SECTION 26 2416
<br />PANELBOARDS
<br />PART 1 - GENERAL
<br />1.01 SUMMARY
<br />A.SECTION INCLUDES LOAD CENTERS AND PANELBOARDS, OVERCURRENT PROTECTIVE
<br />DEVICES, AND ASSOCIATED AUXILIARY EQUIPMENT RATED 600 V AND LESS FOR THE
<br />FOLLOWING TYPES:
<br />1.LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS.
<br />2.DISTRIBUTION PANELBOARDS.
<br />3.TRANSIENT VOLTAGE SURGE SUPPRESSOR PANELBOARDS.
<br />1.02 DEFINITIONS
<br />A.EMI: ELECTROMAGNETIC INTERFERENCE.
<br />B.GFCI: GROUND-FAULT CIRCUIT INTERRUPTER. FI: RADIO-FREQUENCY INTERFERENCE.
<br />C.RMS: ROOT MEAN SQUARE.
<br />D.SPDT: SINGLE POLE, DOUBLE THROW.
<br />E.TVSS: TRANSIENT VOLTAGE SURGE SUPPRESSOR.
<br />1.03 SUBMITTALS
<br />A.PRODUCT DATA: FOR EACH TYPE OF PANELBOARD, OVERCURRENT PROTECTIVE
<br />DEVICE, AND COMPONENT INDICATED. INCLUDE DIMENSIONS AND MANUFACTURERS'
<br />TECHNICAL DATA ON FEATURES, PERFORMANCE, ELECTRICAL CHARACTERISTICS,
<br />RATINGS, AND FINISHES.
<br />B.SHOP DRAWINGS: FOR EACH PANELBOARD AND RELATED EQUIPMENT.
<br />1.DIMENSIONED PLANS, ELEVATIONS, SECTIONS, AND DETAILS. SHOW TABULATIONS
<br />OF INSTALLED DEVICES, EQUIPMENT FEATURES, AND RATINGS. INCLUDE THE
<br />FOLLOWING:
<br />a.ENCLOSURE TYPES AND DETAILS FOR TYPES OTHER THAN NEMA 250, TYPE 1.
<br />b.BUS CONFIGURATION, CURRENT, AND VOLTAGE RATINGS.
<br />c.SHORT-CIRCUIT CURRENT RATING OF PANELBOARDS AND OVERCURRENT
<br />PROTECTIVE DEVICES.
<br />d.FEATURES, CHARACTERISTICS, RATINGS, AND FACTORY SETTINGS OF INDIVIDUAL
<br />OVERCURRENT PROTECTIVE DEVICES AND AUXILIARY COMPONENTS.
<br />2.WIRING DIAGRAMS: DIAGRAM POWER, SIGNAL, AND CONTROL WIRING AND
<br />DIFFERENTIATE BETWEEN MANUFACTURER-INSTALLED AND FIELD-INSTALLED
<br />WIRING.
<br />C.MANUFACTURER SEISMIC QUALIFICATION CERTIFICATION: SUBMIT CERTIFICATION THAT
<br />PANELBOARDS, OVERCURRENT PROTECTIVE DEVICES, ACCESSORIES, AND
<br />COMPONENTS WILL WITHSTAND SEISMIC FORCES DEFINED IN DIVISION 26 SECTION
<br />"VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL WORK." INCLUDE THE
<br />FOLLOWING:
<br />1.BASIS OF CERTIFICATION: INDICATE WHETHER WITHSTAND CERTIFICATION IS BASED
<br />ON ACTUAL TEST OF ASSEMBLED COMPONENTS OR ON CALCULATION.
<br />2.THE TERM "WITHSTAND" MEANS "THE UNIT WILL REMAIN IN PLACE WITHOUT
<br />SEPARATION OF INTERNAL AND EXTERNAL PARTS DURING A SEISMIC EVENT AND THE
<br />UNIT WILL BE FULLY OPERATIONAL AFTER THE EVENT."
<br />3.DIMENSIONED OUTLINE DRAWINGS OF EQUIPMENT UNIT: IDENTIFY CENTER OF
<br />GRAVITY AND LOCATE AND DESCRIBE MOUNTING AND ANCHORAGE PROVISIONS.
<br />4.DETAILED DESCRIPTION OF EQUIPMENT ANCHORAGE DEVICES ON WHICH THE
<br />CERTIFICATION IS BASED AND THEIR INSTALLATION REQUIREMENTS.
<br />D.FIELD TEST REPORTS: SUBMIT WRITTEN TEST REPORTS AND INCLUDE THE FOLLOWING:
<br />1.TEST PROCEDURES USED.
<br />2.TEST RESULTS THAT COMPLY WITH REQUIREMENTS.
<br />3.RESULTS OF FAILED TESTS AND CORRECTIVE ACTION TAKEN TO ACHIEVE TEST
<br />RESULTS THAT COMPLY WITH REQUIREMENTS.
<br />E.PANELBOARD SCHEDULES: FOR INSTALLATION IN PANELBOARDS. SUBMIT FINAL
<br />VERSIONS AFTER LOAD BALANCING.
<br />F.MAINTENANCE DATA: FOR PANELBOARDS AND COMPONENTS TO INCLUDE IN
<br />MAINTENANCE MANUALS SPECIFIED IN DIVISION 01. IN ADDITION TO REQUIREMENTS
<br />SPECIFIED IN DIVISION 01 INCLUDE THE FOLLOWING:
<br />1.MANUFACTURER'S WRITTEN INSTRUCTIONS FOR TESTING AND ADJUSTING
<br />OVERCURRENT PROTECTIVE DEVICES.
<br />2.TIME-CURRENT CURVES, INCLUDING SELECTABLE RANGES FOR EACH TYPE OF
<br />OVERCURRENT PROTECTIVE DEVICE.
