GENERAL: <br />1. ALL FRAMING MEMBERS SHALL BE SO ARRANGED AND SPACED AS TO PERMIT <br />INSTALLATION OF PIPES, CONDUITS, CONTROLS AND DUCTWORK WITH A MINIMUM OF <br />CUTTING. SHAFT WALLS SHALL BE PROVIDED WITH NECESSARY FRAMES, BRACING AND <br />SEALANT AROUND THE OPENING. <br />2. OFFSET STUDS WHERE REQUIRED SO THAT FINISH WALL SURFACE WILL BE FLUSH. IF <br />STRUCTURAL PANELS ARE REQUIRED ON A WALL PLANE, THE ENTIRE WALL PLANE SHALL <br />BE FURRED OR FINISHED FLUSH. <br />3. CONTRACTOR SHALL PROVIDE AND INSTALL ALL STIFFENERS, BRACING, BACK-UP <br />PLATES, AND SUPPORTING BRACKETS REQUIRED FOR THE INSTALLATION OF ALL <br />CASEWORK, STAIR RAILINGS, TOILET ACCESSORIES, PARTITION, AND ALL WALL-MOUNTED <br />OR SUSPENDED MECHANICAL, ELECTRICAL OR MISCELLANEOUS EQUIPMENT. <br />4. AT A MINIMUM FIREBLOCKING SHALL BE PROVIDED THROUGHOUT AS REQUIRED PER <br />CURRENT BUILDING CODES. SEE NOTES THIS SHEET. <br />5. AT A MINIMUM FIRE DAMPERS SHALL BE PROVIDED WHERE AIR DUCTS PENETRATE FIRE <br />RATED ASSEMBLIES IN COMPLIANCE WITH CURRENT BUILDING CODES. SEE NOTES THIS <br />SHEET. <br />6. PLASTIC PIPE PENETRATION IN ACOUSTICAL PARTY FLOOR-CEILING OR WALL <br />ASSEMBLIES ARE PROHIBITED (UNLESS ALLOWED BY LISTED ASSEMBLY). PLASTIC PIPES <br />AND PLASTIC BOXES (EXCEPT UL FIRE RATED BOXES) SHALL NOT PENETRATE FIRE RATED <br />WALLS, FLOORS, CEILINGS. NEC 300-21. SEE SHEET A-61.1 FOR FIRE STOPPING <br />REQUIREMENTS. <br />7. FURNISH AND INSTALL ALL ACCESS DOORS, FIRE DAMPERS, ETC. IN CEILING AND WALL <br />CONSTRUCTION LOCATED AS REQUIRED BY INSTALLATION OF MECHANICAL, PLUMBING AND <br />ELECTRICAL WORK AND AS APPROVED BY THE ARCHITECT. PROVIDE REQUIRED FIRE <br />RATED ASSEMBLIES IN FIRE RATED WALLS AND CEILINGS. <br />8. CONTACT BETWEEN DISSIMILAR METALS SHALL BE PROTECTED AT ALL LOCATIONS W/ <br />UNDERLAYMENT - BITUMINOUS PAINT, NEOPRENE WASHERS OR ANOTHER NON- <br />CONDUCTING MATERIAL. <br />9. PROVIDE INSULATION PER SCHEDULE AND CONFORMING TO ASTM C 665-98 TYPE III - <br />BLANKETS W/ A REFLECTIVE VAPOR-RETARDED ON PRINCIPAL SIDE. FIRE RESISTANCE <br />RATED WHERE EXPOSED IN THE EXTERIOR WALL OR AT THE CEILING PLENUM. <br />10. ROOFING SYSTEM SHALL BEAR UL LISTING AS A CLASS "A" SYSTEM. ALL <br />MANUFACTURED MATERIALS USED SHALL BEAR THE APPROPRIATE UL LABEL. <br />11. CONTRACTOR SHALL PROVIDE ALL CONCRETE HOUSEKEEPING PADS FOR MECHANICAL <br />AND ELECTRICAL EQUIPMENT, AS REQUIRED. <br />12. ALL CONSTRUCTION SHALL COMPLY WITH ACOUSTICAL REQUIREMENTS NOTED ON <br />GEN-3 AND ELSEWHERE IN THE DRAWINGS AND SPECIFICATIONS. UNIT TO UNIT WALLS AND <br />FLOOR/CEILING ASSEMBLIES