SECTION 26 2416 <br />PANELBOARDS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES LOAD CENTERS AND PANELBOARDS, OVERCURRENT PROTECTIVE <br />DEVICES, AND ASSOCIATED AUXILIARY EQUIPMENT RATED 600 V AND LESS FOR THE <br />FOLLOWING TYPES: <br />1.LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS. <br />2.DISTRIBUTION PANELBOARDS. <br />3.TRANSIENT VOLTAGE SURGE SUPPRESSOR PANELBOARDS. <br />1.02 DEFINITIONS <br />A.EMI: ELECTROMAGNETIC INTERFERENCE. <br />B.GFCI: GROUND-FAULT CIRCUIT INTERRUPTER. FI: RADIO-FREQUENCY INTERFERENCE. <br />C.RMS: ROOT MEAN SQUARE. <br />D.SPDT: SINGLE POLE, DOUBLE THROW. <br />E.TVSS: TRANSIENT VOLTAGE SURGE SUPPRESSOR. <br />1.03 SUBMITTALS <br />A.PRODUCT DATA: FOR EACH TYPE OF PANELBOARD, OVERCURRENT PROTECTIVE <br />DEVICE, AND COMPONENT INDICATED. INCLUDE DIMENSIONS AND MANUFACTURERS' <br />TECHNICAL DATA ON FEATURES, PERFORMANCE, ELECTRICAL CHARACTERISTICS, <br />RATINGS, AND FINISHES. <br />B.SHOP DRAWINGS: FOR EACH PANELBOARD AND RELATED EQUIPMENT. <br />1.DIMENSIONED PLANS, ELEVATIONS, SECTIONS, AND DETAILS. SHOW TABULATIONS <br />OF INSTALLED DEVICES, EQUIPMENT FEATURES, AND RATINGS. INCLUDE THE <br />FOLLOWING: <br />a.ENCLOSURE TYPES AND DETAILS FOR TYPES OTHER THAN NEMA 250, TYPE 1. <br />b.BUS CONFIGURATION, CURRENT, AND VOLTAGE RATINGS. <br />c.SHORT-CIRCUIT CURRENT RATING OF PANELBOARDS AND OVERCURRENT <br />PROTECTIVE DEVICES. <br />d.FEATURES, CHARACTERISTICS, RATINGS, AND FACTORY SETTINGS OF INDIVIDUAL <br />OVERCURRENT PROTECTIVE DEVICES AND AUXILIARY COMPONENTS. <br />2.WIRING DIAGRAMS: DIAGRAM POWER, SIGNAL, AND CONTROL WIRING AND <br />DIFFERENTIATE BETWEEN MANUFACTURER-INSTALLED AND FIELD-INSTALLED <br />WIRING. <br />C.MANUFACTURER SEISMIC QUALIFICATION CERTIFICATION: SUBMIT CERTIFICATION THAT <br />PANELBOARDS, OVERCURRENT PROTECTIVE DEVICES, ACCESSORIES, AND <br />COMPONENTS WILL WITHSTAND SEISMIC FORCES DEFINED IN DIVISION 26 SECTION <br />"VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL WORK." INCLUDE THE <br />FOLLOWING: <br />1.BASIS OF CERTIFICATION: INDICATE WHETHER WITHSTAND CERTIFICATION IS BASED <br />ON ACTUAL TEST OF ASSEMBLED COMPONENTS OR ON CALCULATION. <br />2.THE TERM "WITHSTAND" MEANS "THE UNIT WILL REMAIN IN PLACE WITHOUT <br />SEPARATION OF INTERNAL AND EXTERNAL PARTS DURING A SEISMIC EVENT AND THE <br />UNIT WILL BE FULLY OPERATIONAL AFTER THE EVENT." <br />3.DIMENSIONED OUTLINE DRAWINGS OF EQUIPMENT UNIT: IDENTIFY CENTER OF <br />GRAVITY AND LOCATE AND DESCRIBE MOUNTING AND ANCHORAGE PROVISIONS. <br />4.DETAILED DESCRIPTION OF EQUIPMENT ANCHORAGE DEVICES ON WHICH THE <br />CERTIFICATION IS BASED AND THEIR INSTALLATION REQUIREMENTS. <br />D.FIELD TEST REPORTS: SUBMIT WRITTEN TEST REPORTS AND INCLUDE THE FOLLOWING: <br />1.TEST PROCEDURES USED. <br />2.TEST RESULTS THAT COMPLY WITH REQUIREMENTS. <br />3.RESULTS OF FAILED TESTS AND CORRECTIVE ACTION TAKEN TO ACHIEVE TEST <br />RESULTS THAT COMPLY WITH REQUIREMENTS. <br />E.PANELBOARD SCHEDULES: FOR INSTALLATION IN PANELBOARDS. SUBMIT FINAL <br />VERSIONS AFTER LOAD BALANCING. <br />F.MAINTENANCE DATA: FOR PANELBOARDS AND COMPONENTS TO INCLUDE IN <br />MAINTENANCE MANUALS SPECIFIED IN DIVISION 01. IN ADDITION TO REQUIREMENTS <br />SPECIFIED IN DIVISION 01 INCLUDE THE FOLLOWING: <br />1.MANUFACTURER'S WRITTEN INSTRUCTIONS FOR TESTING AND ADJUSTING <br />OVERCURRENT PROTECTIVE DEVICES. <br />2.TIME-CURRENT CURVES, INCLUDING SELECTABLE RANGES FOR EACH TYPE OF <br />OVERCURRENT PROTECTIVE DEVICE. <br />1.04 QUALITY ASSURANCE <br />A.TESTING AGENCY QUALIFICATIONS: TESTING AGENCY THAT IS A MEMBER COMPANY OF <br />THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION AND THAT IS ACCEPTABLE TO <br />AUTHORITIES HAVING JURISDICTION. <br />1.TESTING AGENCY'S FIELD SUPERVISOR: PERSON CURRENTLY CERTIFIED BY THE <br />INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR NATIONAL INSTITUTE FOR <br />CERTIFICATION IN ENGINEERING TECHNOLOGIES TO SUPERVISE ON-SITE TESTING <br />SPECIFIED IN PART 3. <br />B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS <br />DEFINED IN CEC, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO THE OWNER, AND <br />MARKED FOR INTENDED USE. <br />C.COMPLY WITH NEMA PB 1. <br />D.COMPLY WITH CEC. <br />E.STRUCTURAL SEISMIC PERFORMANCE: REFER TO DIVISION 26 SECTION “VIBRATION AND <br />SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.” <br />1.05 COORDINATION <br />A.COORDINATE LAYOUT AND INSTALLATION OF PANELBOARDS AND COMPONENTS WITH <br />OTHER CONSTRUCTION THAT PENETRATES WALLS OR IS SUPPORTED BY THEM, <br />INCLUDING ELECTRICAL AND OTHER TYPES OF EQUIPMENT, RACEWAYS, PIPING, AND <br />ENCUMBRANCES TO WORKSPACE CLEARANCE REQUIREMENTS. <br />1.06 EXTRA MATERIALS <br />A.KEYS: TWO SPARES OF EACH TYPE OF PANELBOARD CABINET LOCK, KEYED ALIKE TO <br />MATCH THE OWNER'S STANDARD KEY REQUIREMENTS. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY ONE OF THE FOLLOWING: <br />1.PANELBOARDS, OVERCURRENT PROTECTIVE DEVICES, CONTROLLERS, <br />CONTACTORS, AND ACCESSORIES: <br />a.EATON CORP.; CUTLER-HAMMER PRODUCTS. <br />b.GENERAL ELECTRIC CO.; ELECTRICAL DISTRIBUTION & CONTROL DIV. <br />c.SIEMENS ENERGY & AUTOMATION, INC. <br />d.SQUARE-D CO. <br />e.OR EQUAL. <br />2.TVSS PANELBOARDS: <br />a.CURRENT TECHNOLOGY, INC. <br />b.OR EQUAL. <br />B.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01 <br />SECTION “PRODUCT OPTIONS AND SUBSTITUTIONS”. SPECIFIC PROCEDURES MUST BE <br />FOLLOWED BEFORE USE OF AN UNNAMED PRODUCT OR MANUFACTURER. <br />2.02 FABRICATION AND FEATURES <br />A.ENCLOSURES: FLUSH- AND SURFACE-MOUNTED CABINETS. NEMA PB 1, TYPE 1, TO MEET <br />ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION. <br />1.OUTDOOR LOCATIONS: NEMA 250, TYPE 4 STAINLESS STEEL. <br />2.KITCHEN AREAS: NEMA 250, TYPE 4X, STAINLESS STEEL. <br />3.OTHER WET OR DAMP INDOOR LOCATIONS: NEMA 250, TYPE 4. <br />4.HAZARDOUS AREAS INDICATED ON DRAWINGS: NEMA 250, TYPE 7C. <br />B.HINGED FRONT COVER: ENTIRE FRONT TRIM HINGED TO BOX AND WITH STANDARD <br />DOOR WITHIN HINGED TRIM COVER. <br />C.FINISH: MANUFACTURER'S STANDARD ENAMEL FINISH OVER CORROSION-RESISTANT <br />TREATMENT OR PRIMER COAT. <br />D.DIRECTORY CARD: TYPED PANEL CIRCUIT SCHEDULE/INDEX WITH TRANSPARENT <br />PROTECTIVE COVER, MOUNTED