<br />1.04 QUALITY ASSURANCE
<br />A.TESTING AGENCY QUALIFICATIONS: TESTING AGENCY THAT IS A MEMBER COMPANY OF
<br />THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION AND THAT IS ACCEPTABLE TO
<br />AUTHORITIES HAVING JURISDICTION.
<br />1.TESTING AGENCY'S FIELD SUPERVISOR: PERSON CURRENTLY CERTIFIED BY THE
<br />INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR NATIONAL INSTITUTE FOR
<br />CERTIFICATION IN ENGINEERING TECHNOLOGIES TO SUPERVISE ON-SITE TESTING
<br />SPECIFIED IN PART 3.
<br />B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS
<br />DEFINED IN CEC, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO THE OWNER, AND
<br />MARKED FOR INTENDED USE.
<br />C.COMPLY WITH NEMA PB 1.
<br />D.COMPLY WITH CEC.
<br />E.STRUCTURAL SEISMIC PERFORMANCE: REFER TO DIVISION 26 SECTION “VIBRATION AND
<br />SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.”
<br />1.05 COORDINATION
<br />A.COORDINATE LAYOUT AND INSTALLATION OF PANELBOARDS AND COMPONENTS WITH
<br />OTHER CONSTRUCTION THAT PENETRATES WALLS OR IS SUPPORTED BY THEM,
<br />INCLUDING ELECTRICAL AND OTHER TYPES OF EQUIPMENT, RACEWAYS, PIPING, AND
<br />ENCUMBRANCES TO WORKSPACE CLEARANCE REQUIREMENTS.
<br />1.06 EXTRA MATERIALS
<br />A.KEYS: TWO SPARES OF EACH TYPE OF PANELBOARD CABINET LOCK, KEYED ALIKE TO
<br />MATCH THE OWNER'S STANDARD KEY REQUIREMENTS.
<br />PART 2 - PRODUCTS
<br />2.01 MANUFACTURERS
<br />A.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE
<br />PRODUCTS BY ONE OF THE FOLLOWING:
<br />1.PANELBOARDS, OVERCURRENT PROTECTIVE DEVICES, CONTROLLERS,
<br />CONTACTORS, AND ACCESSORIES:
<br />a.EATON CORP.; CUTLER-HAMMER PRODUCTS.
<br />b.GENERAL ELECTRIC CO.; ELECTRICAL DISTRIBUTION & CONTROL DIV.
<br />c.SIEMENS ENERGY & AUTOMATION, INC.
<br />d.SQUARE-D CO.
<br />e.OR EQUAL.
<br />2.TVSS PANELBOARDS:
<br />a.CURRENT TECHNOLOGY, INC.
<br />b.OR EQUAL.
<br />B.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND
<br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01
<br />SECTION “PRODUCT OPTIONS AND SUBSTITUTIONS”. SPECIFIC PROCEDURES MUST BE
<br />FOLLOWED BEFORE USE OF AN UNNAMED PRODUCT OR MANUFACTURER.
<br />2.02 FABRICATION AND FEATURES
<br />A.ENCLOSURES: FLUSH- AND SURFACE-MOUNTED CABINETS. NEMA PB 1, TYPE 1, TO MEET
<br />ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION.
<br />1.OUTDOOR LOCATIONS: NEMA 250, TYPE 4 STAINLESS STEEL.
<br />2.KITCHEN AREAS: NEMA 250, TYPE 4X, STAINLESS STEEL.
<br />3.OTHER WET OR DAMP INDOOR LOCATIONS: NEMA 250, TYPE 4.
<br />4.HAZARDOUS AREAS INDICATED ON DRAWINGS: NEMA 250, TYPE 7C.
<br />B.HINGED FRONT COVER: ENTIRE FRONT TRIM HINGED TO BOX AND WITH STANDARD
<br />DOOR WITHIN HINGED TRIM COVER.
<br />C.FINISH: MANUFACTURER'S STANDARD ENAMEL FINISH OVER CORROSION-RESISTANT
<br />TREATMENT OR PRIMER COAT.
<br />D.DIRECTORY CARD: TYPED PANEL CIRCUIT SCHEDULE/INDEX WITH TRANSPARENT
<br />PROTECTIVE COVER, MOUNTED INSIDE METAL FRAME, INSIDE PANELBOARD DOOR.
<br />E.BUS: HARD-DRAWN COPPER, 98 PERCENT CONDUCTIVITY.
<br />F.MAIN AND NEUTRAL LUGS: COMPRESSION TYPE SUITABLE FOR USE WITH CONDUCTOR
<br />MATERIAL.
<br />G.EQUIPMENT GROUND BUS: ADEQUATE FOR FEEDER AND BRANCH-CIRCUIT EQUIPMENT
<br />GROUND CONDUCTORS; BONDED TO BOX. WHEN ISOLATED GROUNDS ARE REQUIRED,
<br />PROVIDE GROUND BUS INSULATED FROM BOX.
<br />H.FUTURE DEVICES: MOUNTING BRACKETS, BUS CONNECTIONS, AND NECESSARY
<br />APPURTENANCES REQUIRED FOR FUTURE INSTALLATION OF DEVICES.
<br />I.ISOLATED EQUIPMENT GROUND BUS: ADEQUATE FOR BRANCH-CIRCUIT EQUIPMENT
<br />GROUND CONDUCTORS; INSULATED FROM BOX.
<br />J.EXTRA-CAPACITY NEUTRAL BUS: NEUTRAL BUS RATED 200 PERCENT OF PHASE BUS AND
<br />UL LISTED AS SUITABLE FOR NONLINEAR LOADS.
<br />K.SPLIT BUS: VERTICAL BUSES DIVIDED INTO INDIVIDUAL VERTICAL SECTIONS.