SHALL MEET A MINIMUM STC AND IIC SOUND RATING OF 50. <br />REFERENCE INDIVIDUAL WALL AND FLOOR CEILING ASSEMBLIES NOTED IN THESE <br />DRAWINGS. <br />13. ALL ROOF PIPE PENETRATIONS TO BE ROUND. <br />REQUIRED LOCATIONS: <br />1. CONCEALED SPACES OF WALLS AND PARTITIONS, INCLUDING FURRED SPACES, AT 10'-0" <br />INTERVALS BOTH HORIZONTAL AND VERTICAL. <br />2. AT INTERSECTIONS BETWEEN VERTICAL AND HORIZONTAL. <br />3. AT CONCEALED SPACES BETWEEEN STAIR STRINGERS AT TOP AND BOTTOM OF STAIR <br />RUN. <br />4. IN OPENING AROUND PIPES, DUCTS AT CEILINGS AND FLOORS. <br />CONSTRUCTION: <br />1. 2" NOMINAL LUMBER, OR (2) LAYERS OF 1" LUMBER WITH BROKEN LAPS, OR (1) LAYER OF <br />3/4" STRUCTURAL PANEL WITH JOINTS BACKED BY 3/4" STRUCTURAL PANEL. <br />2. GYPSUM BOARD, CEMENT FIBER BOARD. <br />3. BLANKETS OF MINERAL FIBER (IF TESTED FOR USE). NO LOOSE FILL INSULATION. <br />1. PARTY WALL AND DIVISION WALL FRAMING REQUIREMENTS: <br />A. STUDS SHALL NOT OVERRIDE PLATES OF PARTY OR DIVISION WALLS. KNOT HOLES, <br />WARPED LUMBER, SPLINTERED WOOD, SPLICES, CHIPS AND SAWCUTS SHALL NOT BE <br />PERMITTED AT VERTICAL OR HORIZONTAL PARTY WALL CONNECTIONS. <br />B. FRAMING AT BUILT-UP CORNERS AND JOISTS TO WALL CONNECTIONS ALONG PARTY <br />WALLS SHALL FIT TIGHTLY WITHOUT AIR GAPS. SPECIAL CARE SHALL BE TAKEN SO THAT <br />DRY WALL NAILER BLOCKING MEETS THIS CONDITION BETWEEN JOISTS. <br />C. CONCRETE POUR MATERIAL SHALL NOT FLOW ONTO PART WALL SOLE PLATES. <br />CONCRETE SHALL NOT BE POURED ONTO OR INTO PARTY WALL SEPARATION CAVITIES <br />BETWEEN PLATES. <br />D. NOT USED. <br />E. GYPSUM WALLBOARD SHALL CONTINUE TO THE ROOF LINE ON ONE SIDE OF THE <br />WALL TO AVOID FLANKING OF SOUND THROUGH THE ATTIC SPACE. GYPSUM <br />WALLBOARD SHALL BE INSTALLED TO MAINTAIN A 1/4" GAP AT ALL PARTY OR DIVISION <br />WALL PERIMETERS AND FILL THE GAP WITH ACOUSTICAL CAULK. <br />F. WHERE TWO LAYERS OF GYPSUM WALLBOARD ARE REQUIRED ON ONE SIDE OF A <br />COMMON WALL, THE JOINTS BETWEEN THE SECOND LAYER OF WALLBOARD MUST BE <br />STAGGERED WITH RESPECT TO THE JOINTS OF THE FIRST LAYER, I.E. THE JOINTS MUST <br />NOT OVERLAP. <br />G. GYPSUM WALLBOARD AT PARTY AND DIVISION WALLS SHALL BE INSTALLED TO <br />MAINTAIN A 1/4” GAP AT PERIMETERS. FILL GAP WITH ACOUSTICAL SEALANT. <br />2. FLOOR/CEILING REQUIREMENTS: <br />A. PROVIDE 1-1/2 INCH THICK 2000 PSI GYSPUM CONCRETE FLOOR UNDERLAYMENT <br />OVER ENKASONIC UNDERLAYMENT OVER STRUCTURAL SHEATHING @ ALL APARTMENTS <br />ABOVE GROUND FLOOR. <br />B. REFER TO INSULATION SCHEDULE ON THIS SHEET FOR ACOUSTIC INSULATION <br />REQUIREMETNS. ALL FLOOR/CEILING