SCALE: NONESCALE: NONESCALE: NONE
<br />SCALE: NONE
<br />SCALE: NONE
<br />SCALE: NONE
<br />SCALE: NONE
<br />1 PIPE PENETRATION THRU FIRE RATED CONC. WALL & FLOOR3PIPE PENETRATION THROUGH FIRE RATED CONC. WALL & FLOOR5PIPE PENETRATION NOTES
<br />2 PIPE PENETRATION THRU FIRE RATED GYPSUM WALL
<br />6 NO-HUB PIPE SWAY BRACING FOR HORIZONTAL PIPING
<br />4 NO-HUB PIPE BRACING FOR MULTIPLE FITTINGS
<br />7 TYPICAL SUB-WATER METER PIPING DETAIL
<br />M
<br />System No. C-AJ-1421
<br />SECTION A-A
<br />1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3) CONCRETE. WALL
<br />MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 6 IN. (152 MM).
<br />SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
<br />2. METALLIC SLEEVE - (OPTIONAL) NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL
<br />ASSEMBLY, FLUSH WITH FLOOR OR WALL
<br />SURFACES.3. THROUGH-PENETRANT - ONE METALLIC PIPE OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE
<br />ANNULAR SPACE BETWEEN PIPE, TUBE OR CONDUIT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (0 MM) (POINT CONTACT) TO MAX 5-3/8 IN. (137 MM). PIPE OR
<br />CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES OR CONDUITS MAY
<br />BE USED:
<br />A. STEEL PIPE - NOM 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
<br />B. IRON PIPE - NOM 4 IN. (102 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
<br />C. COPPER PIPE - NOM 4 IN. (102 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
<br />D. COPPER TUBING - NOM 4 IN. (102 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
<br />E. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL CONDUIT.
<br />F. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT).
<br />4. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
<br />A. PACKING MATERIAL - MIN 4 IN. (102 MM) THICKNESS OF MIN 4 PCF (64 KG/M3) MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A
<br />PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO
<br />ACCOMMODATE THE REQUIRED THICKNESS OF FILL
<br />MATERIAL.B. FILL, VOID OR CAVITY MATERIAL* - SEALANT - MIN 1/4 IN. (6 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF
<br />FLOOR OR WITH BOTH SURFACES OF WALL. FOR 3 HR RATED ASSEMBLIES, A MIN 1/4 IN. (6 MM) DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE
<br />CONCRETE/PIPE INTERFACE AT THE POINT CONTACT LOCATION ON THE TOP SURFACE OF FLOOR AND ON BOTH SURFACES OF WALL.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE SEALANT OR CP604 SELF-LEVELING FIRESTOP SEALANT. CP604 SHALL BE USED IN FLOOR
<br />APPLICATIONS ONLY. WHEN CP604 IS USED, F RATING IS 2
<br />HR.*BEARING THE UL CLASSIFICATION MARK
<br />A
<br />REPRODUCED BY HILTI, INC.
<br />COURTESY OF UNDERWRITERS
<br />LABORATORIES, INC.
<br />APRIL 26, 2004
<br />F Rating - 2 and 3 Hr (See Item 4B)
<br />T Rating = 0 Hr
<br />A
<br />4B
<br />2
<br />3
<br />4B
<br />1
<br />4A
<br />System No. C-AJ-1226
<br />SECTION A-A
<br />A
<br />REPRODUCED BY HILTI, INC. COURTESY
<br />OF UNDERWRITERS LABORATORIES,
<br />INC.
<br />JUNE 27, 2007
<br />F Rating - 3 Hr
<br />T Rating - 0 Hr
<br />L Rating At Ambient - Less Than 1 CFM/Sq Ft
<br />L Rating At 400 F - 4 CFM/Sq Ft
<br />Hilti Firestop Systems
<br />1. FLOOR OR WALL ASSEMBLY —MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL
<br />CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 32
<br />IN.2. METALLIC SLEEVE —(OPTIONAL) NOM 32 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH
<br />FLOOR OR WALL SURFACES OR EXTENDING A MAX OF 3 IN. ABOVE FLOOR OR BEYOND BOTH SURFACES OF WALL.