<br />L.GUTTER BARRIER: ARRANGE TO ISOLATE INDIVIDUAL PANEL SECTIONS.
<br />M.COLUMN-TYPE PANELBOARDS: NARROW GUTTER EXTENSION, WITH COVER, TO
<br />OVERHEAD JUNCTION BOX EQUIPPED WITH GROUND AND NEUTRAL TERMINAL BUSES.
<br />2.03 PANELBOARD SHORT-CIRCUIT RATING
<br />A.UL LABEL INDICATING SERIES-CONNECTED RATING WITH INTEGRAL OR REMOTE
<br />UPSTREAM DEVICES. INCLUDE SIZE AND TYPE OF UPSTREAM DEVICE ALLOWABLE,
<br />BRANCH DEVICES ALLOWABLE, AND UL SERIES-CONNECTED SHORT-CIRCUIT RATING.
<br />B.FULLY RATED TO INTERRUPT SYMMETRICAL SHORT-CIRCUIT CURRENT AVAILABLE AT
<br />TERMINALS.
<br />2.04 LIGHTING AND APPLIANCE BRANCH-CIRCUIT PANELBOARDS
<br />A.BRANCH OVERCURRENT PROTECTIVE DEVICES: BOLT-ON CIRCUIT BREAKERS,
<br />REPLACEABLE WITHOUT DISTURBING ADJACENT UNITS.
<br />B.DOORS: FRONT MOUNTED WITH CONCEALED HINGES; SECURED WITH FLUSH LATCH
<br />WITH TUMBLER LOCK; KEYED ALIKE.
<br />2.05 DISTRIBUTION PANELBOARDS
<br />C.DOORS: FRONT MOUNTED, EXCEPT OMIT IN FUSED-SWITCH PANELBOARDS; SECURED
<br />WITH VAULT-TYPE LATCH WITH TUMBLER LOCK; KEYED ALIKE.
<br />D.MAIN OVERCURRENT PROTECTIVE DEVICES: CIRCUIT BREAKER.
<br />E.BRANCH OVERCURRENT PROTECTIVE DEVICES SHALL BE ONE OF THE FOLLOWING:
<br />1.FOR CIRCUIT-BREAKER FRAME SIZES 125 A AND SMALLER: BOLT-ON CIRCUIT
<br />BREAKERS WITH COPPER TERMINALS.
<br />2.FOR CIRCUIT-BREAKER FRAME SIZES LARGER THAN 125 A: BOLT-ON CIRCUIT
<br />BREAKERS WITH COPPER TERMINALS; PLUG-IN CIRCUIT BREAKERS WHERE
<br />INDIVIDUAL POSITIVE-LOCKING DEVICE REQUIRES MECHANICAL RELEASE FOR
<br />REMOVAL.
<br />3.FUSED SWITCHES.
<br />2.06 TVSS PANELBOARDS
<br />A.DOORS: FRONT MOUNTED; SECURED WITH VAULT-TYPE LATCH WITH TUMBLER LOCK;
<br />KEYED ALIKE. MANUFACTURER'S STANDARD ENAMEL FINISH OVER
<br />CORROSION-RESISTANT TREATMENT OR PRIMER COAT.
<br />B.MAIN OVERCURRENT DEVICES: THERMAL-MAGNETIC CIRCUIT BREAKER WITH COPPER
<br />TERMINALS.
<br />C.BRANCH OVERCURRENT PROTECTIVE DEVICES: BOLT-ON CIRCUIT BREAKERS WITH
<br />COPPER TERMINALS.
<br />D.BUS: COPPER PHASE AND NEUTRAL BUSES; 200 PERCENT CAPACITY NEUTRAL BUS.
<br />E.TVSS DEVICE: IEEE C62.41, INTEGRALLY MOUNTED, PLUG-IN-STYLE, SOLID-STATE,
<br />PARALLEL-CONNECTED, SINE-WAVE TRACKING SUPPRESSION AND FILTERING MODULES.
<br />1.MINIMUM SINGLE-IMPULSE CURRENT RATING SHALL BE AS FOLLOWS:
<br />a.LINE TO NEUTRAL: 100,000 A.
<br />b.LINE TO GROUND: 100,000 A.
<br />c.NEUTRAL TO GROUND: 50,000 A.
<br />2.PROTECTION MODES SHALL BE AS FOLLOWS:
<br />a.LINE TO NEUTRAL.
<br />b.LINE TO GROUND.
<br />c.NEUTRAL TO GROUND.
<br />3.EMI/RFI NOISE ATTENUATION USING 50-OHM INSERTION LOSS TEST: 55 DB AT 100
<br />KHZ.
<br />4.CATEGORY C COMBINATION WAVE CLAMPING VOLTAGE SHALL NOT EXCEED 600 V,
<br />LINE TO NEUTRAL AND LINE TO GROUND ON 120/208 V SYSTEMS OR 1000 V, LINE TO
<br />NEUTRAL AND LINE TO GROUND ON 277/480 V SYSTEMS.
<br />5.UL 1449 CLAMPING LEVELS SHALL NOT EXCEED 400 V, LINE TO NEUTRAL AND LINE TO
<br />GROUND ON 120/208 V SYSTEMS OR 800 V, LINE TO NEUTRAL AND LINE TO GROUND
<br />ON 277/480 V SYSTEMS.
<br />6.WITHSTAND CAPABILITIES: 3000 CATEGORY C SURGES WITH LESS THAN 5 PERCENT
<br />CHANGE IN CLAMPING VOLTAGE.