INSIDE METAL FRAME, INSIDE PANELBOARD DOOR. <br />E.BUS: HARD-DRAWN COPPER, 98 PERCENT CONDUCTIVITY. <br />F.MAIN AND NEUTRAL LUGS: COMPRESSION TYPE SUITABLE FOR USE WITH CONDUCTOR <br />MATERIAL. <br />G.EQUIPMENT GROUND BUS: ADEQUATE FOR FEEDER AND BRANCH-CIRCUIT EQUIPMENT <br />GROUND CONDUCTORS; BONDED TO BOX. WHEN ISOLATED GROUNDS ARE REQUIRED, <br />PROVIDE GROUND BUS INSULATED FROM BOX. <br />H.FUTURE DEVICES: MOUNTING BRACKETS, BUS CONNECTIONS, AND NECESSARY <br />APPURTENANCES REQUIRED FOR FUTURE INSTALLATION OF DEVICES. <br />I.ISOLATED EQUIPMENT GROUND BUS: ADEQUATE FOR BRANCH-CIRCUIT EQUIPMENT <br />GROUND CONDUCTORS; INSULATED FROM BOX. <br />J.EXTRA-CAPACITY NEUTRAL BUS: NEUTRAL BUS RATED 200 PERCENT OF PHASE BUS AND <br />UL LISTED AS SUITABLE FOR NONLINEAR LOADS. <br />K.SPLIT BUS: VERTICAL BUSES DIVIDED INTO INDIVIDUAL VERTICAL SECTIONS. <br />L.GUTTER BARRIER: ARRANGE TO ISOLATE INDIVIDUAL PANEL SECTIONS. <br />M.COLUMN-TYPE PANELBOARDS: NARROW GUTTER EXTENSION, WITH COVER, TO <br />OVERHEAD JUNCTION BOX EQUIPPED WITH GROUND AND NEUTRAL TERMINAL BUSES. <br />2.03 PANELBOARD SHORT-CIRCUIT RATING <br />A.UL LABEL INDICATING SERIES-CONNECTED RATING WITH INTEGRAL OR REMOTE <br />UPSTREAM DEVICES. INCLUDE SIZE AND TYPE OF UPSTREAM DEVICE ALLOWABLE, <br />BRANCH DEVICES ALLOWABLE, AND UL SERIES-CONNECTED SHORT-CIRCUIT RATING. <br />B.FULLY RATED TO INTERRUPT SYMMETRICAL SHORT-CIRCUIT CURRENT AVAILABLE AT <br />TERMINALS. <br />2.04 LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS <br />A.BRANCH OVERCURRENT PROTECTIVE DEVICES: BOLT-ON CIRCUIT BREAKERS, <br />REPLACEABLE WITHOUT DISTURBING ADJACENT UNITS. <br />B.DOORS: FRONT MOUNTED WITH CONCEALED HINGES; SECURED WITH FLUSH LATCH <br />WITH TUMBLER LOCK; KEYED ALIKE. <br />2.05 DISTRIBUTION PANELBOARDS <br />C.DOORS: FRONT MOUNTED, EXCEPT OMIT IN FUSED-SWITCH PANELBOARDS; SECURED <br />WITH VAULT-TYPE LATCH WITH TUMBLER LOCK; KEYED ALIKE. <br />D.MAIN OVERCURRENT PROTECTIVE DEVICES: CIRCUIT BREAKER. <br />E.BRANCH OVERCURRENT PROTECTIVE DEVICES SHALL BE ONE OF THE FOLLOWING: <br />1.FOR CIRCUIT-BREAKER FRAME SIZES 125 A AND SMALLER: BOLT-ON CIRCUIT <br />BREAKERS WITH COPPER TERMINALS. <br />2.FOR CIRCUIT-BREAKER FRAME SIZES LARGER THAN 125 A: BOLT-ON CIRCUIT <br />BREAKERS WITH COPPER TERMINALS; PLUG-IN CIRCUIT BREAKERS WHERE <br />INDIVIDUAL POSITIVE-LOCKING DEVICE REQUIRES MECHANICAL RELEASE FOR <br />REMOVAL. <br />3.FUSED SWITCHES. <br />2.06 TVSS PANELBOARDS <br />A.DOORS: FRONT MOUNTED; SECURED WITH VAULT-TYPE LATCH WITH TUMBLER LOCK; <br />KEYED ALIKE. MANUFACTURER'S STANDARD ENAMEL FINISH OVER <br />CORROSION-RESISTANT TREATMENT OR PRIMER COAT. <br />B.MAIN OVERCURRENT DEVICES: THERMAL-MAGNETIC CIRCUIT BREAKER WITH COPPER <br />TERMINALS. <br />C.BRANCH OVERCURRENT PROTECTIVE DEVICES: BOLT-ON CIRCUIT BREAKERS WITH <br />COPPER TERMINALS. <br />D.BUS: COPPER PHASE AND NEUTRAL BUSES; 200 PERCENT CAPACITY NEUTRAL BUS. <br />E.TVSS DEVICE: IEEE C62.41, INTEGRALLY MOUNTED, PLUG-IN-STYLE, SOLID-STATE, <br />PARALLEL-CONNECTED, SINE-WAVE TRACKING SUPPRESSION AND FILTERING MODULES. <br />1.MINIMUM SINGLE-IMPULSE CURRENT RATING SHALL BE AS FOLLOWS: <br />a.LINE TO NEUTRAL: 100,000 A. <br />b.LINE TO GROUND: 100,000 A. <br />c.NEUTRAL TO GROUND: 50,000 A. <br />2.PROTECTION MODES SHALL BE AS FOLLOWS: <br />a.LINE TO NEUTRAL. <br />b.LINE TO GROUND. <br />c.NEUTRAL TO GROUND. <br />3.EMI/RFI NOISE ATTENUATION USING 50-OHM INSERTION LOSS TEST: 55 DB AT 100 <br />KHZ. <br />4.CATEGORY C COMBINATION WAVE CLAMPING VOLTAGE SHALL NOT EXCEED 600 V, <br />LINE TO NEUTRAL AND LINE TO GROUND ON 120/208 V SYSTEMS OR 1000 V, LINE TO <br />NEUTRAL AND LINE TO GROUND ON 277/480 V SYSTEMS. <br />5.UL 1449 CLAMPING LEVELS SHALL NOT EXCEED 400 V, LINE TO NEUTRAL AND LINE TO <br />GROUND ON 120/208 V SYSTEMS OR 800 V, LINE TO NEUTRAL AND LINE TO GROUND <br />ON 277/480 V SYSTEMS. <br />6.WITHSTAND CAPABILITIES: 3000 CATEGORY C SURGES WITH LESS THAN 5 PERCENT <br />CHANGE IN CLAMPING VOLTAGE. <br />7.ACCESSORIES SHALL INCLUDE THE FOLLOWING: <br />a.FORM-C CONTACTS, ONE NORMALLY OPEN AND ONE NORMALLY CLOSED, FOR <br />REMOTE MONITORING OF SYSTEM OPERATION. CONTACTS TO REVERSE <br />POSITION ON FAILURE OF ANY SURGE DIVERSION MODULE. <br />b.AUDIBLE ALARM ACTIVATED ON FAILURE OF ANY SURGE DIVERSION MODULE. <br />c.SIX-DIGIT TRANSIENT-COUNTER SET TO TOTAL TRANSIENT SURGES THAT <br />DEVIATE FROM THE SINE-WAVE ENVELOPE BY MORE THAN 125 V. <br />2.07 OVERCURRENT PROTECTIVE DEVICES <br />A.MOLDED-CASE CIRCUIT BREAKER: NEMA AB 1, WITH INTERRUPTING CAPACITY TO MEET <br />AVAILABLE FAULT CURRENTS. <br />1.THERMAL-MAGNETIC CIRCUIT BREAKERS: INVERSE TIME-CURRENT ELEMENT FOR <br />LOW-LEVEL OVERLOADS, AND INSTANTANEOUS MAGNETIC TRIP ELEMENT FOR <br />SHORT CIRCUITS. ADJUSTABLE MAGNETIC TRIP SETTING FOR CIRCUIT-BREAKER <br />FRAME SIZES 225 AMPERES AND LARGER. <br />2.ADJUSTABLE INSTANTANEOUS-TRIP CIRCUIT BREAKERS: MAGNETIC TRIP ELEMENT <br />WITH FRONT-MOUNTED, FIELD-ADJUSTABLE TRIP SETTING. <br />3.ELECTRONIC TRIP UNIT CIRCUIT BREAKERS: RMS SENSING; FIELD-REPLACEABLE <br />RATING PLUG; WITH THE FOLLOWING FIELD-ADJUSTABLE SETTINGS: <br />a.INSTANTANEOUS TRIP. <br />b.LONG- AND SHORT-TIME PICKUP LEVELS. <br />c.LONG- AND SHORT-TIME TIME ADJUSTMENTS. <br />d.GROUND-FAULT PICKUP LEVEL, TIME DELAY, AND I2T RESPONSE. <br />4.CURRENT-LIMITING CIRCUIT BREAKERS: FRAME SIZES 400 A AND SMALLER; <br />LET-THROUGH RATINGS LESS THAN NEMA FU 1, RK-5. <br />5.INTEGRALLY FUSED CIRCUIT BREAKERS: THERMAL-MAGNETIC TRIP ELEMENT WITH <br />INTEGRAL LIMITER-STYLE FUSE LISTED FOR USE WITH CIRCUIT BREAKER; TRIP <br />ACTIVATION ON FUSE OPENING OR ON OPENING OF FUSE COMPARTMENT DOOR. <br />6.GFCI CIRCUIT BREAKERS: SINGLE- AND TWO-POLE CONFIGURATIONS WITH 5 -MA <br />TRIP SENSITIVITY. <br />B.MOLDED-CASE CIRCUIT-BREAKER FEATURES AND ACCESSORIES. STANDARD FRAME <br />SIZES, TRIP RATINGS, AND NUMBER OF POLES. <br />1.LUGS: COMPRESSION STYLE COPPER, SUITABLE FOR NUMBER, SIZE, TRIP RATINGS, <br />AND MATERIAL OF CONDUCTORS. <br />2.APPLICATION LISTING: APPROPRIATE FOR APPLICATION; TYPE SWD FOR SWITCHING <br />FLUORESCENT LIGHTING LOADS; TYPE HACR FOR HEATING, AIR-CONDITIONING, AND <br />REFRIGERATING EQUIPMENT. <br />3.GROUND-FAULT PROTECTION: INTEGRALLY