<br />2A. SHEET METAL SLEEVE —(OPTIONAL) MAX 6 IN. DIAM, MIN 26 GA GALV STEEL PROVIDED WITH A 26 GA GALV STEEL SQUARE FLANGE SPOT WELDED TO THE SLEEVE AT
<br />APPROX MID-HEIGHT, OR FLUSH WITH BOTTOM OF SLEEVE IN FLOORS, AND SIZED TO BE A MIN OF 2 IN. LARGER THAN THE SLEEVE DIAM. THE SLEEVE IS TO BE CAST IN PLACE
<br />AND MAY EXTEND A MAX OF 4 IN. BELOW THE BOTTOM OF THE DECK AND A MAX OF 1 IN. ABOVE THE TOP SURFACE OF THE CONCRETE
<br />FLOOR.2B. SHEET METAL SLEEVE —(OPTIONAL) - MAX 12 IN. DIAM, MIN 24 GA GALV STEEL PROVIDED WITH A 24 GA GALV STEEL SQUARE FLANGE SPOT WELDED TO THE SLEEVE AT
<br />APPROX MID-HEIGHT, OR FLUSH WITH BOTTOM OF SLEEVE IN FLOORS, AND SIZED TO BE A MIN OF 2 IN. LARGER THAN THE SLEEVE DIAM. THE SLEEVE IS TO BE CAST IN PLACE
<br />AND MAY EXTEND A MAX OF 4 IN. BELOW THE BOTTOM OF THE DECK AND A MAX OF 1 IN. ABOVE THE TOP SURFACE OF THE CONCRETE
<br />FLOOR.3. THROUGH-PENETRANT —ONE METALLIC PIPE, TUBE OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE
<br />ANNULAR SPACE BETWEEN PENETRANT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO MAX 1-7/8 IN. PENETRANT MAY BE INSTALLED WITH CONTINUOUS
<br />POINT CONTACT. PENETRANT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PENETRANTS MAY
<br />BE USED:
<br />A. STEEL PIPE —NOM 30 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
<br />B. IRON PIPE —NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
<br />C. COPPER PIPE —NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
<br />D. COPPER TUBING —NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
<br />E. CONDUIT —NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT.
<br />F. CONDUIT —NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT).
<br />4. FIRESTOP SYSTEM —THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
<br />A. PACKING MATERIAL —MIN 4 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL
<br />TO BE RECESSED FROM TOP SURFACE OF FLOOR OR SLEEVE OR FROM BOTH SURFACES OF WALL OR SLEEVE AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS
<br />OF FILL
<br />MATERIAL.B. FILL, VOID OR CAVITY MATERIAL*—SEALANT —MIN 1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR
<br />SLEEVE OR WITH BOTH SURFACES OF WALL OR SLEEVE. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BETWEEN PENETRANT AND CONCRETE OR SLEEVE, A MIN 1/4
<br />IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE OR SLEEVE/ PIPE PENETRANT INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH
<br />SURFACES OF WALL.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC —FS-ONE SEALANT
<br />*BEARING THE UL CLASSIFICATION MARK
<br />A
<br />2
<br />3
<br />4B
<br />3
<br />14B
<br />4A
<br />Hilti Firestop Systems
<br />C
<br />CLASSI FIED
<br />Classified by
<br />Underwriters Laboratories,
<br />Inc.
<br />to UL 1479 and
<br />CAN/ULC-S115
<br />US
<br />C
<br />CLASSI F IED
<br />Classified by
<br />Underwriters Laboratories,
<br />Inc.