<br />7.ACCESSORIES SHALL INCLUDE THE FOLLOWING:
<br />a.FORM-C CONTACTS, ONE NORMALLY OPEN AND ONE NORMALLY CLOSED, FOR
<br />REMOTE MONITORING OF SYSTEM OPERATION. CONTACTS TO REVERSE
<br />POSITION ON FAILURE OF ANY SURGE DIVERSION MODULE.
<br />b.AUDIBLE ALARM ACTIVATED ON FAILURE OF ANY SURGE DIVERSION MODULE.
<br />c.SIX-DIGIT TRANSIENT-COUNTER SET TO TOTAL TRANSIENT SURGES THAT
<br />DEVIATE FROM THE SINE-WAVE ENVELOPE BY MORE THAN 125 V.
<br />2.07 OVERCURRENT PROTECTIVE DEVICES
<br />A.MOLDED-CASE CIRCUIT BREAKER: NEMA AB 1, WITH INTERRUPTING CAPACITY TO MEET
<br />AVAILABLE FAULT CURRENTS.
<br />1.THERMAL-MAGNETIC CIRCUIT BREAKERS: INVERSE TIME-CURRENT ELEMENT FOR
<br />LOW-LEVEL OVERLOADS, AND INSTANTANEOUS MAGNETIC TRIP ELEMENT FOR
<br />SHORT CIRCUITS. ADJUSTABLE MAGNETIC TRIP SETTING FOR CIRCUIT-BREAKER
<br />FRAME SIZES 225 AMPERES AND LARGER.
<br />2.ADJUSTABLE INSTANTANEOUS-TRIP CIRCUIT BREAKERS: MAGNETIC TRIP ELEMENT
<br />WITH FRONT-MOUNTED, FIELD-ADJUSTABLE TRIP SETTING.
<br />3.ELECTRONIC TRIP UNIT CIRCUIT BREAKERS: RMS SENSING; FIELD-REPLACEABLE
<br />RATING PLUG; WITH THE FOLLOWING FIELD-ADJUSTABLE SETTINGS:
<br />a.INSTANTANEOUS TRIP.
<br />b.LONG- AND SHORT-TIME PICKUP LEVELS.
<br />c.LONG- AND SHORT-TIME TIME ADJUSTMENTS.
<br />d.GROUND-FAULT PICKUP LEVEL, TIME DELAY, AND I2T RESPONSE.
<br />4.CURRENT-LIMITING CIRCUIT BREAKERS: FRAME SIZES 400 A AND SMALLER;
<br />LET-THROUGH RATINGS LESS THAN NEMA FU 1, RK-5.
<br />5.INTEGRALLY FUSED CIRCUIT BREAKERS: THERMAL-MAGNETIC TRIP ELEMENT WITH
<br />INTEGRAL LIMITER-STYLE FUSE LISTED FOR USE WITH CIRCUIT BREAKER; TRIP
<br />ACTIVATION ON FUSE OPENING OR ON OPENING OF FUSE COMPARTMENT DOOR.
<br />6.GFCI CIRCUIT BREAKERS: SINGLE- AND TWO-POLE CONFIGURATIONS WITH 5 -MA
<br />TRIP SENSITIVITY.
<br />B.MOLDED-CASE CIRCUIT-BREAKER FEATURES AND ACCESSORIES. STANDARD FRAME
<br />SIZES, TRIP RATINGS, AND NUMBER OF POLES.
<br />1.LUGS: COMPRESSION STYLE COPPER, SUITABLE FOR NUMBER, SIZE, TRIP RATINGS,
<br />AND MATERIAL OF CONDUCTORS.
<br />2.APPLICATION LISTING: APPROPRIATE FOR APPLICATION; TYPE SWD FOR SWITCHING
<br />FLUORESCENT LIGHTING LOADS; TYPE HACR FOR HEATING, AIR-CONDITIONING, AND
<br />REFRIGERATING EQUIPMENT.
<br />3.GROUND-FAULT PROTECTION: INTEGRALLY MOUNTED RELAY AND TRIP UNIT WITH
<br />ADJUSTABLE PICKUP AND TIME-DELAY SETTINGS, PUSH-TO-TEST FEATURE, AND
<br />GROUND-FAULT INDICATOR.
<br />4.COMMUNICATION CAPABILITY: CIRCUIT-BREAKER-MOUNTED COMMUNICATION
<br />MODULE WITH FUNCTIONS AND FEATURES COMPATIBLE WITH POWER MONITORING
<br />AND CONTROL SYSTEM.
<br />5.SHUNT TRIP: 120-V TRIP COIL ENERGIZED FROM SEPARATE CIRCUIT, SET TO TRIP AT
<br />75 PERCENT OF RATED VOLTAGE.
<br />6.UNDER-VOLTAGE TRIP: SET TO OPERATE AT 35 TO 75 PERCENT OF RATED VOLTAGE
<br />WITHOUT INTENTIONAL TIME DELAY.
<br />7.AUXILIARY SWITCH: TWO SPDT SWITCHES WITH "A" AND "B" CONTACTS; "A"
<br />CONTACTS MIMIC CIRCUIT-BREAKER CONTACTS, "B" CONTACTS OPERATE IN
<br />REVERSE OF CIRCUIT-BREAKER CONTACTS.
<br />8.KEY INTERLOCK KIT: EXTERNALLY MOUNTED TO PROHIBIT CIRCUIT-BREAKER
<br />OPERATION; KEY SHALL BE REMOVABLE ONLY WHEN CIRCUIT BREAKER IS IN OFF
<br />POSITION.
<br />9.ZONE-SELECTIVE INTERLOCKING: INTEGRAL WITH ELECTRONIC TRIP UNIT; FOR
<br />INTERLOCKING GROUND-FAULT PROTECTION FUNCTION.
<br />C.FUSED SWITCH: NEMA KS 1, TYPE HD; CLIPS TO ACCOMMODATE SPECIFIED FUSES;
<br />LOCKABLE HANDLE.