INSULATION SHALL BE SNUGLY FITTED AND/OR <br />STAPLED BETWEEN JOISTS. <br />C. GYPSUM WALLBOARD AT FLOOR CEILING ASSEMBLIES SHALL BE INSTALLED TO <br />MAINTAIN A 1/4” GAP AT PERIMETERS. FILL GAP WITH ACOUSTICAL SEALANT. <br />D. SEALANT FOR ALL FLOOR/CEILING ASEMBLIES SHALL BE INSTALLED IN STRICT <br />CONFORMANCE WITH MANUFACTURER’S SPECIFICATIONS. <br />E. RESILIENT CHANNELS SHALL BE INSTALLED PER CONFORMANCE WITH THE <br />MANUFACTURER, ASTM STANDARDS AND THE GYPSUM CONSTRUCTION HANDBOOK. <br />F. WALLS SHALL BE INSTALLED BEFORE THE RESILIENT CHANNELS TO ENSURE THAT <br />THE CHANNELS REMAIN TO THE OUTSIDE OF THE WALL TO ALLOW THE CEILING TO <br />FLOAT OR MOVE VERTICALLY WITHOUT HINDRANCE. <br />3. SEALANT: <br />A. THE INTENT OF THESE RECOMMENDATIONS IS TO ENSURE THAT AN AIR TIGHT <br />COMMON PARTITION CONSTRUCTION IS MAINTAINED. A 1 SQ. IN. HOLE, CRACK OR GAP <br />IN A 100 SQ. FT. WALL WILL REDUCE THE STC RATING BY 10 POINTS AS COMPARED OT <br />HTE SAME WALL WITH AN AIR TIGHT CONSTRUCTION. THUS, THE IMPORTANCE OF <br />PERFORMING CAULKING AND SEALING COMPLETELY AND PRECISELY CANNOT BE <br />OVEREMPHASIZED. <br />B. ACOUSTICAL SEALANT SHALL BE NON-SKINNING, NON-HARDENING, FLEXIBLE SEALANT <br />SPECIFICALLY DESIGNED FOR SEALING GYPSUM WALLBOARD (ASTMC C919). SEALANT <br />SHALL BE CAPABLE OF SPANNING 1/2” WIDE BY 3/8” DEEP GAPS. ACCEPTABLE <br />PRODUCTS INCLUDE: TREMO OR USG SEALANT (OR APPROVED EQUAL). SEALANT SHALL <br />BE INSTALLED IN STRICT CONFORMANCE WITH MANUFACTURER’S SPECIFICATIONS. <br />C. IF MULTIPLE LAYERS OF WALLBOARD ARE APPLIED TO A WALL SURFACE THE <br />SEALANT MUST BE INSTALLEED FOR LAST LAYER (EA. SIDE OF WALL). <br />D. AT ALL PENETRATIONS IN COMMON WALLS OR COMMON CEILINGS FOR SUCH ITEMS <br />AS ELECTRICAL BOXES, LIGHT FIXTURES, PLUMBING LINES, ETC., LEAVE A 3/16” TO 1/4” <br />GAP IN THE WALLBOARD AROUND THE FIXTURE AND THEN FILL THE GAP WITH <br />ACOUSTICAL SEALANT. IN ADDITION, THE BACKS OF ALL ELECTRICAL BOXES, <br />TELEPHONE BOXES, MEDICINE CABINETS, AND OTHER THIN WALLED ITEMS INSET INTO A <br />COMMON WALL MUST BE COVERED WITH AN AIRTIGHT GYPSUM WALLBOARD HOUSING <br />OR WITH HEAVY MASTIC MATERIAL SUCH AS LOWRY PADS. <br />4. RESILIENT CHANNEL ASSEMBLIES: <br />A. RESILIENT CHANNELS SHALL BE DIETRICH RC DELUXE FOR WALLS, SUBSTITUTOINS <br />ARE NOT ALLOWED. <br />NOTE: THERE SHALL BE NO CONTACT BETWEN THE SHORT (NON-FASTEN) LEG OF THE <br />CHANNEL AND THE JOIST OR STUDS. <br />B. ATTACHING CHANNELS: ORIENT CHANNELS PERPENDICULAR TO FRAMING AND WITH <br />FLANGES FACING IN ONLY ONE DIRECTION. ATTACH CHANNELS AT SPACINGS AND WITH <br />FASTENERS DENOTED IN THE FIRE TEST ASSEMBLY. USE THE PRE-DRILLED MOUNTING <br />HOLES IN THE CHANNELS FOR ATTACHMENT TO THE STUDS OR JOISTS. LOCATE <br />CHANNELS A MAXIMUM OF 3” AND HOLD BACK ENDS 1/2” FROM INTERSECTING <br />SURFACES. PROVIDE SUFFICIENT FRAMING SO CHANNELS ARE NOT CANTILEVERED <br />GREATER THAN 6”. CHANNELS MUST NOT CROSS EACH OTHER UNDER ANY <br />CIRCUMSTANCE. CHANNELS MAY ONLY BE OVERLAPPED AT SPLICES. SPLIE CHANNELS <br />ONLY AT FRAMING WITH A MAXIMUM OVERLAP OF 1.5” AND SCREW ATTACH THROUGH <br />BOTH FLANGES. <br />C. ATTACHING GYPSUM WALLBOARD: APPLY GYPSUM WALLBOARD AT A MAXIMUM <br />PRACTICAL LENGTH WITH THE LONG EDGE PARALLEL WITH AND CENTERED ON <br />CHANNELS. FASTEN GYPSUM WALLBOARD AT SPACINGS AND WITH FASTENERS <br />DENOTED IN THE FIRE TEST ASSEMBLY. NAILING RESLIENT CHANNELS ISS NOT <br />PERMITTED. FASTENERS SHALL ONLY BE ATTACHED TO THE CHANNELS AND NOT THE <br />FRAMING. INSTALL GYPSUM WALLBOARD TO ALLOW FOR 1/4”GAP FROM INTERSECTING <br />SURFACES. WHEN CONSTRUCTION OF MULTIPLE LAYERS OF GYPSUM WALLBOARD IS <br />INDICATED, APPLY THE FACE LAYER WITH THE LONG EDGE JOINTS OFFSET BY 24” AND <br />THE SHORT EDGE JOINTS OFFSET BY 48” FROM THE BASE LAYER. ADDITIONALLY, <br />OFFSET THE FACE LAYER SCREW PATTERN 6” FROM THE BASE LAYER SCREWS ALONG <br />THE CHANNELS. <br />D. SEALANT: SEAL ALL PERIMETER JOINTS OF RESILIENT ASSEMBLIES AIRTIGHT WITH <br />APPROVED ACOUSTICAL SEALANT. <br />E. BASEBOARD AND TRIM: DO NOT RIGIDLY ATTACH BASEBOARD OR OTHER FINISH TRIM <br />TO UNDERLYING FRAMING THROUGH RESILIENT ASSEMBLIES. SCREW ATTACH <br />BASEBOARD OR OTHER FINISH TRIM TO RESILIENT CHANNELS. ADHERING FINISH TRIM IS <br />AN ACCEPTABLE ALTERNATIVE. <br />5. PLUMBING: <br />A. IN ORDER TO MINIMIZE OR ELIMINATE FLOW NOISE AT ALL WATER, WASTE, DRAIN AND <br />REFRIGERANT PIPING, CONTRACTOR IS TO PROVIDE VIBRATION ISOLATION: <br />I) SUPPLY PIPING 1” DIAMETER OR SMALLER SHALL BE INSTALLED WITH ISOLATOR <br />HOLDERS, AND GUIDES. <br />II) SUPPLY AND WASTE PIPING MORE THAN 1” IN DIAMETER SHALL BE INSTALLED WITH PILE <br />ISOLATORS <br />II) PLASTER R THIN-WALLED COPER WASTE AND DRAIN PIPING SHALL BE COMPLETELY <br />WRAPPED USING LOWRY ACOUSTICAL PIPIE WRPA AS MANUFACTURED BY HARRY A. <br />LOWRY COMPANY (OR APPROVED EQUAL) <br />IV) REFRIGERANT LINES SHALL BE ISOLATED BY INSULATING THE ENTIRE LENGTH OF THE <br />LINE WITH A MINIMUM OF 1/2” “ARMAFLEX” (OR APPROVED EQUAL). PLACE CLAMPS OVER <br />THE INSULATION WHEN ATTTACHING TO THE STRUCTURE SO THAT THERE IS NO DIRECT <br />CONTACT BETWEEN THE PIPING AND THE STRUCTURE. MAINTAIN A 2” CLEANCE