THAT COMPLY WITH THE FOLLOWING LIMITS FOR VOC <br />CONTENT WHEN CALCULATED ACCORDING TO 40 CFR 59M SUBPART D (EPA METHOD 24): <br />A.FLAT PAINTS, COATINGS, TOPCOATS, AND PRIMERS: VOC CONTENT < 50 G/L. <br />B.NON-FLAT PAINTS, COATINGS, AND PRIMERS: VOC CONTENT < 150 G/L. <br />C.FLOOR COATINGS: VOC CONTENT < 100 G/L. <br />5.RESTRICTED COMPONENTS: PAINTS AND COATINGS SHALL NOT CONTAIN ANY OF THE FOLLOWING: <br />ACROLEIN, ACRYLONITRILE, ANTIMONY, BENZENE, BUTYL BENZYL PHTHALATE, CADMIUM, DI (2- <br />ETHYLHEXYL PHTHALATE, DI-N-BUTYL PHTHALATE, DI-N-OCTYL PHTHALATE, 1,2- <br />DICHLOROBENZENE, DIETHYL PHTHALATE, DIMENTHYL PHTHALATE, ETHYLBENZENE, <br />FORMALDEHYDE, HEXAVALENT CHROMIUM, ISOPHORONE, LEAD, MERCURY. METHYL ETHYL <br />KETONE, METHYL ISOBUTYL KETONE, METHYLENE CHLORIDE, NAPHTHALENE, TOLUENE <br />(METHYLBENZENE), 1,1,1-TRICLOROETHANE, VINYL CHLORIDE. <br />6.ALL PAINTED WALLS SHALL RECEIVE ONE (1) PRIMER COAT AND TWO (2) COATS OF PAINT, U.N.O. <br />PAINT FINISH SHALL HAVE CONSISTENT COVERAGE, FREE OF ROLLER OR BRUSH MARKS. <br />7.WHERE PAINT COLORS CHANGE, CORNERS SHALL BE CUT-IN AND FREE OF OVERLAP. <br />8.ALL GYP. BD. CEILINGS AND SOFFITS SHALL HAVE A LEVEL 5 FINISH AND RECEIVE TWO (2) COATS <br />FLAT PAINT OVER (1) COAT PRIMER, U.N.O. <br />9.PAINT FINISH ON METAL SURFACES INCLUDING DOOR FRAMES, HANDRAILS, ELEVATOR DOORS, ETC. <br />SHALL BE SEMI-GLOSS, U.N.O. <br />10.ALL METAL ACCESS DOORS SHALL BE PAINTED TO MATCH ADJACENT WALL OR CEILING FINISH. <br />11.SUBMIT SEAMING MOCK-UP SAMPLES ON GYP. BD. OF ALL SPECIFIED WALLCOVERINGS TO HENDY <br />FOR APPROVAL PRIOR TO PLACEMENT OF ORDER. <br />12.ALL SURFACES RECEIVING WALLCOVERING SHALL BE PROPERLY PREPARED PER MANUFACTURER'S <br />SPECIFICATIONS. PRIMER AND ADHESIVE SHALL BE FROM SAME MANUFACTURER OR OTHER <br />APPROVED/ COMPATIBLE PRODUCTS. <br />13.PROVIDE WALLCOVERING ADHESIVE THAT IS MILDEW RESISTANT AND NON-STAINING FOR USE WITH <br />SPECIFIC WALLCOVERING AND SUBSTRATE APPLICATION, AS RECOMMENDED IN WRITING BY <br />WALLCOVERING MANUFACTURER. USE WALLCOVERING ADHESIVE WITH VOC CONTENT OF NOT <br />MORE THAN 50 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). <br />14.COORDINATE WALLCOVERING INSTALLATION IN OR ON MILLWORK WITH SUB-CONTRACTORS. <br />15.WALLCOVERING SHALL BE HUNG IN SEQUENCE AND FROM SAME DYE LOT. <br />16.POLYOLEFIN WALLCOVERING SHALL RECEIVE SCOTCH GUARD APPLICATION IF NOT FACTORY <br />APPLIED. <br />17.INSTALL WALLCOVERING PER MANUFACTURER'S SPECIFICATIONS. WALLCOVERING SHALL BE <br />INSTALLED SMOOTH, WITHOUT WRINKLES, BUBBLES OR LOOSE EDGES. ALL PASTE AND BRUSH <br />MARKS SHALL BE REMOVED. WALL COVERING TERMINATIONS SHALL BE CUT STRAIGHT AND <br />SQUARE. WALLCOVERING AT ALL