<br />2.08 CONTROLLERS
<br />A.MOTOR CONTROLLERS: NEMA ICS 2, CLASS A COMBINATION CONTROLLER EQUIPPED
<br />FOR PANELBOARD MOUNTING AND INCLUDING THE FOLLOWING ACCESSORIES:
<br />1.INDIVIDUAL CONTROL-POWER TRANSFORMERS.
<br />2.FUSES FOR CONTROL-POWER TRANSFORMERS.
<br />3.BIMETALLIC-ELEMENT OVERLOAD RELAY.
<br />4.MELTING-ALLOY OVERLOAD RELAY.
<br />5.INDICATING LIGHTS.
<br />6.SEAL-IN CONTACT.
<br />7.2 CONVERTIBLE AUXILIARY CONTACTS.
<br />8.PUSH BUTTONS.
<br />9.SELECTOR SWITCHES.
<br />B.CONTACTORS: NEMA ICS 2, CLASS A COMBINATION CONTROLLER EQUIPPED FOR
<br />PANELBOARD MOUNTING AND INCLUDING THE FOLLOWING ACCESSORIES:
<br />1.INDIVIDUAL CONTROL-POWER TRANSFORMERS.
<br />2.FUSES FOR CONTROL-POWER TRANSFORMERS.
<br />3.INDICATING LIGHTS.
<br />4.SEAL-IN CONTACT.
<br />5.2 CONVERTIBLE AUXILIARY CONTACTS.
<br />6.PUSH BUTTONS.
<br />7.SELECTOR SWITCHES.
<br />C.CONTROLLER DISCONNECT SWITCHES: FUSED SWITCH AND INTERLOCKED WITH
<br />CONTROLLER.
<br />1.AUXILIARY CONTACTS: INTEGRAL WITH DISCONNECT SWITCHES TO DE-ENERGIZE
<br />EXTERNAL CONTROL-POWER SOURCE.
<br />D.CONTACTORS IN MAIN BUS: NEMA ICS 2, CLASS A, MECHANICALLY HELD
<br />GENERAL-PURPOSE CONTROLLER.
<br />1.CONTROL-POWER SOURCE: CONTROL-POWER TRANSFORMER, WITH FUSED
<br />PRIMARY AND SECONDARY TERMINALS, CONNECTED TO MAIN BUS AHEAD OF
<br />CONTACTOR CONNECTION.
<br />2.CONTROL-POWER SOURCE: 120-V BRANCH CIRCUIT.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION
<br />A.INSTALL PANELBOARDS AND ACCESSORIES IN ACCORDANCE WITH NEMA PB 1.1.
<br />B.COMPLY WITH MOUNTING AND ANCHORING REQUIREMENTS SPECIFIED IN DIVISION 26
<br />SECTION "VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL WORK."
<br />C.MOUNTING HEIGHTS: TOP OF TRIM 74 INCHES ABOVE FINISHED FLOOR, UNLESS
<br />OTHERWISE INDICATED.
<br />D.MOUNTING: PLUMB AND RIGID WITHOUT DISTORTION OF BOX. MOUNT RECESSED
<br />PANELBOARDS WITH FRONTS UNIFORMLY FLUSH WITH WALL FINISH.
<br />E.CIRCUIT DIRECTORY: CREATE A DIRECTORY TO INDICATE INSTALLED CIRCUIT LOADS
<br />AFTER BALANCING PANELBOARD LOADS. OBTAIN APPROVAL BEFORE INSTALLING. USE
<br />A COMPUTER OR TYPEWRITER TO CREATE DIRECTORY; HANDWRITTEN DIRECTORIES
<br />ARE NOT ACCEPTABLE.
<br />F.INSTALL FILLER PLATES IN UNUSED SPACES.
<br />G.PROVISION FOR FUTURE CIRCUITS AT FLUSH PANELBOARDS: STUB FOUR 1-INCH EMPTY
<br />CONDUITS FROM PANELBOARD INTO ACCESSIBLE CEILING SPACE OR SPACE
<br />DESIGNATED TO BE CEILING SPACE IN THE FUTURE. STUB FOUR 1-INCH EMPTY
<br />CONDUITS INTO RAISED FLOOR SPACE OR BELOW SLAB NOT ON GRADE.
<br />H.WIRING IN PANELBOARD GUTTERS: ARRANGE CONDUCTORS INTO GROUPS AND BUNDLE
<br />AND WRAP WITH WIRE TIES AFTER COMPLETING LOAD BALANCING.
<br />3.02 IDENTIFICATION
<br />A.IDENTIFY FIELD-INSTALLED CONDUCTORS, INTERCONNECTING WIRING, AND
<br />COMPONENTS; PROVIDE WARNING SIGNS AS SPECIFIED IN DIVISION 26 SECTION
<br />IDENTIFICATION FOR ELECTRICAL SYSTEMS.
<br />B.PANELBOARD NAMEPLATES: LABEL EACH PANELBOARD WITH LAMINATED-PLASTIC
<br />NAMEPLATE MOUNTED WITH CORROSION-RESISTANT SCREWS.
<br />3.03 CONNECTIONS
<br />A.INSTALL EQUIPMENT GROUNDING CONNECTIONS FOR PANELBOARDS WITH GROUND
<br />CONTINUITY TO MAIN ELECTRICAL GROUND BUS.
<br />B.TIGHTEN ELECTRICAL CONNECTORS AND TERMINALS IN ACCORDANCE WITH
<br />MANUFACTURER'S PUBLISHED TORQUE-TIGHTENING VALUES. IF MANUFACTURER'S
<br />TORQUE VALUES ARE NOT INDICATED, USE THOSE SPECIFIED IN UL 486A.