BETWEEN <br />THE REFRIGERANT LINES AND THE GYPSUM WALLBOARD. <br />B. AT A MINIMUM PROVIDE PIPING SUPPORT PER PLUMBING CODE (SEE PLUMBING <br />DRAWINGS). THE PLUMBING PIPING, PIPE CONNECTIONS, PIPE HANGERS, OR VALVES, <br />SHALL NOT MAKE CONTACT WITH ANY PART OF THE SURROUNDING STRUCTURE. JOISTS, <br />STUDS, WALLBOARD OR OTHER PIPES, PIPING AND/OR DUCTING WITHIN FLOOR/CEILING <br />ASSEMBLIES SHALL BE SUPPORTED FROM THE JOISTS AND COMPLETELY ISOLATED FROM <br />THE CEILING. <br />C. IN OTHERWISE UN-INSULATED STUD BAY OR JOIST CAVITY CONTAINING PIPING INSTALL A <br />MINIMUM OF 3-1/2” ACOUSTIC BATT INSULATION OR OTHER SOUND ABSORPTIVE MATERIAL. <br />D. WATER PRESSURE CONTROL: GENERAL CONTRACTOR TO CONFIRM THT WATER SUPPLY <br />PIPING INSTALLED WILL MAINTAIN A MAXIMUM WATER FLOW RATE OF 4 FEET PER SECOND <br />IN 1/2” AND 3/4” DIAMETER BRANCH LINES. FOR LARER LINES THE MAXIMUM FLOW RATE <br />SHALL BE 6 FEET PER SECOND. MAINTAIN A MAXIMUM OF 50 PSI WATER PRESSURE AT <br />PLUMBING FIXTURES, CONSISTEN WITH ADEQUATE FLOW RATES. <br />E. ACOUSTICAL (FIRE STOPPING) SEALANT SHALL BE INSTALLED AT ALL PIPE <br />PENETRATIONS AS DESCRIBED ABOVE. <br />6. MECHANICAL: <br />A. PROVIDE NEOPRENE PADS WHERE ROOFTOP EQUIPMENT IS OVER RESIDENTIAL <br />DWELLING UNITS. WHERE ROOFTOP EQUIPMENT IS PLACED OVER RESIDENTIAL DWELLING <br />LIVING AND SLEEPING AREAS, AND WHENEVER OVER COMMON AREAS, MASON INDUSTRIES, <br />INC. TYPE SLR SPRING MOUNTS TO BE PROVIDED. USE SLACK CABLE RESTRAINT OR <br />SEPARATE SEISMIC SNUBBERS TO LIMIT HORIZONTAL MOVEMENT. MECHANICAL <br />CONTRACTOR SHALL CONSULT AN INDEPENDENT STRUCURAL ENGINEER FOR <br />APPROPRIATE SEISMIC RESTRAINT SYSTEM DESIGN. ROOFTOP EQUIPMENT SHALL BE <br />INSTALLED ON CONCRETE HOUSEKEEPING PADS. <br />B. INSTALL SUSPENDED MEHCANICAL UNITS SUCH AS FAN/COIL OR IN-LINE FANS ON A <br />MINIMUM OF 1” STATIC DEFLECTION SPRING HANGERS SUCH AS MASON TYPE 3ON (OR <br />APPROVED EQUAL). DO NOT ALLOW DIRECT CONTACT BETWEEN THE MECHANICAL UNIT <br />AND THE STRUCTURE OR OTHER ADJACENT UTILITIES. MAINTAIN A MINIMUM OF 2” <br />CLEARANCE BETWEEN THE REFRIGERANT LINES AND GYPSUM WALLBOARD SURFACES. <br />C. AT A MINIMUM, PROVIDE BATHROOM EXHAUST FANS WITH A NOISE RATING LOWER THAN <br />2.0 SONES. NOTE THAT FAN SOUND RATINGS TYPICALLY ASSUME 10 FEET OF STRAIGHT <br />DUCT ATTACHED OT THE FAN. WHERE CONDITIONS VARY FROM THIS ASSUMPTION, <br />PROVIDE FANS WITH LOWER SOUND RATINGS. MANY RESTROOM FANS ARE AVAILABLE <br />WITH SOUND RATINGS BELOW 1.0 SONE. RESTROOM FAN HOUSING WHICH ARE MOUNTED <br />WITHIN A SEPARATION ASSEMBLY SHALL BE BOXED IN WITH 