<br />to UL 1479 and
<br />CAN/ULC-S115
<br />US
<br />Hilti Firestop Systems
<br />System No. W-L-1206
<br />SECTION A-A
<br />1. WALL ASSEMBLY —THE FIRE-RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U400 OR V400
<br />SERIES WALL AND PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
<br />A. STUDS —"C-T" SHAPED STUDS 1-5/8 IN. WIDE BY 2-1/2 IN. DEEP, FABRICATED FROM 25 MSG GALV STEEL, SPACED MAX 24 IN. OC.
<br />B. GYPSUM BOARD*—ONE LAYER OF NOM 1 IN. THICK, 24 IN. WIDE GYPSUM LINER AND ONE OR TWO LAYERS OF NOM 5/8 IN. THICK, 4 FT. WIDE GYPSUM BOARD WITH SQUARE OR TAPERED
<br />EDGES. THE GYPSUM BOARD TYPES, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL WALL AND PARTITION DESIGN. MAX
<br />DIAMOF OPENING IS 10-1/2 IN.
<br />1A. WALL ASSEMBLY —AS AN ALTERNATE TO THE ABOVE WALL ASSEMBLY, THE 1 OR 2 HR FIRE RATED GYPSUM BOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND
<br />IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300, U400 OR V400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING
<br />CONSTRUCTION FEATURES:
<br />A. STUDS —WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. STEEL STUDS TO BE MIN 2-1/2 IN. WIDE AND SPACED MAX 24 IN. OC. WOOD STUDS TO
<br />CONSIST OF NOM 2 BY 4 IN. LUMBER SPACED 16 IN. OC.
<br />B. GYPSUM BOARD*—THICKNESS, TYPE, NUMBER OF LAYERS AND FASTENERS AS REQUIRED IN THE INDIVIDUAL WALL AND PARTITION DESIGN. MAX DIAM OF OPENING IS 10-1/2 IN.
<br />THE HOURLY F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED.
<br />2. METALLIC SLEEVE —MAX 10-1/2 IN. DIAM CYLINDRICAL SLEEVE FABRICATED FROM MIN 0.016 IN. THICK (28 GAUGE) GALV SHEET STEEL AND HAVING A MIN 1 IN. LAP ALONG THE LONGITUDINAL
<br />SEAM. LENGTH OF STEEL SLEEVE TO BE EQUAL TO THICKNESS OF WALL. SLEEVE INSTALLED BY COILING THE SHEET STEEL TO A DIAM SMALLER THAN THE THROUGH OPENING, INSERTING THE
<br />COIL THROUGH THE OPENING AND RELEASING THE COIL TO LET IT UNCOIL AGAINST THE CIRCULAR CUTOUTS IN THE GYPSUM BOARD LAYERS. SLEEVE MAY ALSO BE FORMED OF NO. 8 STEEL
<br />WIRE MESH HAVING A MIN 1 IN. LAP ALONG THE LONGITUDINAL
<br />SEAM.3. THROUGH-PENETRANTS —ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE OF
<br />MIN 0 IN. (POINT CONTACT) TO MAX 1-7/8 IN. IS REQUIRED WITHIN FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE
<br />FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
<br />A. STEEL PIPE —NOM 8 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
<br />B. IRON PIPE —NOM 8 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
<br />C. CONDUIT —NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR 4 IN. DIAM STEEL CONDUIT.
<br />D. COPPER TUBING —NOM 4 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
<br />E. COPPER PIPE —NOM 4 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
<br />F. FLEXIBLE STEEL CONDUIT+—NOM 2 IN. DIAM (OR SMALLER) FLEXIBLE STEEL CONDUIT.
<br />SEE FLEXIBLE METAL CONDUIT (DXUZ) CATEGORY IN THE ELECTRICAL CONSTRUCTION EQUIPMENT DIRECTORY FOR NAMES OF MANUFACTURERS.