<br />3.04 FIELD QUALITY CONTROL
<br />A.PREPARE FOR ACCEPTANCE TESTS AS FOLLOWS:
<br />1.TEST INSULATION RESISTANCE FOR EACH PANELBOARD BUS, COMPONENT,
<br />CONNECTING SUPPLY, FEEDER, AND CONTROL CIRCUIT.
<br />2.TEST CONTINUITY OF EACH CIRCUIT.
<br />B.TESTING: AFTER INSTALLING PANELBOARDS AND AFTER ELECTRICAL CIRCUITRY HAS
<br />BEEN ENERGIZED, DEMONSTRATE PRODUCT CAPABILITY AND COMPLIANCE WITH
<br />REQUIREMENTS.
<br />1.PROCEDURES: PERFORM EACH VISUAL AND MECHANICAL INSPECTION AND
<br />ELECTRICAL TEST INDICATED IN NETA ATS, SECTION 7.5 FOR SWITCHES AND
<br />SECTION 7.6 FOR MOLDED-CASE CIRCUIT BREAKERS. CERTIFY COMPLIANCE WITH
<br />TEST PARAMETERS.
<br />2.CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE, AND RETEST TO
<br />DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RETEST.
<br />C.BALANCING LOADS: AFTER SUBSTANTIAL COMPLETION, BUT NOT MORE THAN 60 DAYS
<br />AFTER FINAL ACCEPTANCE, MEASURE LOAD BALANCING AND MAKE CIRCUIT CHANGES
<br />AS FOLLOWS:
<br />1.MEASURE AS DIRECTED DURING PERIOD OF NORMAL SYSTEM LOADING.
<br />2.PERFORM LOAD-BALANCING CIRCUIT CHANGES OUTSIDE NORMAL
<br />OCCUPANCY/WORKING SCHEDULE OF THE FACILITY AND AT TIME DIRECTED. AVOID
<br />DISRUPTING CRITICAL 24-HOUR SERVICES SUCH AS FAX MACHINES AND ON-LINE
<br />DATA-PROCESSING, COMPUTING, TRANSMITTING, AND RECEIVING EQUIPMENT.
<br />3.AFTER CIRCUIT CHANGES, RECHECK LOADS DURING NORMAL LOAD PERIOD.
<br />RECORD LOAD READINGS BEFORE AND AFTER CHANGES AND SUBMIT TEST
<br />RECORDS.
<br />4.TOLERANCE: DIFFERENCE EXCEEDING 20 PERCENT BETWEEN PHASE LOADS, WITHIN
<br />A PANELBOARD, IS NOT ACCEPTABLE. REBALANCE AND RECHECK AS NECESSARY TO
<br />MEET THIS MINIMUM REQUIREMENT.
<br />3.05 ADJUSTING
<br />A.SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES.
<br />3.06 CLEANING
<br />A.ON COMPLETION OF INSTALLATION, INSPECT INTERIOR AND EXTERIOR OF
<br />PANELBOARDS. REMOVE PAINT SPLATTERS AND OTHER SPOTS. VACUUM DIRT AND
<br />DEBRIS; DO NOT USE COMPRESSED AIR TO ASSIST IN CLEANING. REPAIR EXPOSED
<br />SURFACES TO MATCH ORIGINAL FINISH.
<br />SECTION 26 2816
<br />ENCLOSED SWITCHES AND CIRCUIT BREAKERS
<br />PART 1 - GENERAL
<br />1.01 SUMMARY
<br />A.SECTION INCLUDES THE FOLLOWING INDIVIDUALLY MOUNTED, ENCLOSED SWITCHES
<br />AND CIRCUIT BREAKERS:
<br />1.FUSIBLE SWITCHES.
<br />2.NONFUSIBLE SWITCHES.
<br />3.BOLTED-PRESSURE CONTACT SWITCHES.
<br />4.ENCLOSURES.
<br />1.02 DEFINITIONS
<br />A.HD: HEAVY DUTY.
<br />1.03 SUBMITTALS
<br />A.PRODUCT DATA: FOR EACH TYPE OF ENCLOSED SWITCH, CIRCUIT BREAKER,
<br />ACCESSORY, AND COMPONENT INDICATED. INCLUDE DIMENSIONED ELEVATIONS,
<br />SECTIONS, WEIGHTS, AND MANUFACTURERS' TECHNICAL DATA ON FEATURES,
<br />PERFORMANCE, ELECTRICAL CHARACTERISTICS, RATINGS, AND FINISHES.
<br />1.ENCLOSURE TYPES AND DETAILS FOR TYPES OTHER THAN NEMA 250, TYPE 1.
<br />2.CURRENT AND VOLTAGE RATINGS.
<br />3.SHORT-CIRCUIT CURRENT RATING.
<br />4.FEATURES, CHARACTERISTICS, RATINGS, AND FACTORY SETTINGS OF INDIVIDUAL
<br />OVERCURRENT PROTECTIVE DEVICES AND AUXILIARY COMPONENTS.
<br />B.SHOP DRAWINGS: DIAGRAM POWER, SIGNAL, AND CONTROL WIRING.
<br />C.MANUFACTURER SEISMIC QUALIFICATION CERTIFICATION: SUBMIT CERTIFICATION THAT
<br />ENCLOSED SWITCHES AND CIRCUIT BREAKERS, ACCESSORIES, AND COMPONENTS WILL
<br />WITHSTAND SEISMIC FORCES DEFINED IN DIVISION 26 SECTION "VIBRATION AND SEISMIC
<br />CONTROLS FOR ELECTRICAL WORK." INCLUDE THE FOLLOWING:
<br />1.BASIS OF CERTIFICATION: INDICATE WHETHER WITHSTAND CERTIFICATION IS BASED
<br />ON ACTUAL TEST OF ASSEMBLED COMPONENTS OR ON CALCULATION.