5/8” GYPSUM BOARD, SEALED <br />AIR TIGHT AND SURROUNDED WITHFIBERGLAS OR EQUIVALENT SOUND ABSORPTIVE <br />MATERIAL. <br />D. PROVIDE A MINIMUM OF 3 FEET OF ACOUSTICALLY LINED DUCT BETWEEN THE FAN/COIL <br />UNIT AND ANY DIFFUSER. DIFFUSERS AND GRILLS SHALL PERFORM A BACKGROUND NOISE <br />CRITERION OF 3 POINTS BELOW NC 30 (I.E. NC25). <br />7. ELECTRICAL: <br />A. CONVENIENCE OUTLETS IN OPPOSITE FACES OF PARTY OR DIVISION WALLS SHALL BE <br />INSULATED AS FOLLOWS: <br />I) ELECTRICAL BOXES (SWITCHES, OUTLETS, WALL FIXTURES, ETC. IN OPPOSITE FACES OF <br />PARTY OR DIVISION WALLS SHALL BE SEPARATED HORIZONTALLY BY NOT LESS THAN 24 <br />INCHES (I.E. IN DIFFERENT STUD BAYS). IN THE EVENT IT IS NOT PRACTICAL OR POSSIBLE TO <br />PLACE OUTLETS IN DIFFERENT STUD BAYS, THEY SHALL BE SEPARATED FROM EACH OTHER <br />AS MUCH AS POSSIBLE AND IN NO CASE SHALL THERE BE PHYSICAL CONTACT BETWEEN <br />THE TWO ELECTRICAL BOXES. HOWEVER, THE FOLLOWING ITEMS ARE APPLICABLE IN ALL <br />CASES: <br />II) MASTIC SEALER (LOWRY PADS OR APPROVED EQUAL) SHALL BE WRAPPED AROUND <br />BACK SIDES, TOP AND BOTTOM OF ALL ELECTRICAL BOXES IN PARTY WALLS. <br />III) ELECTRICAL BOXES SHALL BE BACKED BY R-11 FIBERGLASS AS NEEDED TO <br />COMPLETELY FILL THE STUD BAY. <br />IV) KNOCKOUT PLATES ON ELECTRICAL BOXES IN PARTY OR DIVISION WALLS SHALL NOT BE <br />BENT OR REMOVED WHERE CONDUITS ARE NOT CONNECTED TO THE BOX. <br />B. RECESSED LIGHT FIXURES IN CEILINGS SHALL HAVE NO VENTILATION HOLES. JUNCTION <br />BOXES IN CEILINGS SHALL BE WRAPPED AROUDN BACK AND SIDES WITH LOWRY PADS (OR <br />APPROVED EQUAL) AND SEALED AIRTIGHT WITH ACOUSTICAL SEALANT. <br />8. FLOOR COVERINGS: <br />A. IF A RESILIENT VINYL FLOOR COVERING IS USED, A DURABLE BRAND OF VINYL MEETING <br />RESILIENT FLOOR COVERING COMMITTEE F6 AT THE AMERICAN SOCIETY FOR TESTING AND <br />MATERIALS (ASTM) REQUIREMENTS SHALL BE PROVIDED. <br />B. REFER TO FINISH SCHEULE FOR SPECIFICATION OF ACOUSTIC UNDERLYAMENTS AT TILE <br />FLOOR ASSEMBLIES. <br />INSULATION NOTES: <br />1. INSULATION INSTALLED IN A FLOOR/CEILING OR ROOF CEILING ASSEMBLY SHALL BE SUPPORTED BY WIRE STAYS (OR EQUAL) SO THAT <br />THE INSULATION DOES NOT MAKE CONTACT WITH THE FACE MEMBRANE OF THE ASSEMBLY (GYPSUM WALLBOARD). <br />2. MATERIAL NOTED AS S.A.B. REFERS TO FLEXIBLE FIBERGLASS SOUND ATTENTUATION BATT (S.A.B.) <br />3. INSULATION SCHEDULED FOR COMMON WALL UNIT TO UNIT SHALL BE INSTALLED IN EACH SIDE OF THE WALL ASSEMBLY. <br />4. ALL INTERIOR WALL CAVITY SPACES TO RECEIVE INSULATION. <br />5. REFER TO MECHANICAL PLANS FOR DETAILED INFORMATION REGARDING ENERGY CODE