<br />4. FIRESTOP SYSTEM —THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
<br />A. PACKING MATERIAL —MIN 1-5/8 OR 2-1/4 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO SLEEVE ON ONE SIDE OF THE WALL AS PERMANENT FORM
<br />FOR 1 AND 2 HR WALLS, RESPECTIVELY. PACKING MATERIAL TO BE RECESSED FROM THE ROOM SIDE OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL
<br />MATERIAL. IN ALTERNATE WALL ASSEMBLY, PACKING MATERIAL TO BE FLUSH WITH EITHER SIDE OF THE WALL AND RECESSED FROM THE OTHER SIDE OF THE WALL TO ACCOMMODATE
<br />THE REQUIRED THICKNESS OF FILL
<br />MATERIAL.B. FILL, VOID OR CAVITY MATERIAL —SEALANT*—MIN 1-1/2 IN. THICKNESS APPLIED WITHIN SLEEVE, FLUSH WITH THE SURFACE OF WALL. AT THE POINT CONTACT LOCATION BETWEEN
<br />PIPE AND WALL, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE PIPE/WALL INTERFACE.
<br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC —FS-ONE SEALANT
<br />*BEARING THE UL CLASSIFICATION MARK
<br />+BEARING THE UL LISTING MARK
<br />A
<br />REPRODUCED BY HILTI, INC. COURTESY
<br />OF UNDERWRITERS LABORATORIES,
<br />INC.
<br />AUGUST 31, 2005
<br />F Ratings — 1 and 2 Hr (See Items 1 and 4)
<br />T Rating — 0 Hr
<br />A
<br />3 2
<br />4B
<br />4A
<br />1 4B
<br />3
<br />2
<br />4B
<br />C
<br />CLASSI F IED
<br />Classified by
<br />Underwriters Laboratories,
<br />Inc.
<br />to UL 1479 and
<br />CAN/ULC-S115
<br />US
<br />PIPE PENETRATION NOTES :
<br />1. PIPE PENETRATION DETAILS SHOWN ARE TYPICAL DETAILS. IF FIELD CONDITIONS DO NOT MATCH REQUIREMENTS OF TYPICAL DETAILS, APPROVED ALTERNATE DETAILS SHALL BE
<br />UTILIZED. FIELD CONDITIONS AND DIMENSIONS NEED TO BE VERIFIED FOR COMPLIANCE WITH THE DETAILS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING:
<br />* MINIMUM AND MAXIMUM WIDTH OF JOINTS
<br />* TYPE AND THICKNESS OF FIRE-RATED CONSTRUCTION. THE MINIMUM ASSEMBLY RATING OF THE FIRESTOP ASSEMBLY SHALL MEET OR EXCEED THE HIGHEST RATING OF THE
<br />ADJACENTCONSTRUCTION.
<br />2. IF ALTERNATE PIPE PENETRATION DETAILS MATCHING THE FIELD CONDITIONS ARE NOT AVAILABLE, MANUFACTURER'S ENGINEERING JUDGMENT DRAWINGS ARE ACCEPTABLE.
<br />DRAWINGSSHALL FOLLOW THE INTERNATIONAL FIRESTOP COUNCIL (IFC) GUIDELINES FOR EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS.
<br />3. REFERENCES:
<br />* 2012 UNDERWRITER'S LABORATORIES FIRE RESISTANCE DIRECTORY, VOLUME 2
<br />* NFPA 101 LIFE SAFETY CODE
<br />* ALL GOVERNING LOCAL AND REGIONAL BUILDING CODES
<br />4. FIRESTOP SYSTEM INSTALLATION MUST MEET REQUIREMENTS OF ASTM E-814 (UL 1479) TESTED ASSEMBLIES THAT PROVIDE A FIRE RATING EQUAL TO THAT OF CONSTRUCTION BEING
<br />PENETRATED.