<br />a.THE TERM "WITHSTAND" MEANS "THE UNIT WILL REMAIN IN PLACE WITHOUT
<br />SEPARATION OF ANY PARTS FROM THE DEVICE WHEN SUBJECTED TO THE
<br />SEISMIC FORCES SPECIFIED AND THE UNIT WILL BE FULLY OPERATIONAL AFTER
<br />THE SEISMIC EVENT."
<br />2.DIMENSIONED OUTLINE DRAWINGS OF EQUIPMENT UNIT: IDENTIFY CENTER OF
<br />GRAVITY AND LOCATE AND DESCRIBE MOUNTING AND ANCHORAGE PROVISIONS.
<br />3.DETAILED DESCRIPTION OF EQUIPMENT ANCHORAGE DEVICES ON WHICH THE
<br />CERTIFICATION IS BASED AND THEIR INSTALLATION REQUIREMENTS.
<br />D.QUALIFICATION DATA: FOR TESTING AGENCY.
<br />E.FIELD QUALITY-CONTROL TEST REPORTS INCLUDING THE FOLLOWING:
<br />1.TEST PROCEDURES USED.
<br />2.TEST RESULTS THAT COMPLY WITH REQUIREMENTS.
<br />3.RESULTS OF FAILED TESTS AND CORRECTIVE ACTION TAKEN TO ACHIEVE TEST
<br />RESULTS THAT COMPLY WITH REQUIREMENTS.
<br />F.MANUFACTURER'S FIELD SERVICE REPORT.
<br />G.OPERATION AND MAINTENANCE DATA: FOR ENCLOSED SWITCHES AND CIRCUIT
<br />BREAKERS TO INCLUDE IN EMERGENCY, OPERATION, AND MAINTENANCE MANUALS. IN
<br />ADDITION TO ITEMS SPECIFIED IN DIVISION 01 SECTIONS "PROJECT CLOSEOUT” AND
<br />“OPERATION AND MAINTENANCE DATA," INCLUDE THE FOLLOWING:
<br />1.MANUFACTURER'S WRITTEN INSTRUCTIONS FOR TESTING AND ADJUSTING
<br />ENCLOSED SWITCHES AND CIRCUIT BREAKERS.
<br />2.TIME-CURRENT CURVES, INCLUDING SELECTABLE RANGES FOR EACH TYPE OF
<br />CIRCUIT BREAKER.
<br />1.04 QUALITY ASSURANCE
<br />A.TESTING AGENCY QUALIFICATIONS: AN INDEPENDENT AGENCY, WITH THE EXPERIENCE
<br />AND CAPABILITY TO CONDUCT THE TESTING INDICATED, THAT IS A MEMBER COMPANY OF
<br />THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR IS A NATIONALLY
<br />RECOGNIZED TESTING LABORATORY (NRTL) AS DEFINED BY OSHA IN 29 CFR 1910.7, AND
<br />THAT IS ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION.
<br />1.TESTING AGENCY'S FIELD SUPERVISOR: PERSON CURRENTLY CERTIFIED BY THE
<br />INTERNATIONAL ELECTRICAL TESTING ASSOCIATION OR THE NATIONAL INSTITUTE
<br />FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES TO SUPERVISE ON-SITE
<br />TESTING SPECIFIED IN PART 3.
<br />B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS
<br />DEFINED IN CEC, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES
<br />HAVING JURISDICTION, AND MARKED FOR INTENDED USE.
<br />C.COMPLY WITH CEC.
<br />D.PRODUCT SELECTION FOR RESTRICTED SPACE: DRAWINGS INDICATE MAXIMUM
<br />DIMENSIONS FOR ENCLOSED SWITCHES AND CIRCUIT BREAKERS, INCLUDING
<br />CLEARANCES BETWEEN ENCLOSURES, AND ADJACENT SURFACES AND OTHER ITEMS.
<br />COMPLY WITH INDICATED MAXIMUM DIMENSIONS.
<br />E.STRUCTURAL SEISMIC PERFORMANCE: REFER TO DIVISION 26 SECTION “VIBRATION AND
<br />SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.”
<br />1.05 PROJECT CONDITIONS
<br />A.ENVIRONMENTAL LIMITATIONS: RATE EQUIPMENT FOR CONTINUOUS OPERATION UNDER
<br />THE FOLLOWING CONDITIONS, UNLESS OTHERWISE INDICATED:
<br />1.AMBIENT TEMPERATURE: NOT LESS THAN MINUS 22°F AND NOT EXCEEDING 104°F.
<br />2.ALTITUDE: NOT EXCEEDING 6600 FEET.
<br />1.06 COORDINATION
<br />A.COORDINATE LAYOUT AND INSTALLATION OF SWITCHES, CIRCUIT BREAKERS, AND
<br />COMPONENTS WITH OTHER CONSTRUCTION, INCLUDING CONDUIT, PIPING, EQUIPMENT,
<br />AND ADJACENT SURFACES. MAINTAIN REQUIRED WORKSPACE CLEARANCES AND
<br />REQUIRED CLEARANCES FOR EQUIPMENT ACCESS DOORS AND PANELS.
<br />1.07 EXTRA MATERIALS
<br />A.FURNISH EXTRA MATERIALS DESCRIBED BELOW THAT MATCH PRODUCTS INSTALLED
<br />AND THAT ARE PACKAGED WITH PROTECTIVE COVERING FOR STORAGE AND IDENTIFIED
<br />WITH LABELS DESCRIBING CONTENTS.
<br />1.SPARES: FOR THE FOLLOWING:
<br />a.POTENTIAL TRANSFORMER FUSES: 4.