MOUNTED RELAY AND TRIP UNIT WITH <br />ADJUSTABLE PICKUP AND TIME-DELAY SETTINGS, PUSH-TO-TEST FEATURE, AND <br />GROUND-FAULT INDICATOR. <br />4.COMMUNICATION CAPABILITY: CIRCUIT-BREAKER-MOUNTED COMMUNICATION <br />MODULE WITH FUNCTIONS AND FEATURES COMPATIBLE WITH POWER MONITORING <br />AND CONTROL SYSTEM. <br />5.SHUNT TRIP: 120-V TRIP COIL ENERGIZED FROM SEPARATE CIRCUIT, SET TO TRIP AT <br />75 PERCENT OF RATED VOLTAGE. <br />6.UNDER-VOLTAGE TRIP: SET TO OPERATE AT 35 TO 75 PERCENT OF RATED VOLTAGE <br />WITHOUT INTENTIONAL TIME DELAY. <br />7.AUXILIARY SWITCH: TWO SPDT SWITCHES WITH "A" AND "B" CONTACTS; "A" <br />CONTACTS MIMIC CIRCUIT-BREAKER CONTACTS, "B" CONTACTS OPERATE IN <br />REVERSE OF CIRCUIT-BREAKER CONTACTS. <br />8.KEY INTERLOCK KIT: EXTERNALLY MOUNTED TO PROHIBIT CIRCUIT-BREAKER <br />OPERATION; KEY SHALL BE REMOVABLE ONLY WHEN CIRCUIT BREAKER IS IN OFF <br />POSITION. <br />9.ZONE-SELECTIVE INTERLOCKING: INTEGRAL WITH ELECTRONIC TRIP UNIT; FOR <br />INTERLOCKING GROUND-FAULT PROTECTION FUNCTION. <br />C.FUSED SWITCH: NEMA KS 1, TYPE HD; CLIPS TO ACCOMMODATE SPECIFIED FUSES; <br />LOCKABLE HANDLE. <br />2.08 CONTROLLERS <br />A.MOTOR CONTROLLERS: NEMA ICS 2, CLASS A COMBINATION CONTROLLER EQUIPPED <br />FOR PANELBOARD MOUNTING AND INCLUDING THE FOLLOWING ACCESSORIES: <br />1.INDIVIDUAL CONTROL-POWER TRANSFORMERS. <br />2.FUSES FOR CONTROL-POWER TRANSFORMERS. <br />3.BIMETALLIC-ELEMENT OVERLOAD RELAY. <br />4.MELTING-ALLOY OVERLOAD RELAY. <br />5.INDICATING LIGHTS. <br />6.SEAL-IN CONTACT. <br />7.2 CONVERTIBLE AUXILIARY CONTACTS. <br />8.PUSH BUTTONS. <br />9.SELECTOR SWITCHES. <br />B.CONTACTORS: NEMA ICS 2, CLASS A COMBINATION CONTROLLER EQUIPPED FOR <br />PANELBOARD MOUNTING AND INCLUDING THE FOLLOWING ACCESSORIES: <br />1.INDIVIDUAL CONTROL-POWER TRANSFORMERS. <br />2.FUSES FOR CONTROL-POWER TRANSFORMERS. <br />3.INDICATING LIGHTS. <br />4.SEAL-IN CONTACT. <br />5.2 CONVERTIBLE AUXILIARY CONTACTS. <br />6.PUSH BUTTONS. <br />7.SELECTOR SWITCHES. <br />C.CONTROLLER DISCONNECT SWITCHES: FUSED SWITCH AND INTERLOCKED WITH <br />CONTROLLER. <br />1.AUXILIARY CONTACTS: INTEGRAL WITH DISCONNECT SWITCHES TO DE-ENERGIZE <br />EXTERNAL CONTROL-POWER SOURCE. <br />D.CONTACTORS IN MAIN BUS: NEMA ICS 2, CLASS A, MECHANICALLY HELD <br />GENERAL-PURPOSE CONTROLLER. <br />1.CONTROL-POWER SOURCE: CONTROL-POWER TRANSFORMER, WITH FUSED <br />PRIMARY AND SECONDARY TERMINALS, CONNECTED TO MAIN BUS AHEAD OF <br />CONTACTOR CONNECTION. <br />2.CONTROL-POWER SOURCE: 120-V BRANCH CIRCUIT. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A.INSTALL PANELBOARDS AND ACCESSORIES IN ACCORDANCE WITH NEMA PB 1.1. <br />B.COMPLY WITH MOUNTING AND ANCHORING REQUIREMENTS SPECIFIED IN DIVISION 26 <br />SECTION "VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL WORK." <br />C.MOUNTING HEIGHTS: TOP OF TRIM 74 INCHES ABOVE FINISHED FLOOR, UNLESS <br />OTHERWISE INDICATED. <br />D.MOUNTING: PLUMB AND RIGID WITHOUT DISTORTION OF BOX. MOUNT RECESSED <br />PANELBOARDS WITH FRONTS UNIFORMLY FLUSH WITH WALL FINISH. <br />E.CIRCUIT DIRECTORY: CREATE A DIRECTORY TO INDICATE INSTALLED CIRCUIT LOADS <br />AFTER BALANCING PANELBOARD LOADS. OBTAIN APPROVAL BEFORE INSTALLING. USE <br />A COMPUTER OR TYPEWRITER TO CREATE DIRECTORY; HANDWRITTEN DIRECTORIES <br />ARE NOT ACCEPTABLE. <br />F.INSTALL FILLER PLATES IN UNUSED SPACES. <br />G.PROVISION FOR FUTURE CIRCUITS AT FLUSH PANELBOARDS: STUB FOUR 1-INCH EMPTY <br />CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE <br />DESIGNATED TO BE CEILING SPACE IN THE FUTURE. STUB FOUR 1-INCH EMPTY <br />CONDUITS INTO RAISED FLOOR SPACE OR BELOW SLAB NOT ON GRADE. <br />H.WIRING IN PANELBOARD GUTTERS: ARRANGE CONDUCTORS INTO GROUPS AND BUNDLE <br />AND WRAP WITH WIRE TIES AFTER COMPLETING LOAD BALANCING. <br />3.02 IDENTIFICATION <br />A.IDENTIFY FIELD-INSTALLED CONDUCTORS, INTERCONNECTING WIRING, AND <br />COMPONENTS; PROVIDE WARNING SIGNS AS SPECIFIED IN DIVISION 26 SECTION <br />IDENTIFICATION FOR ELECTRICAL SYSTEMS. <br />B.PANELBOARD NAMEPLATES: LABEL EACH PANELBOARD WITH LAMINATED-PLASTIC <br />NAMEPLATE MOUNTED WITH CORROSION-RESISTANT SCREWS. <br />3.03 CONNECTIONS <br />A.INSTALL EQUIPMENT GROUNDING CONNECTIONS FOR PANELBOARDS WITH GROUND <br />CONTINUITY TO MAIN ELECTRICAL GROUND BUS. <br />B.TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS IN ACCORDANCE WITH <br />MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S <br />TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A. <br />3.04 FIELD QUALITY CONTROL <br />A.PREPARE FOR ACCEPTANCE TESTS AS FOLLOWS: <br />1.TEST INSULATION RESISTANCE FOR EACH PANELBOARD BUS, COMPONENT, <br />CONNECTING SUPPLY, FEEDER, AND CONTROL CIRCUIT. <br />2.TEST CONTINUITY OF EACH CIRCUIT. <br />B.TESTING: AFTER INSTALLING PANELBOARDS AND AFTER ELECTRICAL CIRCUITRY HAS <br />BEEN ENERGIZED, DEMONSTRATE PRODUCT CAPABILITY AND COMPLIANCE WITH <br />REQUIREMENTS. <br />1.PROCEDURES: PERFORM EACH VISUAL AND MECHANICAL INSPECTION AND <br />ELECTRICAL TEST INDICATED IN NETA ATS, SECTION 7.5 FOR SWITCHES AND <br />SECTION 7.6 FOR MOLDED-CASE CIRCUIT BREAKERS. CERTIFY COMPLIANCE WITH <br />TEST PARAMETERS. <br />2.CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE, AND RETEST TO <br />DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RETEST. <br />C.BALANCING LOADS: AFTER SUBSTANTIAL COMPLETION, BUT NOT MORE THAN 60 DAYS <br />AFTER FINAL ACCEPTANCE, MEASURE LOAD BALANCING AND MAKE CIRCUIT CHANGES <br />AS FOLLOWS: <br />1.MEASURE AS DIRECTED DURING PERIOD OF NORMAL SYSTEM LOADING. <br />2.PERFORM LOAD-BALANCING CIRCUIT CHANGES OUTSIDE NORMAL <br />OCCUPANCY/WORKING SCHEDULE OF THE FACILITY AND AT TIME DIRECTED. AVOID <br />DISRUPTING CRITICAL 24-HOUR SERVICES SUCH AS FAX MACHINES AND ON-LINE <br />DATA-PROCESSING, COMPUTING, TRANSMITTING, AND RECEIVING EQUIPMENT. <br />3.AFTER CIRCUIT CHANGES, RECHECK LOADS DURING NORMAL LOAD PERIOD. <br />RECORD LOAD READINGS BEFORE AND AFTER CHANGES AND SUBMIT TEST <br />RECORDS. <br />4.TOLERANCE: DIFFERENCE EXCEEDING 20 PERCENT BETWEEN PHASE LOADS, WITHIN <br />A PANELBOARD, IS NOT ACCEPTABLE. REBALANCE AND RECHECK AS NECESSARY TO <br />MEET THIS MINIMUM REQUIREMENT. <br />3.05 ADJUSTING <br />A.SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES. <br />3.06 CLEANING <br />A.ON COMPLETION OF INSTALLATION, INSPECT INTERIOR AND EXTERIOR OF <br />PANELBOARDS. REMOVE PAINT SPLATTERS AND OTHER SPOTS. VACUUM DIRT AND <br />DEBRIS; DO NOT USE COMPRESSED AIR TO ASSIST IN CLEANING. REPAIR EXPOSED <br />SURFACES TO MATCH ORIGINAL FINISH. <br />SECTION 26 2816 <br />ENCLOSED SWITCHES AND CIRCUIT BREAKERS <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES THE FOLLOWING INDIVIDUALLY MOUNTED, ENCLOSED SWITCHES <br />AND CIRCUIT BREAKERS: <br />1.FUSIBLE SWITCHES. <br />2.NONFUSIBLE SWITCHES. <br />3.BOLTED-PRESSURE CONTACT SWITCHES. <br />4.ENCLOSURES. <br />1.02 DEFINITIONS <br />A.HD: HEAVY DUTY. <br />1.03 SUBMITTALS <br />A.PRODUCT DATA: FOR EACH TYPE OF ENCLOSED SWITCH, CIRCUIT BREAKER, <br />ACCESSORY, AND COMPONENT INDICATED. INCLUDE DIMENSIONED ELEVATIONS, <br />SECTIONS, WEIGHTS, AND MANUFACTURERS' TECHNICAL DATA ON FEATURES, <br />PERFORMANCE, ELECTRICAL CHARACTERISTICS, RATINGS, AND FINISHES. <br />1.ENCLOSURE TYPES AND DETAILS FOR TYPES OTHER THAN NEMA 250, TYPE 1. <br />2.CURRENT AND VOLTAGE RATINGS. <br />3.SHORT-CIRCUIT CURRENT RATING. <br />4.FEATURES, CHARACTERISTICS, RATINGS, AND FACTORY SETTINGS OF INDIVIDUAL <br />OVERCURRENT PROTECTIVE DEVICES AND AUXILIARY COMPONENTS. <br />B.SHOP DRAWINGS: DIAGRAM POWER, SIGNAL, AND CONTROL WIRING. <br />C.MANUFACTURER SEISMIC QUALIFICATION CERTIFICATION: SUBMIT CERTIFICATION THAT <br />ENCLOSED SWITCHES AND CIRCUIT BREAKERS, ACCESSORIES, AND COMPONENTS WILL <br />WITHSTAND SEISMIC FORCES DEFINED IN DIVISION 26 SECTION "VIBRATION AND SEISMIC <br />CONTROLS FOR ELECTRICAL WORK." INCLUDE THE FOLLOWING: <br />1.BASIS OF CERTIFICATION: INDICATE WHETHER WITHSTAND CERTIFICATION IS BASED <br />ON ACTUAL TEST OF ASSEMBLED COMPONENTS OR ON CALCULATION. <br />a.THE TERM "WITHSTAND" MEANS "THE UNIT WILL REMAIN IN PLACE WITHOUT <br />SEPARATION OF ANY PARTS FROM THE DEVICE WHEN SUBJECTED TO THE <br />SEISMIC FORCES SPECIFIED AND THE UNIT WILL BE FULLY OPERATIONAL AFTER <br />THE SEISMIC EVENT." <br />2.DIMENSIONED OUTLINE DRAWINGS OF EQUIPMENT UNIT: IDENTIFY CENTER OF <br />GRAVITY AND LOCATE AND DESCRIBE MOUNTING AND ANCHORAGE PROVISIONS. <br />3.DETAILED DESCRIPTION OF EQUIPMENT ANCHORAGE DEVICES ON WHICH THE <br />CERTIFICATION IS BASED AND THEIR INSTALLATION REQUIREMENTS. <br />D.QUALIFICATION DATA: FOR TESTING AGENCY. <br />E.FIELD QUALITY-CONTROL TEST REPORTS INCLUDING THE FOLLOWING: <br />1.TEST PROCEDURES USED. <br />2.TEST RESULTS THAT COMPLY WITH REQUIREMENTS. <br />3.RESULTS OF FAILED TESTS AND CORRECTIVE ACTION TAKEN TO ACHIEVE TEST <br />RESULTS THAT COMPLY WITH REQUIREMENTS. <br />F.MANUFACTURER'S FIELD SERVICE REPORT. <br />G.OPERATION AND MAINTENANCE DATA: FOR ENCLOSED SWITCHES AND CIRCUIT <br />BREAKERS TO INCLUDE IN EMERGENCY, OPERATION, AND MAINTENANCE MANUALS. IN <br />ADDITION TO ITEMS SPECIFIED IN DIVISION 01 SECTIONS "PROJECT CLOSEOUT” AND <br />“OPERATION AND MAINTENANCE DATA," INCLUDE THE FOLLOWING: <br />1.MANUFACTURER'S WRITTEN INSTRUCTIONS FOR TESTING AND ADJUSTING <br />ENCLOSED SWITCHES AND CIRCUIT BREAKERS. <br />2.TIME-CURRENT CURVES, INCLUDING SELECTABLE RANGES FOR EACH TYPE OF <br />CIRCUIT BREAKER. <br />1.04 QUALITY ASSURANCE <br />A.TESTING AGENCY QUALIFICATIONS: AN INDEPENDENT AGENCY, WITH THE EXPERIENCE <br />AND CAPABILITY TO CONDUCT THE TESTING INDICATED, THAT IS A MEMBER COMPANY OF <br />THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR IS A NATIONALLY <br />RECOGNIZED TESTING LABORATORY (NRTL) AS DEFINED BY OSHA IN 29 CFR 1910.7, AND <br />THAT IS ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. <br />1.TESTING AGENCY'S FIELD SUPERVISOR: PERSON CURRENTLY CERTIFIED BY THE <br />INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR THE NATIONAL INSTITUTE <br />FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES TO SUPERVISE ON-SITE <br />TESTING SPECIFIED IN PART 3. <br />B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS <br />DEFINED IN CEC, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES <br />HAVING JURISDICTION, AND MARKED FOR INTENDED USE. <br />C.COMPLY WITH CEC. <br />D.PRODUCT SELECTION FOR RESTRICTED SPACE: DRAWINGS INDICATE MAXIMUM <br />DIMENSIONS FOR ENCLOSED SWITCHES AND CIRCUIT BREAKERS, INCLUDING <br />CLEARANCES BETWEEN ENCLOSURES, AND ADJACENT SURFACES AND OTHER ITEMS. <br />COMPLY WITH INDICATED MAXIMUM DIMENSIONS. <br />E.STRUCTURAL SEISMIC PERFORMANCE: REFER TO DIVISION 26 SECTION “VIBRATION AND <br />SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.” <br />1.05 PROJECT CONDITIONS <br />A.ENVIRONMENTAL LIMITATIONS: RATE EQUIPMENT FOR CONTINUOUS OPERATION UNDER <br />THE FOLLOWING CONDITIONS, UNLESS OTHERWISE INDICATED: <br />1.AMBIENT TEMPERATURE: NOT LESS THAN MINUS 22°F AND NOT EXCEEDING 104°F. <br />2.ALTITUDE: NOT EXCEEDING 6600 FEET. <br />1.06 COORDINATION <br />A.COORDINATE LAYOUT AND INSTALLATION OF SWITCHES, CIRCUIT BREAKERS, AND <br />COMPONENTS WITH OTHER CONSTRUCTION, INCLUDING CONDUIT, PIPING, EQUIPMENT, <br />AND ADJACENT SURFACES. MAINTAIN REQUIRED WORKSPACE CLEARANCES AND <br />REQUIRED CLEARANCES FOR EQUIPMENT ACCESS DOORS AND PANELS. <br />1.07 EXTRA MATERIALS <br />A.FURNISH EXTRA MATERIALS DESCRIBED BELOW THAT MATCH PRODUCTS INSTALLED <br />AND THAT ARE PACKAGED WITH PROTECTIVE COVERING FOR STORAGE AND IDENTIFIED <br />WITH LABELS DESCRIBING CONTENTS. <br />1.SPARES: FOR THE FOLLOWING: <br />a.POTENTIAL TRANSFORMER FUSES: 4. <br />b.CONTROL-POWER FUSES: 4. <br />c.FUSES FOR FUSIBLE SWITCHES: 3. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.IN OTHER PART 2 ARTICLES WHERE TITLES BELOW INTRODUCE LISTS, THE FOLLOWING <br />REQUIREMENTS APPLY TO PRODUCT SELECTION: <br />1.