REVEALS SHALL RETURN INTO REVEAL, U.N.O. <br />18.INSTALL BASE LENGTHS AS LONG AS POSSIBLE. WRAP BASE AROUND CORNER AND CONTINUE A <br />MIN. OF 6 INCHES BEYOND BEFORE SEAMING OR USE PRE-FORMED CORNER PIECES. <br />19.COORDINATE THE INSTALLATION OF WALL BASE WITH MILLWORK. OMIT BASE WHERE BUILT-IN <br />CABINETS ARE INDICATED. PROVIDE BASE AT BACK WALL INSIDE ACCESSIBLE SINK CABINET. <br />1. COMPLY WITH TCNA'S "HANDBOOK FOR CERAMIC, GLASS, AND STONE TILE INSTALLATION" METHODS <br />AND WITH PARTS OF ANSI A108 SERIES" SPECIFICATIONS FOR INSTALLATION OF CERAMIC TILE" THAT <br />RE REFERENCE IN TCNA INSTALLATION METHODS. APPLY TO TYPES OF SETTING AND GROUTING <br />MATERIALS USED. <br />2. EXAMINE TILE SUBSTRATES, AREAS, AND CONDITIONS FOR COMPLIANCE WITH INSTALLATION <br />TOLERANCES AND OTHER CONDITIONS AFFECTING THE WORK. PROCEED WITH INSTALLATION ONLY <br />AFTER UNSATISFACTORY CONDITIONS HAVE BEEN CORRECTED. FILL CRACKS, HOLES, AND <br />DEPRESSIONS IN CONCRETE SUBSTRATES WITH TROWELABLE LEVELING AND PATCHING COMPOUND <br />SPECIFICALLY RECOMMENDED BY TILE MANUFACTURER. SEE ALSO "PATCHING AND PREPPING" <br />NOTES / IA-G1. <br />3. WHERE TILE FLOOR SLOPES TO DRAIN, PROVIDE WATERPROOFING OVER REINFORCED MORTAR <br />BED, SLOPE 1/4" PER FOOT MAX TOWARD DRAIN. <br />4. AT WET WALLS AND AREAS SUCH AS SHOWERS, PROVIDE WATERPROOF MEMBRANE COMPLIANT <br />WITH ANSI A118.10 AND AS RECOMMENDED BY THE MANUFACTURER FOR THE APPLICATION <br />INDICATED. INCLUDE REINFORCEMENT AND ACCESSORIES RECOMMENDED BY THE MANUFACTURER. <br />5. PROVIDE EXPANSION JOINTS AND OTHER SEALANT-FILLED JOINTS, INCLUDING CONTROL JOINT, <br />CONTRACTION, AND ISOLATION JOINTS. CONFIRM JOINT LOCATIONS WITH HENDY PRIOR TO <br />INSTALLATION. DO NOT SAW-CUT JOINTS AFTER INSTALLING TILES. <br />6. GROUT JOINTS AT TILES SHALL BE 1/8" MAX., U.N.O. GROUT SHALL BE SEALED WITH AQUAMIX <br />"SEALER'S CHOICE" PER MANUFACTURER'S WRITTEN SPECIFICATIONS. <br />7. PROVIDE CERAMIC TILE ADHESIVE CONTAINING VOC CONTENT OF NOT MORE THAN 50 G/L WHEN <br />CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA 24). <br />8. PROVIDE CERAMIC TILE SETTING GROUTING MATERIALS THAT ARE CHEMICAL RESISTANT, WATER- <br />CLEANABLE, TILE-SETTING AND GROUTING EPOXY COMPLIANT WITH ANSI A118.3, WITH A VOC <br />CONTENT OF NOT MORE THAN 65 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D <br />(EPA 24). <br />9. ON COMPLETION OF PLACEMENT AND GROUTING, CLEAN ALL CERAMIC TILE SURFACES SO THEY ARE <br />FREE OF FOREIGN MATTER. <br />1. FABRICATE CABINETS AND COUNTERTOPS WITH WOOD AND WOOD-BASED PRODUCTS PRODUCED <br />FROM NOT LESS THAN 70% OF WOOD OBTAINED FROM FORESTS CERTIFIED BY AN FSC-ACCREDITED <br />CERTIFICATION BODY TO COMPLY WITH FSC