REQUIREMENTS. <br />ASSEMBLY THERMAL INSULATION <br />THICKNESS MATERIAL R-VALUE <br />ROOF/CEILING <br />FLOOR/CEILING <br />DROP CEILING <br />EXTERIOR WALL <br />PARTY WALL <br />10” <br />5-1/2” <br />BATT <br />BATT <br />R-30 <br />R-19 <br />ACOUSTICAL INSULATION <br />THICKNESS MATERIAL R-VALUE <br />3-1/2" <br />3-1/2” <br />3-1/2” <br />S.A.B. <br />S.A.B. <br />S.A.B. <br />CORRIDOR WALL <br />INTERIOR PLUMBING WALL 3-1/2” S.A.B. <br />3-1/2” S.A.B. <br />INTERIOR SHAFT WALL 2-1/2” S.A.B. <br />2” MIN RIGID R-10 MIN <br />1” @ OTHER BLDGS RIGID R-5 <br />@ METAL SIDING WALL CONTINUOUS INSULATION <br />PROVIDED BY INSULATED WALL PANELS <br />WINDOW NOTES: <br />1. EXTERIOR WINDOWS SHALL HAVE THE FOLLOWING MINIMUM ENERGY PERFORMANCE CHARACTERISTICS: <br />U-VALUE: 0.30 <br />SHGC: 0.20 MAX. <br />2” @ BLDG A TYPES RIGID R-5 <br />PLUS <br />THIS DOCUMENT CONTAINS INFORMATION PROPRIETARY TO SVA ARCHITECTS <br />INC. AND IS FURNISHED IN CONFIDENCE FOR THE LIMITED PURPOSE OF <br />EVALUATION, BIDDING OR REVIEW. THIS DOCUMENT OR ITS CONTENTS MAY <br />NOT BE USED FOR ANY OTHER PURPOSE AND MAY NOT BE REPRODUCED OR <br />DISCLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN CONSENT OF SVA <br />ARCHITECTS INC. ALL RIGHTS RESERVED, © COPYRIGHT 2018. <br />SCALE: <br />REVISIONS: <br />OW <br />N <br />E <br />R <br />: <br />PR <br />O <br />J <br />E <br />C <br />T <br /> <br />N <br />A <br />M <br />E <br />: <br />CL <br />I <br />E <br />N <br />T <br /> <br />A <br />D <br />D <br />R <br />E <br />S <br />S <br />: <br />6 HUTTON CENTRE DR, SUITE 1150 SANTA ANA, CA 92707 <br />T 949.809.3380 WWW.SVA-ARCHITECTS.COM <br />DATE ISSUED: <br />PROJECT NO: <br />As indicated <br />07/08/24 <br />GEN-3 <br />CONSTRUCTION <br />ASSEMBLY <br />NOTES AND <br />REQUIREMENTS <br />2022-40123 <br />CI <br />T <br />Y <br /> <br />O <br />F <br /> <br />S <br />A <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br />NE <br />W <br />H <br />O <br />P <br />E <br /> <br />L <br />I <br />B <br />R <br />A <br />R <br />Y <br />MO <br />D <br />E <br />R <br />N <br />I <br />Z <br />A <br />T <br />I <br />O <br />N <br />12 <br />2 <br /> <br />N <br />. <br /> <br />N <br />E <br />W <br />H <br />O <br />P <br />E <br /> <br />S <br />T <br />. <br />, <br /> <br />S <br />A <br />N <br />T <br />A <br /> <br />A <br />N <br />A <br /> <br />C <br />A <br /> <br />9 <br />2 <br />7 <br />0 <br />3 <br />CONSTRUCTION ASSEMBLIES -GENERAL <br />FIRE BLOCKING NOTES <br />ACOUSTICAL CONTROL REQUIREMENTS <br />ASSEMBLY SCHEDULE <br />DESCRIPTION DATE <br />1 ASI #01 04/09/25