Laserfiche WebLink
CITY OF SANTA ANA <br />SPECIFICATIONS <br />PROJECT NO.: XX-XXXX <br />PROJECT TITLE <br /> <br />175 <br />Ductile iron pipe section shall be (18') and or (20') sections, except where shorter lengths <br />are required to fit horizontal or vertical alignment. Pipe sections shall not be deflected at <br />any joint, either vertically or horizontally, beyond the limits specified by the <br />manufacturer. <br />All pipe segments shall be sound and clean before laying. Ductile iron pipe cutting shall <br />be done with a machine at right angles to the axis of the pipe. Cut end to be joined with a <br />bell shall be beveled to conform to the spigot end. <br />All fittings shall be mechanical joint (M.J.), or flanged (FLG) except where noted <br />otherwise. All valves to fitting connections shall be flanged. Valves for lateral lines, <br />hydrant leads and service lines shall be bolted directly to main line tee. Where it is <br />necessary to install a reducer or other type of fitting between the lateral valve and main <br />line, said fitting shall be flanged at both ends. <br />No push-on joint fittings or connections shall be allowed unless specifically <br />approved by the Engineer. <br />All flanged fittings and connections shall comply with the applicable provisions of <br />AWWA C110. The bolt circle and bolt holes of these flanges shall match those of the <br />Class 125 flanges shown in ANSI B16.1. <br />The Contractor shall coordinate the flange requirements with the connecting pipe and <br />valve manufacturers. <br />Contractor shall provide flange to connecting pipe adaptors as needed. Adaptors may be <br />flange by connecting pipe fittings (e.g. FLG x M.J.) or Megaflange-Flange adapter. "E-Z <br />Flange" and similar set screw type adaptors are not acceptable. <br />Concrete thrust blocks shall be provided at all valves, fittings and hydrants in accordance <br />with AWWA Standards and City of Santa Ana Standard Plan Nos. 1412 and 1420. Type <br />V cement shall be used for all concrete thrust blocks. <br />Where called for on the plans, a high -early strength concrete shall be used for thrust <br />blocks at points of connection. Admixtures for high-early strength concrete shall be non- <br />chloride admixtures which meet the requirements of ASTM C494. Acceptable products <br />are Pozzutec 200 and Pozzolith NC 534 by Master Builders, Inc. or approved equal. <br />Concrete shall reach 2,500 psi by four (4) hours. <br />For restrained mechanical joint fittings, the mechanical joint fitting shall be fitted with <br />joint restraints. Mechanical joint restraint shall be incorporated with the design of the <br />follower gland and shall include a restraining mechanism which, when activated, imparts <br />multiple wedging action against the pipe, increasing its resistance as the pressure <br />increases. The joint shall maintain flexibility after burial. Follower glands shall be <br />manufactured of ductile iron conforming to ASTM A536-80. The mechanical joint <br />restraint shall be EBBA IRON, Inc., MEGALUG, UNIFLANGE Series 1400, The Ford <br />Meter Box Co., Inc. or approved equal. Any restrained joint fittings which require a pipe <br />field weldment will not be permitted. <br />505 E Central Ave <br />#B11/6/2024