<br />5. ALL RATED THROUGH-PENETRATIONS SHALL BE PROMINENTLY LABELED WITH THE FOLLOWING INFORMATION:
<br />* ATTENTION: FIRE RATED ASSEMBLY
<br />* UL SYSTEM #
<br />* PRODUCT(S) USED
<br />* HOURLY RATING (F-RATING)
<br />* INSTALLATION DATE
<br />SEISMIC BRACES MAY BE INSTALLED AT EITHER HANGER. BRACES AT BOTH HANGERS ARE NOT REQUIRED.
<br />WHERE MULTIPLE SHIELD AND CLAMP JOINTS OCCUR IN CLOSELY SPACED ASSEMBLY (I.E. FITTING-FITTING-FITTING,
<br />ETC.) A 16 GAUGE HALF SLEEVE MAY BE INSTALLED UNDER THE ASSEMBLY WITH A PIPE HANGER AT EACH
<br />END OF THE SLEEVE.
<br />FOR ALL PIPING SYSTEM SEISMIC BRACING AND SEISMIC RESTRAINTS SHALL BE PER SMACNA LATEST EDITION.
<br />NOTES:
<br />1.
<br />2.
<br />3.
<br />GREATER
<br />BRACE ON OFFSETS IN EXCESS OF 10 FEET. SUBMIT DETAILS IF VARIATION
<br />LOCATE BRACE EVERY 30 FT. ON STRAIGHT RUNS WITH AT LEAST ONE
<br />SWAY BRACING SHALL BE PROVIDED TO PREVENT HORIZONTAL MOVEMENT.
<br />WHEN HUBLESS PIPING IS SUSPENDED IN EXCESS OF 6" BELOW STRUCTURE,
<br />THAN 6"
<br />16" GAUGE CONTINUOUS
<br />GALVANIZED SHEET METAL
<br />MAXIMUM HANGER SPACING 10'-0"
<br />SLEEVE
<br />TYP. RIGID TRANSVERSE
<br />BRACE (IF REQUIRED)
<br />IS REQUIRED.
<br />45°
<br />BRACE (ALTERNATE
<br />LOCATION IF REQUIRED)
<br />TYP. RIGID TRANSVERSE
<br />SWAY BRACE
<br />45°
<br />CLEVIS OR "J" HANGER
<br />TYP. RIGID LONGITUDINAL
<br />BRACE
<br />HUBLESS CAST IRON
<br />SOIL PIPE FITTING
<br />CW SUPPLY TO BUILDING
<br />FULL-SIZED BY-PASS LINE
<br />WITH SOV(N.C.)
<br />DCW SUPPLY FROM BUILDING
<br />PROVIDE CONNECTION TO BMS
<br />SUB-WATER METER IN ACCESSIBLE AREAUNION (TYP)
<br />© Gensler
<br />Date Description
<br />Project Name
<br />Project Number
<br />Description
<br />Scale
<br />Seal / Signature
<br />2015
<br />NOT FOR
<br />CONSTRUCTION
<br />Tel 949.863.9434
<br />Fax 949-553-1676
<br />4675 MacArthur Court
<br />Suite 100
<br />Newport Beach, CA
<br />92600
<br />USA
<br />Job No.:
<br />Contact:
<br />www.glumac.com
<br />18200 Von Karman Ave., Suite 100
<br />Irvine, CA 92612
<br />T. 949.833.8190
<br />6/12/2024 7:40:14 PM
<br />BIM 360://007.3757.000 - Caribou Industries - 3rd & Broadway/3RD-B_MEP_WEST_R20.rvt
<br />R1-P9.3
<br />PLUMBING DETAILS
<br />21US00608
<br />3rd & Broadway West
<br />1103 North Broadway
<br />Santa Ana, CA 92701
<br />21US00608
<br />TG
<br />1 9/21/2021 REISSUE FOR PLAN CHECK
<br />2 01/18/2022 REISSUE FOR PLAN CHECK
<br />4 06/17/2024 REVISION TO PERMIT
<br />EOR: SEAN AGUON
<br />LIC#: M41274
<br />10/11/2024
|