SCALE: NONESCALE: NONE <br />SCALE: NONESCALE: NONE <br />SCALE: NONE <br />SCALE: NONE <br />1 1/2"UP TO 125 <br />SEE NOTE 2 <br />RECEPTOR <br />APPROVED <br />SLOPE TO <br />S.P.x1.5+2" <br />S.P.x0.5+1" <br />S.P.x1.5+2" <br />S.P.x1.5+2" <br />THE NIPPLE ON THE UNIT. <br />LEAST THE SAME SIZE AS <br />DRAIN LINE SHALL BE AT <br />S.P. = SYSTEM STATIC PRESSURE-INCHES <br />BLOW THRU <br />DRAW THRU <br />'A' 'B'UNIT TYPE <br />41-90 1 1/4 " <br />1" <br /> 3/4 " <br />21-40 <br />UP TO 20 <br />DRAIN SIZETONS <br />6" <br />MIN. <br />3" <br />'A''B' <br />DIELECTRIC UNION <br />HVAC EQUIPMENT <br />TYPE 'M' COPPER TUBING WITH <br />WROUGHT COPPER FITTING <br />NOTES: <br />1. ALL INTERIOR CONDENSATE DRAINS ABOVE CEILING SHALL BE INSULATED. <br />2. IF HORIZONTAL RUN IS GREATER THAN 15 FT., INSTALL VENT, SAME SIZE AS DRAIN. <br />3. PROVIDE SECONDARY CONDENSATE DRAIN (SCD) SAME SIZE AS THE PRIMARY DRAIN. TERMINATE <br />SCD AT 1-INCH BELOW THE CEILING WITH DECORATIVE ESCUTCHEON. COORDINATE TERMINATION <br />LOCATION WITH THE <br />ARCHITECT. <br />1 VENT THROUGH ROOF DETAIL4ROOF PIPE SUPPORT <br />2 CONDENSATE DRAIN DETAIL5WALL CLEANOUT <br />3 PUMPED CONDENSATE DRAIN DETAIL (AS NEEDED) <br />6 FLOOR CLEANOUT <br />SET IN BED OF MASTIC. VERIFY MASTIC TYPE <br />WITH ROOF MEMBRANE MANUFACTURER AND <br />GENERAL CONTRACTOR (COORD. WITH DIV. 7 <br />SPECS). <br />NOTES: <br />1. SUPPORT PIPE AT INTERVAL PER CURRENT CPC AND AT EACH <br />ELBOW. <br />U-CLAMP, 1/8" STEEL, 1-5/8" <br />WIDE. <br />PIPE INSULATION AND <br />JACKET (WHERE <br />APPLICABLE) <br />PRE-ASSEMBLED STAINLESS <br />STEEL THREADED SUPPORT RODS <br />AND CHANNEL STRUT. <br />PIPE <br />PIPE SADDLE STEEL REINFORCING BOOT <br />ROOF <br />ROOFING <br />NOTE: <br />SEE ARCHITECTURAL FOR <br />WATER PROOFING <br />VENT TERMINATION <br />HEIGHT PER LOCAL <br />CODE REQUIREMENTS <br />CAULKING MASTIC (WATER <br />TIGHT SEAL) <br />COUNTER FLASHING <br />SLEEVE <br />NON-HARDENING <br />ELASTOMER SEALANT <br />SEAMLESS LEAD <br />ROOF FLASHING <br />MOP LEAD IN WITH <br />ROOFING <br />ROOF CONSTRUCTION, <br />REF. ARCH. DWGS.SEE PLAN <br />FOR SIZE <br />MATERIAL <br />NO-HUB COUPLING, <br />MIN 4 BANDS (TYP). <br />AS REQUIRED. <br />CONCRETE SURFACE <br />CLEANOUT COVER <br />CLEANOUT PLUG <br />FINISHED FLOOR <br />OR FLOOR COVERING <br />CAULKING FERRULE <br />WALL <br />SAME AS CLEANOUT <br />BALANCE OF PIPING <br />WASTE OR VENT <br />MAY EXTEND AS A <br />TO GRADE <br />1/8" C.I. BEND <br />FLOOR LINE <br />STAINLESS STEEL <br />WALLCOVER & SCREW <br />PLUGGED TEE WITH CLEANOUT <br />CAP. <br />1" <br />1 1/4" <br />3/4" <br />EQMT. <br />(TONS REF) <br />THRU 20 <br />THRU 40 <br />THRU 90 <br />THRU 125 1 1/2" <br />MECH. CONTRACTOR <br />REQUIRED. <br />ADAPT TO UNIT AS <br />SCREWED CLEANOUT <br />PLUGS. (TYP.) <br />VENT <br />NOT LESS THAN 8" <br />ADAPTER <br />A.C. UNIT BY <br />CEILING <br />1% SLOPE <br />NOTES : <br />CHECK VALVE <br />SOV <br />CD <br />EQUIPMENT <br />HOUSEPAD/SUPPORT <br />BY MECH. CONTR. <br />CD, PROVIDE APPROVED PIPE <br />SUPPORT & INSULATION <br />PROVIDE APPROVED PIPE <br />SUPPORT & INSULATION <br />CONDENSATE PUMP BY MECH. CONTRACTOR <br />AS NEEDED, INSTALLED BY PLBG. CONTR. <br />(PROVIDE APPROVED SEISMIC SUPPORT) <br />FCD, SEE FLOOR <br />PLANS FOR <br />CONTINUATION <br />CD/FCD <br />SIZE (IN.) <br />1. PROVIDE SECONDARY CONDENSATE DRAIN (SCD) SAME SIZE AS THE PRIMARY DRAIN. <br />TERMINATE SCD AT 1-INCH BELOW THE CEILING WITH DECORATIVE ESCUTCHEON. <br />COORDINATE TERMINATION LOCATION WITH THE ARCHITECT. <br />SEE NOTE-1 <br />© Gensler <br />Date Description <br />Project Name <br />Project Number <br />Description <br />Scale <br />Seal / Signature <br />2015 <br />NOT FOR <br />CONSTRUCTION <br />Tel 949.863.9434 <br />Fax 949-553-1676 <br />4675 MacArthur Court <br />Suite 100 <br />Newport Beach, CA <br />92600 <br />USA <br />Job No.: <br />Contact: <br />www.glumac.com <br />18200 Von Karman Ave., Suite 100 <br />Irvine, CA 92612 <br />T. 949.833.8190 <br />6/12/2024 7:40:13 PM <br />BIM 360://007.3757.000 - Caribou Industries - 3rd & Broadway/3RD-B_MEP_WEST_R20.rvt <br />R1-P9.2 <br />PLUMBING DETAILS <br />21US00608 <br />3rd & Broadway West <br />1103 North Broadway <br />Santa Ana, CA 92701 <br />21US00608 <br />TG <br />1 9/21/2021 REISSUE FOR PLAN CHECK <br />2 01/18/2022 REISSUE FOR PLAN CHECK <br />4 06/17/2024 REVISION TO PERMIT <br />EOR: SEAN AGUON <br />LIC#: M41274 <br />10/11/2024