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE <br />PRODUCTS BY ONE OF THE MANUFACTURERS SPECIFIED. <br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01 <br />SECTION “PRODUCT OPTIONS AND SUBSTITUTIONS”. SPECIFIC PROCEDURES MUST <br />BE FOLLOWED BEFORE USE OF AN UNNAMED PRODUCT OR MANUFACTURER. <br />2.02 FUSIBLE AND NONFUSIBLE SWITCHES <br />A.MANUFACTURERS: <br />1.EATON CORPORATION; CUTLER-HAMMER PRODUCTS. <br />2.GENERAL ELECTRIC CO.; ELECTRICAL DISTRIBUTION & CONTROL DIVISION. <br />3.SIEMENS ENERGY & AUTOMATION, INC. <br />4.SQUARE D/GROUP SCHNEIDER. <br />5.OR EQUAL. <br />B.FUSIBLE SWITCH, 600 A AND SMALLER: NEMA KS 1, TYPE HD, WITH CLIPS OR BOLT PADS <br />TO ACCOMMODATE SPECIFIED FUSES, LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT <br />TWO PADLOCKS, AND INTERLOCKED WITH COVER IN CLOSED POSITION. <br />C.NONFUSIBLE SWITCH, 600 A AND SMALLER: NEMA KS 1, TYPE HD, LOCKABLE HANDLE <br />WITH CAPABILITY TO ACCEPT TWO PADLOCKS, AND INTERLOCKED WITH COVER IN <br />CLOSED POSITION. <br />D.ACCESSORIES: <br />1.EQUIPMENT GROUND KIT: INTERNALLY MOUNTED AND LABELED FOR COPPER <br />GROUND CONDUCTORS. <br />2.NEUTRAL KIT: INTERNALLY MOUNTED; INSULATED, CAPABLE OF BEING GROUNDED, <br />AND BONDED; AND LABELED FOR COPPER NEUTRAL CONDUCTORS. <br />3.AUXILIARY CONTACT KIT: AUXILIARY SET OF CONTACTS ARRANGED TO OPEN <br />BEFORE SWITCH BLADES OPEN. <br />2.03 FUSED POWER CIRCUIT DEVICES <br />A.BOLTED-PRESSURE CONTACT SWITCH: UL 977; OPERATING MECHANISM SHALL USE A <br />ROTARY-MECHANICAL-BOLTING ACTION TO PRODUCE AND MAINTAIN HIGH-CLAMPING <br />PRESSURE ON THE SWITCH BLADE AFTER IT ENGAGES THE STATIONARY CONTACTS. <br />1.MANUFACTURERS: <br />a.EATON CORPORATION; CUTLER-HAMMER PRODUCTS. <br />b.PRINGLE ELECTRICAL MFG. CO. <br />c.SIEMENS ENERGY & AUTOMATION, INC. <br />d.SQUARE D/GROUP SCHNEIDER. <br />e.OR EQUAL. <br />2.04 ENCLOSURES <br />A.NEMA AB 1 AND NEMA KS 1 TO MEET ENVIRONMENTAL CONDITIONS OF INSTALLED <br />LOCATION. <br />1.OUTDOOR LOCATIONS: NEMA 250, TYPE 3R. <br />2.KITCHEN AREAS: NEMA 250, TYPE 4X, STAINLESS STEEL. <br />3.OTHER WET OR DAMP INDOOR LOCATIONS: NEMA 250, TYPE 4. <br />4.HAZARDOUS AREAS INDICATED ON DRAWINGS: NEMA 250, TYPE 7C. <br />PART 3 - EXECUTION <br />3.01 EXAMINATION <br />A.EXAMINE ELEMENTS AND SURFACES TO RECEIVE ENCLOSED SWITCHES AND CIRCUIT <br />BREAKERS FOR COMPLIANCE WITH INSTALLATION TOLERANCES AND OTHER <br />CONDITIONS AFFECTING PERFORMANCE. <br />B.PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN <br />CORRECTED.3.02 CONCRETE BASES <br />C.COORDINATE SIZE AND LOCATION OF CONCRETE BASES. VERIFY STRUCTURAL <br />REQUIREMENTS WITH STRUCTURAL ENGINEER. <br />D.CONCRETE BASE IS SPECIFIED IN DIVISION 26 SECTION "COMMON WORK RESULTS FOR <br />ELECTRICAL," AND CONCRETE MATERIALS AND INSTALLATION REQUIREMENTS ARE <br />SPECIFIED IN DIVISION 03. <br />3.02 INSTALLATION <br />A.COMPLY WITH APPLICABLE PORTIONS OF NECA 1, NEMA PB 1.1, AND NEMA PB 2.1 FOR <br />INSTALLATION OF ENCLOSED SWITCHES AND CIRCUIT BREAKERS. <br />B.MOUNT INDIVIDUAL WALL-MOUNTING SWITCHES AND CIRCUIT BREAKERS WITH TOPS AT <br />UNIFORM HEIGHT, UNLESS OTHERWISE INDICATED. ANCHOR FLOOR-MOUNTING <br />SWITCHES TO CONCRETE BASE. <br />C.<COMPLY WITH MOUNTING AND ANCHORING REQUIREMENTS SPECIFIED IN DIVISION 26 <br />SECTION "VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS."> <br />D.TEMPORARY LIFTING PROVISIONS: REMOVE TEMPORARY LIFTING EYES, CHANNELS, AND <br />BRACKETS AND TEMPORARY BLOCKING OF MOVING PARTS FROM ENCLOSURES AND <br />COMPONENTS. <br />3.03 IDENTIFICATION <br />A.IDENTIFY FIELD-INSTALLED CONDUCTORS, INTERCONNECTING WIRING, AND <br />COMPONENTS; PROVIDE WARNING SIGNS AS SPECIFIED IN DIVISION 26 SECTION <br />"COMMON WORK RESULTS FOR ELECTRICAL” AND IDENTIFICATION FOR ELECTRICAL <br />SYSTEMS." <br />B.ENCLOSURE NAMEPLATES: LABEL EACH ENCLOSURE WITH ENGRAVED METAL OR <br />LAMINATED-PLASTIC NAMEPLATE AS SPECIFIED IN DIVISION 26 SECTION “IDENTIFICATION <br />FOR ELECTRICAL SYSTEMS". <br />3.04 FIELD QUALITY CONTROL <br />A.MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY-AUTHORIZED SERVICE <br />REPRESENTATIVE TO INSPECT TEST, AND ADJUST FIELD-ASSEMBLED COMPONENTS AND <br />EQUIPMENT INSTALLATION, INCLUDING CONNECTIONS, AND TO ASSIST IN FIELD TESTING. <br />REPORT RESULTS IN WRITING. <br />1.INSPECT MECHANICAL AND ELECTRICAL CONNECTIONS. <br />2.VERIFY SWITCH AND RELAY TYPE AND LABELING VERIFICATION. <br />3.VERIFY RATING OF INSTALLED FUSES. <br />4.INSPECT PROPER INSTALLATION OF TYPE, SIZE, QUANTITY, AND ARRANGEMENT OF <br />MOUNTING OR ANCHORAGE DEVICES COMPLYING WITH MANUFACTURER'S <br />CERTIFICATION. <br />B.PERFORM THE FOLLOWING FIELD TESTS AND INSPECTIONS AND PREPARE TEST <br />REPORTS: <br />1.TEST MOUNTING AND ANCHORAGE DEVICES IN ACCORDANCE WITH REQUIREMENTS <br />IN< DIVISION 26 SECTION "VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL <br />WORK". <br />2.PERFORM EACH ELECTRICAL TEST AND VISUAL AND MECHANICAL INSPECTION <br />STATED IN NETA ATS, SECTION 7.5 FOR SWITCHES AND SECTION 7.6 FOR <br />MOLDED-CASE CIRCUIT BREAKERS. CERTIFY COMPLIANCE WITH TEST PARAMETERS. <br />3.CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE, AND RETEST TO <br />DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RETEST. <br />4.INFRARED SCANNING: <br />a.INITIAL INFRARED SCANNING: AFTER SUBSTANTIAL COMPLETION, BUT NOT MORE <br />THAN 60 DAYS AFTER FINAL ACCEPTANCE, PERFORM AN INFRARED SCAN OF <br />EACH ENCLOSED SWITCH AND CIRCUIT BREAKER. OPEN OR REMOVE DOORS OR <br />PANELS SO CONNECTIONS ARE ACCESSIBLE TO PORTABLE SCANNER. <br />b.FOLLOW-UP INFRARED SCANNING: PERFORM AN ADDITIONAL FOLLOW-UP <br />INFRARED SCAN OF EACH UNIT 11 MONTHS AFTER DATE OF SUBSTANTIAL <br />COMPLETION. <br />c.INSTRUMENTS, EQUIPMENT AND REPORTS: <br />1)USE AN INFRARED SCANNING DEVICE DESIGNED TO MEASURE TEMPERATURE <br />OR TO DETECT SIGNIFICANT DEVIATIONS FROM NORMAL VALUES. PROVIDE <br />CALIBRATION RECORD FOR DEVICE. <br />2)PREPARE A CERTIFIED REPORT THAT IDENTIFIES ENCLOSED SWITCHES AND <br />CIRCUIT BREAKERS INCLUDED AND DESCRIBES SCANNING RESULTS. <br />INCLUDE NOTATION OF DEFICIENCIES DETECTED, REMEDIAL ACTION TAKEN, <br />AND OBSERVATIONS AFTER REMEDIAL ACTION. <br />3.05 ADJUSTING <br />A.SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES. <br />3.06 CLEANING <br />A.ON COMPLETION OF INSTALLATION, VACUUM DIRT AND DEBRIS FROM INTERIORS; DO <br />NOT USE COMPRESSED AIR TO ASSIST IN CLEANING. <br />SECTION 26 5103 <br />INTERIOR SOLID STATE LIGHTING <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />B.SECTION INCLUDES: <br />1.INTERIOR SOLID STATE LIGHTING (SSL) LUMINAIRES, LEDS, AND DRIVERS. <br />2.LIGHTING FIXTURE SUPPORTS. <br />1.02 DEFINITIONS <br />A.CCT: CORRELATED COLOR TEMPERATURE. <br />B.CRI: COLOR-RENDERING INDEX. <br />C.LED: LIGHT EMITTING DIODE. <br />D.LER: LUMINAIRE EFFICACY RATING. <br />E.LUMEN: MEASURED OUTPUT OF LAMP AND LUMINAIRE. <br />F.LPW: LUMENS PER WATT. <br />G.LUMINAIRE: COMPLETE LIGHTING FIXTURE, INCLUDING DRIVER. <br />1.03 ACTION SUBMITTALS <br />A.PRODUCT DATA: FOR EACH TYPE OF LIGHTING FIXTURE, ARRANGED OF FIXTURE <br />DESIGNATION. INCLUDE DATA ON FEATURES, ACCESSORIES, FINISHES, AND THE <br />FOLLOWING: <br />1.PHYSICAL DESCRIPTION OF LIGHTING FIXTURE INCLUDING DIMENSIONS. <br />2.ENERGY-EFFICIENCY DATA. <br />3.LIFE, OUTPUT (LUMENS, CCT, AND CRI), AND ENERGY-EFFICIENCY DATA FOR SSL. <br />4.PHOTOMETRIC DATA AND ADJUSTMENT FACTORS BASED ON LABORATORY TESTS, <br />COMPLYING WITH IESNA LIGHTING MEASUREMENTS TESTING & CALCULATION <br />GUIDES, OF EACH LIGHTING FIXTURE TYPE. <br />a.MANUFACTURER CERTIFIED DATA: PHOTOMETRIC DATA SHALL BE CERTIFIED BY <br />A MANUFACTURER'S LABORATORY WITH A CURRENT ACCREDITATION UNDER THE <br />NATIONAL VOLUNTARY LABORATORY ACCREDITATION PROGRAM FOR ENERGY <br />EFFICIENT LIGHTING PRODUCTS. <br />B.PROIVE LIGHTING CONTROL SAMPLES: FOR EACH LIGHTING FIXTURE INDICATED IN THE <br />INTERIOR LIGHTING FIXTURE SCHEDULE. EACH SAMPLE SHALL INCLUDE A COMPLETE <br />LUMINAIRE OR LAMP. <br />C.INSTALLATION INSTRUCTIONS. <br />1.04 INFORMATIONAL SUBMITTALS <br />A.FIELD QUALITY-CONTROL REPORTS. <br />B.WARRANTY: SAMPLE OF SPECIAL OR EXTENDED WARRANTY. <br />C.SSL LUMINAIRE - IES LM-79 TEST REPORT: SUBMIT TEST REPORT ON MANUFACTURER'S <br />STANDARD PRODUCTION MODEL LUMINAIRE. <br />D.LED LIGHT SOURCE - IES LM-80 TEST REPORT: SUBMIT REPORT ON MANUFACTURER'S <br />STANDARD PRODUCTION LED PACKAGE, ARRAY, OR MODULE. <br />1.05 CLOSEOUT SUBMITTALS <br />A.OPERATION AND MAINTENANCE DATA: FOR LIGHTING LUMINAIRES TO INCLUDE IN <br />OPERATION, AND MAINTENANCE MANUALS. <br />1.06 QUALITY ASSURANCE <br />A.LAMPS SHALL BE LISTED ON THE SOUTHERN CALIFORNIA EDISON LIST OF APPROVED <br />LAMP MANUFACTURERS, ENERGY STAR (ES) APPROVED LAMPS AND FIXTURE LISTS AT <br />FOLLOWING WEBSITE: <br />HTTP://WWW.ENERGYSTAR.GOV/PRODUCTFINDER/PRODUCT/CERTIFIED-LIGHT-BULBS <br />HTTP://WWW.ENERGYSTAR.GOV/PRODUCTFINDER/PRODUCT/CERTIFIED-LIGHT-FIXTURES/RESULTS <br />OR THE DESIGNLIGHTS™ CONSORTIUM (DLC) QUALIFIED PRODUCTS LIST WHICH IS <br />AVAILABLE AT THE FOLLOWING WEBSITE <br />HTTP://WWW.DESIGNLIGHTS.ORG/SOLIDSTATE.ABOUT.QUALIFIEDPRODUCTSLIST_PUBLICV2.PHP. <br />B.THE OWNER HAS ENDEAVORED TO PROVIDE THE MOST ENERGY LIGHT SOURCE AND <br />LOWER LIFE CYCLE COST LAMPS AND LUMINARIES. THE OWNER NO LONGER ALLOWS <br />THE USE OF FLUORESCENT TUBES, U-TUBE LAMPS, METAL HALIDE, HIGH OR LOW <br />PRESSURE SODIUM OR INCANDESCENT LAMPS. USE OF SSL IS THE OWNER'S STANDARD. <br />C.LUMINAIRE PHOTOMETRIC DATA TESTING LABORATORY QUALIFICATIONS: PROVIDED BY <br />MANUFACTURERS' LABORATORIES THAT ARE ACCREDITED UNDER THE NATIONAL <br />VOLUNTEER LABORATORY ACCREDITATION PROGRAM FOR ENERGY EFFICIENT LIGHTING <br />PRODUCTS. <br />D.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS <br />DEFINED IN CALIFORNIA ELECTRIC CODE BY A QUALIFIED TESTING AGENCY, AND <br />MARKED FOR INTENDED LOCATION AND APPLICATION. <br />E.UL COMPLIANCE: LIGHTING FIXTURES FOR HAZARDOUS LOCATIONS SHALL BE LISTED <br />AND LABELED FOR INDICATED CLASS AND DIVISION BY UL. <br />F.SSL LIGHT FIXTURES SHALL BE REDUCTION OF HAZARDOUS SUBSTANCES <br />(ROHS)-COMPLIANT. <br />G.STRUCTURAL SEISMIC PERFORMANCE: REFER TO DIVISION 26 SECTION “VIBRATION AND <br />SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.” <br />1.07 COORDINATION <br />A.COORDINATE LAYOUT AND INSTALLATION OF LIGHTING FIXTURES AND SUSPENSION <br />SYSTEM WITH OTHER CONSTRUCTION THAT PENETRATES CEILINGS OR IS SUPPORTED <br />BY THEM, INCLUDING HVAC EQUIPMENT, FIRE-SUPPRESSION SYSTEM, AND PARTITION <br />ASSEMBLIES. <br />1.08 WARRANTY <br />A.SPECIAL WARRANTY FOR EMERGENCY LIGHTING BATTERIES: MANUFACTURER'S <br />STANDARD FORM IN WHICH MANUFACTURER OF BATTERY-POWERED EMERGENCY <br />LIGHTING UNIT AGREES TO REPAIR OR REPLACE COMPONENTS OF RECHARGEABLE <br />BATTERIES THAT FAIL IN MATERIALS OR WORKMANSHIP WITHIN SPECIFIED WARRANTY <br />PERIOD. <br />1.WARRANTY PERIOD FOR EMERGENCY LIGHTING UNIT BATTERIES: 10 YEARS FROM <br />DATE OF SUBSTANTIAL COMPLETION. FULL WARRANTY SHALL APPLY FOR FIRST <br />YEAR, AND PRORATED WARRANTY FOR THE REMAINING NINE YEARS. <br />B.LED LUMINAIRES: SUBMIT A WARRANTY, EXECUTED BY THE INSTALLER AGREEING TO <br />INSTALL REPLACEMENT LED LUMINARIES THAT FAIL WITHIN TWO YEARS, BEGINNING ON <br />THE DATE OF SUBSTANTIAL COMPLETION. THIS WARRANTY IS IN ADDITION TO, AND NOT <br />A LIMITATION OF, OTHER RIGHTS AND REMEDIES THE OWNER MAY HAVE UNDER THE <br />CONTRACTED DOCUMENTS. <br />C.SPECIAL WARRANTY: MANUFACTURER'S STANDARD FORM IN WHICH MANUFACTURER <br />AGREES TO REPAIR OR REPLACE LUMINAIRES OR COMPONENTS OF LUMINAIRES, <br />DIODES, DRIVERS AND LAMPS THAT FAIL IN MATERIALS OR WORKMANSHIP; CORRODE; <br />OR FADE, WITHIN SPECIFIED WARRANTY PERIOD IN THE FIXTURE SCHEDULE. <br />MANUFACTURER MAY EXCLUDE LIGHTNING DAMAGE, VANDALISM, ABUSE, OR <br />UNAUTHORIZED REPAIRS OR ALTERATIONS FROM SPECIAL WARRANTY COVERAGE. <br />1.LUMEN MAINTENANCE VALUE FOR THE PRODUCT SHALL NOT FALL BELOW 70% OF <br />THE LUMEN MAINTENANCE VALUE SPECIFIED. <br />2.FINISH WARRANTY SHALL INCLUDE WARRANTY AGAINST FAILURE AND AGAINST <br />SUBSTANTIAL DETERIORATION SUCH AS BLISTERING, CRACKING, PEELING, <br />CHALKING, OR FADING. <br />3.MATERIAL WARRANTY SHALL INCLUDE: <br />a.POWER SUPPLY UNITS (DRIVERS). <br />b.REPLACEMENT WHEN MORE THAN 10 PERCENT OF LED SOURCES IN ANY LIGHT <br />BAR OR SUBASSEMBLY(S) ARE DEFECTIVE OR NON-STARTING. <br />4.WARRANTY PERIOD MUST BEGIN ON DATE OF BENEFICIAL OCCUPANCY. <br />CONTRACTOR SHALL PROVIDE THE OWNER'S REPRESENTATIVE SIGNED WARRANTY <br />CERTIFICATES. <br />D.EXTENDED WARRANTY FOR LED LAMPS: <br />1.PROVIDE A MANUFACTURER'S WRITTEN 10 YEAR REPLACEMENT WARRANTY FOR <br />MATERIAL AND WORKMANSHIP. <br />2.LUMEN MAINTENANCE VALUE FOR THE PRODUCT SHALL NOT FALL BELOW 70% OF <br />THE LUMEN MAINTENANCE VALUE SPECIFIED. <br />3.MATERIAL WARRANTY SHALL INCLUDE: <br />a.POWER SUPPLY UNITS (DRIVERS). <br />b.REPLACEMENT WHEN MORE THAN 10 PERCENT OF LED SOURCES IN ANY <br />LIGHTBAR OR SUBASSEMBLY(S) ARE DEFECTIVE OR NON-STARTING. <br />4.WARRANTY PERIOD MUST BEGIN ON DATE OF BENEFICIAL OCCUPANCY. <br />CONTRACTOR SHALL PROVIDE THE OWNER'S REPRESENTATIVE SIGNED WARRANTY <br />CERTIFICATES. <br />PART 2 - PRODUCTS <br />2.01 MANUFACTURERS <br />A.IN OTHER PART 2 ARTICLES WHERE TITLES BELOW INTRODUCE LISTS, THE FOLLOWING <br />REQUIREMENTS APPLY TO PRODUCT SELECTION: <br />1.PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS <br />BY ONE OF THE MANUFACTURERS SPECIFIED. <br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND <br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01. <br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED <br />PRODUCT OR MANUFACTURER. <br />2.02 GENERAL REQUIREMENTS FOR LIGHTING FIXTURES AND COMPONENTS <br />A.RECESSED FIXTURES: COMPLY WITH NEMA LE 4 FOR CEILING COMPATIBILITY FOR <br />RECESSED FIXTURES. <br />B.METAL PARTS: FREE OF BURRS AND SHARP CORNERS AND EDGES. <br />C.SHEET METAL COMPONENTS: STEEL UNLESS OTHERWISE INDICATED. FORM AND <br />SUPPORT TO PREVENT WARPING AND SAGGING. <br />D.DOORS, FRAMES, AND OTHER INTERNAL ACCESS: SMOOTH OPERATING, FREE OF LIGHT <br />LEAKAGE UNDER OPERATING CONDITIONS, AND DESIGNED TO PERMIT ACCESS TO <br />COMPONENTS WITHOUT USE OF TOOLS. DESIGNED TO PREVENT DOORS, FRAMES, <br />LENSES, DIFFUSERS, AND OTHER COMPONENTS FROM FALLING ACCIDENTALLY WHEN <br />SECURED IN OPERATING POSITION. <br />E.DIFFUSERS AND GLOBES: <br />1.ACRYLIC LIGHTING DIFFUSERS: 100 PERCENT VIRGIN ACRYLIC PLASTIC. HIGH <br />RESISTANCE TO YELLOWING AND OTHER CHANGES DUE TO AGING, EXPOSURE TO <br />HEAT, AND UV RADIATION. <br />a.LENS THICKNESS: ⅛ INCH, MINIMUM, UNLESS OTHERWISE INDICATED. <br />b.UV STABILIZED. <br />2.GLASS: ANNEALED CRYSTAL GLASS UNLESS OTHERWISE INDICATED. <br />2.03 SOLID STATE LIGHTING LUMINAIRES <br />A.PROVIDE LUMINAIRES AS INDICATED IN LIGHTING FIXTURE SCHEDULE OR DETAILS ON <br />PROJECT PLANS. PROVIDE LUMINAIRES COMPLETE WITH LIGHT SOURCES OF QUANTITY, <br />TYPE, AND WATTAGE INDICATED. LUMINAIRES OF THE SAME TYPE SHALL BE PROVIDED <br />BY THE SAME MANUFACTURER. <br />B.GENERAL REQUIREMENTS <br />1.SSL LUMINAIRE HOUSINGS SHALL BE DIE CAST OR EXTRUDED ALUMINUM <br />2.SSL LUMINAIRES SHALL BE RATED FOR OPERATION WITHIN AN AMBIENT <br />TEMPERATURE RANGE OF MINUS 22 DEGREES F TO 104°F. <br />3.LUMINAIRES SHALL BE UL LISTED FOR WET LOCATIONS PER UL 1598 IF INDICATED. <br />4.SSL LUMINAIRES SHALL PRODUCE A MINIMUM EFFICACY AS SHOWN IN SCHEDULE OR <br />SPECIFIED, TESTED PER IES LM-79. THEORETICAL MODELS OF INITIAL RAW LED <br />LUMENS PER WATT ARE NOT ACCEPTABLE. <br />5.LUMINAIRES SHALL HAVE IES DISTRIBUTION AND NEMA FIELD ANGLE <br />CLASSIFICATIONS AS INDICATED IN LUMINAIRE SCHEDULE ON PROJECT PLANS PER <br />IES HB-10. <br />6.HOUSING FINISH SHALL BE BAKED-ON ENAMEL, ANODIZED, OR BAKED-ON POWDER <br />COAT PAINT. <br />7.LUMINAIRES SHALL BE FULLY ASSEMBLED AND ELECTRICALLY TESTED PRIOR TO <br />SHIPMENT FROM FACTORY. <br />8.THE FINISH COLOR SHALL BE AS INDICATED IN THE LUMINAIRE SCHEDULE OR DETAIL <br />ON THE PROJECT PLANS. <br />9.LUMINAIRES SHALL HAVE A NAMEPLATE BEARING THE MANUFACTURER'S NAME, <br />ADDRESS, MODEL NUMBER, DATE OF MANUFACTURE, AND SERIAL NUMBER <br />SECURELY AFFIXED IN A CONSPICUOUS PLACE. THE NAMEPLATE OF THE <br />DISTRIBUTING AGENT WILL NOT BE ACCEPTABLE. <br />C.LED LIGHT SOURCES <br />1.CCT SHALL BE IN ACCORDANCE WITH NEMA ANSLG C78.377: NOMINAL CCT: 3,500 <br />DEGREES K. <br />2.CRI SHALL BE: GREATER THAN OR EQUAL TO 90 FOR 3,500 DEGREES K LIGHT <br />SOURCES. <br />3.COLOR CONSISTENCY: MANUFACTURER SHALL USE A MAXIMUM 4-STEP MACADAM <br />ELLIPSE BINNING TOLERANCE FOR COLOR CONSISTENCY OF LEDS USED IN <br />LUMINAIRES. <br />D.LED DRIVERS SHALL MEET UL 1310 AND THE FOLLOWING REQUIREMENTS: <br />1.MINIMUM EFFICIENCY SHALL BE 85 PERCENT. <br />2.DRIVE CURRENT TO EACH INDIVIDUAL LED SHALL NOT EXCEED 600 MA, PLUS OR <br />MINUS 10 PERCENT. <br />3.SHALL BE RATED TO OPERATE BETWEEN AMBIENT TEMPERATURES OF MINUS 22°F <br />AND 104°F <br />4.SHALL BE DESIGNED TO OPERATE ON THE VOLTAGE SYSTEM TO WHICH THEY ARE <br />CONNECTED, TYPICALLY RANGING FROM 120 V TO 480 V NOMINAL. <br />5.OPERATING FREQUENCY SHALL BE: 60 HZ. <br />6.POWER FACTOR (PF) SHALL BE GREATER THAN OR EQUAL TO 0.90. <br />7.TOTAL HARMONIC DISTORTION (THD) CURRENT SHALL BE LESS THAN OR EQUAL TO <br />20 PERCENT. <br />8.SHALL MEET REQUIREMENTS OF 47 CFR 15, CLASS B. <br />9.SHALL BE ROHS-COMPLIANT. <br />10.SHALL BE MOUNTED INTEGRAL TO LUMINAIRE. REMOTE MOUNTING OF POWER <br />SUPPLY IS NOT ALLOWED. <br />11.DRIVERS WHERE APPROPRIATE SHALL BE UL LISTED WITH A SOUND RATING OF A. <br />12.SHALL BE DIMMABLE WHERE INDICATED, AND COMPATIBLE WITH A STANDARD <br />DIMMING CONTROL CIRCUIT OF 0 - 10V OR OTHER APPROVED DIMMING SYSTEM. <br />13.SHALL BE EQUIPPED WITH OVER-TEMPERATURE PROTECTION CIRCUIT THAT TURNS <br />LIGHT SOURCE OFF UNTIL NORMAL OPERATING TEMPERATURE IS ACHIEVED. <br />E.LED LUMINAIRE SURGE PROTECTION <br />1.PROVIDE SURGE PROTECTION INTEGRAL TO LUMINAIRE TO MEET C LOW <br />WAVEFORMS AS DEFINED BY IEEE C62.41.2, SCENARIO 1, AND LOCATION CATEGORY <br />C. <br />2.04 LIGHTING FIXTURE SUPPORT COMPONENTS <br />A.COMPLY WITH CALIFORNIA BUILDING CODE FOR CHANNEL- AND ANGLE-IRON SUPPORTS <br />AND NONMETALLIC CHANNEL AND ANGLE SUPPORTS. <br />B.SINGLE-STEM HANGERS: ½-INCH STEEL TUBING WITH SWIVEL BALL FITTINGS AND <br />CEILING CANOPY. FINISH SAME AS FIXTURE. <br />C.TWIN-STEM HANGERS: TWO, ½-INCH STEEL TUBES WITH SINGLE CANOPY DESIGNED TO <br />MOUNT A SINGLE FIXTURE. FINISH SAME AS FIXTURE. <br />D.WIRES: ASTM A641, CLASS 3, SOFT TEMPER, ZINC-COATED STEEL, 12 GAUGE SIZE. <br />E.WIRES FOR HUMID SPACES: ASTM A 580/A 580M, COMPOSITION 302 OR 304, ANNEALED <br />STAINLESS STEEL, 12 GAUGE. <br />F.ROD HANGERS: 3/16-INCH MINIMUM DIAMETER, CADMIUM-PLATED, THREADED STEEL <br />ROD. <br />G.HOOK HANGERS: INTEGRATED ASSEMBLY MATCHED TO FIXTURE AND LINE VOLTAGE <br />AND EQUIPPED WITH THREADED ATTACHMENT, CORD, AND LOCKING-TYPE PLUG. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A.LIGHTING FIXTURES: <br />1.SET LEVEL, PLUMB, AND SQUARE WITH CEILINGS AND WALLS UNLESS OTHERWISE <br />INDICATED. <br />2.INSTALL DIODES IN EACH LUMINAIRE. <br />B.TEMPORARY LIGHTING: IF IT IS NECESSARY, AND APPROVED BY OWNER'S <br />REPRESENTATIVE, TO USE PERMANENT LUMINAIRES FOR TEMPORARY LIGHTING, <br />INSTALL AND ENERGIZE THE MINIMUM NUMBER OF LUMINAIRES NECESSARY. WHEN <br />CONSTRUCTION IS SUFFICIENTLY COMPLETE, DISASSEMBLE LUMINAIRES USED DURING <br />CONSTRUCTION, AND CLEAN THOROUGHLY. <br />C.LAY-IN CEILING LIGHTING FIXTURES SUPPORTS: USE GRID AS A SUPPORT ELEMENT. <br />1.INSTALL CEILING SUPPORT SYSTEM RODS OR WIRES, INDEPENDENT OF THE CEILING <br />SUSPENSION DEVICES, FOR EACH FIXTURE. LOCATE NOT MORE THAN 6 INCHES <br />FROM LIGHTING FIXTURE CORNERS. <br />2.SUPPORT CLIPS: FASTEN TO LIGHTING FIXTURES AND TO CEILING GRID MEMBERS AT <br />OR NEAR EACH FIXTURE CORNER WITH CLIPS THAT ARE UL LISTED FOR THE <br />APPLICATION. <br />3.FIXTURES OF SIZES LESS THAN CEILING GRID: INSTALL AS INDICATED ON REFLECTED <br />CEILING PLANS OR CENTER IN ACOUSTICAL PANEL, AND SUPPORT FIXTURES <br />INDEPENDENTLY WITH AT LEAST TWO 3/4-INCH METAL CHANNELS SPANNING AND <br />SECURED TO CEILING TEES. <br />4.INSTALL AT LEAST ONE INDEPENDENT SUPPORT ROD OR WIRE FROM STRUCTURE TO <br />A TAB ON LIGHTING FIXTURE. WIRE OR ROD SHALL HAVE BREAKING STRENGTH OF <br />THE WEIGHT OF FIXTURE AT A SAFETY FACTOR OF 3. <br />D.SUSPENDED LIGHTING FIXTURE SUPPORT: <br />1.PENDANTS AND RODS: WHERE LONGER THAN 48 INCHES, BRACE TO LIMIT SWINGING. <br />2.STEM-MOUNTED, SINGLE-UNIT FIXTURES: SUSPEND WITH TWIN-STEM HANGERS. <br />3.CONTINUOUS ROWS: USE TUBING OR STEM FOR WIRING AT ONE POINT AND TUBING <br />OR ROD FOR SUSPENSION FOR EACH UNIT LENGTH OF FIXTURE CHASSIS, INCLUDING <br />ONE AT EACH END. <br />4.DO NOT USE GRID AS SUPPORT FOR PENDANT LUMINAIRES. CONNECT SUPPORT <br />WIRES OR RODS TO BUILDING STRUCTURE. <br />E.CONNECT WIRING IN ACCORDANCE WITH CALIFORNIA ELECTRIC CODE. <br />3.02 FIELD QUALITY CONTROL <br />A.TEST FOR EMERGENCY LIGHTING: INTERRUPT POWER SUPPLY TO DEMONSTRATE <br />PROPER OPERATION. VERIFY TRANSFER FROM NORMAL POWER TO EMERGENCY <br />POWER AND RETRANSFER TO NORMAL. <br />B.PREPARE A WRITTEN REPORT OF TESTS, INSPECTIONS, OBSERVATIONS, AND <br />VERIFICATIONS INDICATING AND INTERPRETING RESULTS. IF ADJUSTMENTS ARE MADE <br />TO LIGHTING SYSTEM, RETEST TO DEMONSTRATE COMPLIANCE WITH STANDARDS. <br />3.03 HAZARDOUS LAMP DISPOSAL <br />A.HAZARDOUS LAMPS SHALL BE REMOVED FROM FIXTURES AND DISPOSED PER CITY <br />REQUIREMENTS. <br />B.COMPLY WITH ADDITIONAL INFORMATION AT THE CITY WEBSITE FOR CONSTRUCTION <br />RELATED HAZARDOUS WASTE GUIDELINES. <br />C.AS A CONTRACTOR OPTION, BOX UP AND TRANSPORT THE HAZARDOUS LAMPS TO THE <br />CITY'S HAZARDOUS WASTE FACILITY. <br />SECTION 26 0563 <br />ELECTRICAL TESTING <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES GENERAL REQUIREMENTS FOR ELECTRICAL FIELD TESTING AND <br />INSPECTING. DETAILED REQUIREMENTS ARE SPECIFIED IN EACH SECTION CONTAINING <br />COMPONENTS THAT REQUIRE TESTING. GENERAL REQUIREMENTS INCLUDE THE <br />FOLLOWING: <br />1.QUALIFICATIONS OF TESTING AGENCIES AND THEIR PERSONNEL. <br />2.SUITABILITY OF TEST EQUIPMENT. <br />3.CALIBRATION OF TEST INSTRUMENTS. <br />4.COORDINATION REQUIREMENTS FOR TESTING AND INSPECTING. <br />5.REPORTING REQUIREMENTS FOR TESTING AND INSPECTING. <br />1.02 QUALITY ASSURANCE <br />A.TESTING AGENCY QUALIFICATIONS: AS SPECIFIED IN EACH SECTION CONTAINING <br />ELECTRICAL TESTING REQUIREMENTS AND IN SUBPARAGRAPH AND ASSOCIATED <br />SUBPARAGRAPH BELOW. <br />1.INDEPENDENT TESTING AGENCIES: INDEPENDENT OF MANUFACTURERS, SUPPLIERS, <br />AND INSTALLERS OF COMPONENTS TO BE TESTED OR INSPECTED. <br />a.TESTING AGENCY'S FIELD SUPERVISOR FOR POWER COMPONENT TESTING: <br />PERSON CURRENTLY CERTIFIED BY THE INTERNATIONAL ELECTRICAL TESTING <br />ASSOCIATION OR THE NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING <br />TECHNOLOGIES TO SUPERVISE ON-SITE TESTING SPECIFIED IN DIVISION 26 <br />POWER COMPONENT SECTIONS. <br />B.TEST EQUIPMENT SUITABILITY: COMPLY WITH NETA ATS, SECTION 5.2. <br />C.TEST EQUIPMENT CALIBRATION: COMPLY WITH NETA ATS, SECTION 5.3. <br />PART 2 - NOT USED <br />PART 3 - EXECUTION <br />3.01 GENERAL TESTS AND INSPECTIONS <br />A.IF A GROUP OF TESTS ARE SPECIFIED TO BE PERFORMED BY AN INDEPENDENT TESTING <br />AGENCY, PREPARE SYSTEMS, EQUIPMENT, AND COMPONENTS FOR TESTS AND <br />INSPECTIONS, AND PERFORM PRELIMINARY TESTS TO ENSURE THAT SYSTEMS, <br />EQUIPMENT, AND COMPONENTS ARE READY FOR INDEPENDENT AGENCY TESTING. <br />INCLUDE THE FOLLOWING MINIMUM PREPARATIONS AS APPROPRIATE: <br />1.PERFORM INSULATION-RESISTANCE TESTS. <br />2.PERFORM CONTINUITY TESTS. <br />3.PERFORM ROTATION TEST (FOR MOTORS TO BE TESTED). <br />4.PROVIDE A STABLE SOURCE OF SINGLE-PHASE, 208/120-V ELECTRICAL POWER FOR <br />TEST INSTRUMENTATION AT EACH TEST LOCATION. <br />B.TEST AND INSPECTION REPORTS: IN ADDITION TO REQUIREMENTS SPECIFIED <br />ELSEWHERE, REPORT THE FOLLOWING: <br />1.MANUFACTURER'S WRITTEN TESTING AND INSPECTING INSTRUCTIONS. <br />2.CALIBRATION AND ADJUSTMENT SETTINGS OF ADJUSTABLE AND INTERCHANGEABLE <br />DEVICES INVOLVED IN TESTS. <br />3.TABULATION OF EXPECTED MEASUREMENT RESULTS MADE BEFORE <br />MEASUREMENTS. <br />4.TABULATION OF "AS-FOUND" AND "AS-LEFT" MEASUREMENT AND OBSERVATION <br />RESULTS. <br />Sheet No. <br />Project <br />Agency Plan Check / Permit No. <br />Petersen Design Project No. <br />Consultant <br />5082.1 <br />652 East Dyer Drive <br />Santa Ana, CA 92705 <br />DYER WAREHOUSE <br />Staging & Set-Up Space <br />Tenant Improvements <br />Sheet Title <br />Revision / Submittal History <br />Scale <br />Status <br />. <br />architecture + planning <br />Agency Approval <br />Petersen Design Architects, Inc. <br />17582 Fiesta Way, Tustin, CA 92780 <br />M: 714.904.6720 E: mike@mpdarch.com <br />www.mpdarch.com <br />Architect's Stamp <br />. <br />255 E. Rincon St., Suite 301 <br />Corona, CA 92879 <br />P 951.340.1977 | F 951.340.1090 <br />www.gossengineering.com <br />CALOFI <br />GI <br />RE <br />NG <br />A <br />E <br />S <br />No. E17083 <br />T <br />E <br />ET <br />SAT L CE A <br />F <br />RIC L <br />ORNI <br />EPR <br />RAET <br />RED D.D <br />OF ONABR <br />L <br />SSI <br />NE <br />RE <br />IWD <br />UT <br />HCE <br />Project Number: 125-09-07 <br />Date Signed 01-09-2026 <br />1 01/09/2026 PLAN CHECK RESUBMITTAL <br />ELECTRICAL <br />SPECIFICATIONS <br />E7.3