STD-01-001, FSC PRINCIPLES AND CRITERIA FOR FOREST <br />STEWARDSHIP. <br />2. REVIEW OF SHOP DRAWINGS SHALL BE GENERAL AND/OR FOR AESTHETIC INTERPRETATION, AND <br />EXCEPT WHERE OTHERWISE INDICATED, SHALL NOT BE CONSTRUED AS PERMITTING ANY DEPARTURE <br />FROM CONTRACT OR LEASE REQUIREMENT, RELIEVING THE CONTRACTOR OF RESPONSIBILITY FOR <br />ANY ERROR IN DETAILS OR INSTRUCTIONS PREVIOUSLY FURNISHED BY HENDY. THE CONTRACTOR <br />SHALL CORRECT ERRORS IN AND OMISSIONS FROM THE WORK WITHOUT ADDITIONAL COST TO THE <br />TENANT WHETHER OR NOT WORK WAS INSTALLED AS PER REVIEWED SHOP DRAWINGS. <br />3. WOOD VENEER CABINETS SHALL CONFORM TO AWI/WIC STANDARDS FOR PREMIUM GRADE MILLWORK. <br />ALL PLASTIC LAMINATE CABINETS SHALL BE CUSTOM GRADE MILLWORK. <br />4. PROVIDE WOOD STAIN PRODUCTS THAT COMPLY WITH THE FOLLOWING LIMITS FOR VOC CONTENT <br />WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24): <br />A. CLEAR WOOD FINISHES, VARNISHES: VOC CONTENT NOT MORE THAN 350 G/L. <br />B. CLEAR WOOD FINISHES, LACQUERS: VOC CONTENT NOT MORE THAN 550 G/L. <br />C. STAINS: VOC CONTENT NOT MORE THAN 250 G/L. <br />5. PROVIDE MANUFACTURED WOOD CASEWORK, INCLUDING COUNTERTOPS, MADE WITH ADHESIVES AND <br />COMPOSITE WOOD PRODUCTS THAT DO NOT CONTAIN UREA FORMALDEHYDE. <br />6. PROVIDE PARTICLE BOARD COMPLIANT WITH ANSI A208.1, GRADE M-2, MADE WITH BINDER CONTAINING <br />NO UREA-FORMALDEHYDE RESIN. <br />7. PROVIDE MEDIUM-DENSITY FIBERBOARD: PROVIDE PRODUCTS COMPLIANT WITH ANSI A208.2, GRADE <br />130, MADE WITH BINDER CONTAINING NO UREA FORMALDEHYDE. <br />8. PLASTIC LAMINATE ADHESIVE AND SEALANT: PROVIDE SINGLE-COMPONENT, MILDEW RESISTANT, <br />NEUTRAL CURING SILICONE/LATEX SEALANT RECOMMENDED BY PLASTIC PANELING MANUFACTURER <br />AND COMPLIANT WITH REQUIREMENTS DIVISION 07 SECTION “JOINT SEALANTS”. VOC CONTENT SHALL <br />NOT EXCEED 250 G/L WHEN CALCULATED ACCORDING TO 40 CFR 59, SUBPART D (EPA METHOD 24). <br />9. PROVIDE VENEER-FACED PANEL PRODUCTS (HARDWOOD PLYWOOD) THAT ARE COMPLIANT WITH <br />HPVA-HP-1, MADE WITH ADHESIVE CONTAINING NO UREA FORMALDEHYDE. <br />10. MILLWORKER SHALL VERIFY SITE CONDITIONS FOR DELIVERY ACCESS PRIOR TO INSTALLATION. <br />11. MILLWORKER SHALL VERIFY ALL DIMENSIONS AND CONDITIONS ON JOB SITE. ALL DISCREPANCIES <br />BETWEEN HENDY'S DRAWINGS AND EXISTING CONDITIONS SHALL IMMEDIATELY BE BROUGHT TO THE <br />ATTENTION OF HENDY FOR CLARIFICATION PRIOR TO THE COMMENCEMENT OF WORK. <br />12. ALL BUILT-IN PLUMBING FIXTURES, ELECTRICAL AND APPLIANCES SHALL BE SUPPLIED AND INSTALLED <br />BY GENERAL CONTRACTOR. CUT-OUTS SHALL BE PERFORMED BY MILLWORKER. GENERAL <br />CONTRACTOR SHALL SUPPLY INFORMATION AND COORDINATE CLEARANCES AND CUTOUTS WITH <br />MILLWORKER. <br />13. ALL CABINETS SHALL BE CHECKED FOR PROPER MECHANICAL OPERATION. <br />14. ALL CABINETRY SHALL BE ATTACHED TO WALLS OR STRUCTURE AS REQUIRED FOR STABLE <br />INSTALLATION AND USE. MILLWORKER SHALL COORDINATE BACKING LOCATIONS WITH GENERAL <br />CONTRACTOR AS REQUIRED TO SUPPORT WALL HUNG CABINETS. <br />15. ALL PAINTED WOOD SURFACES SHALL BE PROPERLY SEALED, SANDED AND PRIMED TO RECEIVE FINAL <br />FINISH COAT. <br />16. ALL PLASTIC LAMINATE SHEETS SHALL BE PROPERLY BACKED TO PREVENT WARPAGE OF THE <br />SUBSTRATE. <br />17. ALL MILLWORK SHALL BE FABRICATED OF MINIMUM 3/4" STOCK MATERIAL. <br />18. ALL MILLWORK SHALL BE SCRIBED TO WALLS, FLOORS AND/OR CEILING WHERE OCCURS. <br />19. COUNTERTOP AND BASE CABINET SHALL ALIGN TO OUTSIDE END OF CABINET WHERE NO WALL <br />OCCURS, U.N.O.. ALL EXPOSED FACES OF CABINETRY SHALL BE FINISHED. <br />20. PROVIDE (3) HINGES ON CABINET DOORS EXCEEDING 14 INCHES IN WIDTH. <br />21. SUBMIT MIN. (3) THREE EACH WOOD, PAINT AND/OR STAIN SAMPLES AND FINISHES FOR APPROVAL BY <br />HENDY PRIOR TO FABRICATION ON 8" X 8" MINIMUM SAMPLES. <br />22. ALL WOOD VENEER AND PLASTIC LAMINATE DOOR PANELS SHALL BE VERTICAL GRAINED, UNLESS <br />NOTED OTHERWISE. <br />23. DOOR AND DRAWER EDGES SHALL BE PLASTIC LAMINATE TO MATCH PLASTIC LAMINATE DOOR OR <br />DRAWER FACE. SELF EDGES ON PLASTIC LAMINATE COUNTERTOPS SHALL MATCH COUNTERTOP. <br />HHENDY.COM <br />T (949) 851-3080 <br />4770 Campus Dr., Suite 100 <br />Newport Beach, CA 92660 <br />H ndy <br />ISSUES AND REVISIONS <br />JOB NUMBER <br />SCALE <br />PROJECT <br />TEAM <br />All specifications, drawings, concepts, designs, arrangements, intellectual and written material represented herein constitute <br />unique and unpublished work of H. Hendy Associates and may not be copied, used by or disclosed to others without written <br />consent of H. Hendy Associates. <br /> 2023 H.HendyAssociatesc <br />DATE <br />04463.0000.24 <br />3080 S. HARBOR BLVD. <br />SANTA ANA, CA 92704 <br />GENERAL NOTES <br />IA-G2 <br />MCGUFF <br />AB/CD <br />POWER & COMMUNICATIONS <br />PLUMBING <br />CEILING <br />FIRE SPRINKLERS <br />LIGHT FIXTURES <br />EXISTING ELEVATORS <br />MECHANICAL DEVICES & DISTRIBUTION <br />SEALANTS & ADHESIVES <br />FINISHES <br />FLOOR FINISHES & TRANSITIONS <br />PAINT & WALL FINISHES <br />TILE FINISHES <br />MILLWORK <br />NONE <br />1.SIGNAGE IDENTIFYING ROOMS OR BUILDING AREAS SHALL BE LOCATED ON THE WALL NEXT TO THE <br />LATCH SIDE OF THE DOOR MAXIMUM 60 INCHES A.F.F. AND MINIMUM 48”A.F.F. <br />2.POST INTERNATIONAL SYMBOL OF ACCESSIBILITY ON OR ADJACENT TO ALL DISABLED ACCESSIBLE <br />BUILDING ENTRANCES. <br />SIGNAGE <br />NO. DESCRIPTION DATE <br />PLAN CHECK SUBMITTAL 3/17/25