<br />b.CONTROL-POWER FUSES: 4.
<br />c.FUSES FOR FUSIBLE SWITCHES: 3.
<br />PART 2 - PRODUCTS
<br />2.01 MANUFACTURERS
<br />A.IN OTHER PART 2 ARTICLES WHERE TITLES BELOW INTRODUCE LISTS, THE FOLLOWING
<br />REQUIREMENTS APPLY TO PRODUCT SELECTION:
<br />1.MANUFACTURERS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE
<br />PRODUCTS BY ONE OF THE MANUFACTURERS SPECIFIED.
<br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND
<br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01
<br />SECTION “PRODUCT OPTIONS AND SUBSTITUTIONS”. SPECIFIC PROCEDURES MUST
<br />BE FOLLOWED BEFORE USE OF AN UNNAMED PRODUCT OR MANUFACTURER.
<br />2.02 FUSIBLE AND NONFUSIBLE SWITCHES
<br />A.MANUFACTURERS:
<br />1.EATON CORPORATION; CUTLER-HAMMER PRODUCTS.
<br />2.GENERAL ELECTRIC CO.; ELECTRICAL DISTRIBUTION & CONTROL DIVISION.
<br />3.SIEMENS ENERGY & AUTOMATION, INC.
<br />4.SQUARE D/GROUP SCHNEIDER.
<br />5.OR EQUAL.
<br />B.FUSIBLE SWITCH, 600 A AND SMALLER: NEMA KS 1, TYPE HD, WITH CLIPS OR BOLT PADS
<br />TO ACCOMMODATE SPECIFIED FUSES, LOCKABLE HANDLE WITH CAPABILITY TO ACCEPT
<br />TWO PADLOCKS, AND INTERLOCKED WITH COVER IN CLOSED POSITION.
<br />C.NONFUSIBLE SWITCH, 600 A AND SMALLER: NEMA KS 1, TYPE HD, LOCKABLE HANDLE
<br />WITH CAPABILITY TO ACCEPT TWO PADLOCKS, AND INTERLOCKED WITH COVER IN
<br />CLOSED POSITION.
<br />D.ACCESSORIES:
<br />1.EQUIPMENT GROUND KIT: INTERNALLY MOUNTED AND LABELED FOR COPPER
<br />GROUND CONDUCTORS.
<br />2.NEUTRAL KIT: INTERNALLY MOUNTED; INSULATED, CAPABLE OF BEING GROUNDED,
<br />AND BONDED; AND LABELED FOR COPPER NEUTRAL CONDUCTORS.
<br />3.AUXILIARY CONTACT KIT: AUXILIARY SET OF CONTACTS ARRANGED TO OPEN
<br />BEFORE SWITCH BLADES OPEN.
<br />2.03 FUSED POWER CIRCUIT DEVICES
<br />A.BOLTED-PRESSURE CONTACT SWITCH: UL 977; OPERATING MECHANISM SHALL USE A
<br />ROTARY-MECHANICAL-BOLTING ACTION TO PRODUCE AND MAINTAIN HIGH-CLAMPING
<br />PRESSURE ON THE SWITCH BLADE AFTER IT ENGAGES THE STATIONARY CONTACTS.
<br />1.MANUFACTURERS:
<br />a.EATON CORPORATION; CUTLER-HAMMER PRODUCTS.
<br />b.PRINGLE ELECTRICAL MFG. CO.
<br />c.SIEMENS ENERGY & AUTOMATION, INC.
<br />d.SQUARE D/GROUP SCHNEIDER.
<br />e.OR EQUAL.
<br />2.04 ENCLOSURES
<br />A.NEMA AB 1 AND NEMA KS 1 TO MEET ENVIRONMENTAL CONDITIONS OF INSTALLED
<br />LOCATION.
<br />1.OUTDOOR LOCATIONS: NEMA 250, TYPE 3R.
<br />2.KITCHEN AREAS: NEMA 250, TYPE 4X, STAINLESS STEEL.
<br />3.OTHER WET OR DAMP INDOOR LOCATIONS: NEMA 250, TYPE 4.
<br />4.HAZARDOUS AREAS INDICATED ON DRAWINGS: NEMA 250, TYPE 7C.
<br />PART 3 - EXECUTION
<br />3.01 EXAMINATION
<br />A.EXAMINE ELEMENTS AND SURFACES TO RECEIVE ENCLOSED SWITCHES AND CIRCUIT
<br />BREAKERS FOR COMPLIANCE WITH INSTALLATION TOLERANCES AND OTHER
<br />CONDITIONS AFFECTING PERFORMANCE.
<br />B.PROCEED WITH INSTALLATION ONLY AFTER UNSATISFACTORY CONDITIONS HAVE BEEN
<br />CORRECTED.3.02 CONCRETE BASES
<br />C.COORDINATE SIZE AND LOCATION OF CONCRETE BASES. VERIFY STRUCTURAL
<br />REQUIREMENTS WITH STRUCTURAL ENGINEER.
<br />D.CONCRETE BASE IS SPECIFIED IN DIVISION 26 SECTION "COMMON WORK RESULTS FOR
<br />ELECTRICAL," AND CONCRETE MATERIALS AND INSTALLATION REQUIREMENTS ARE
<br />SPECIFIED IN DIVISION 03.
<br />3.02 INSTALLATION
<br />A.COMPLY WITH APPLICABLE PORTIONS OF NECA 1, NEMA PB 1.1, AND NEMA PB 2.1 FOR
<br />INSTALLATION OF ENCLOSED SWITCHES AND CIRCUIT BREAKERS.
<br />B.MOUNT INDIVIDUAL WALL-MOUNTING SWITCHES AND CIRCUIT BREAKERS WITH TOPS AT
<br />UNIFORM HEIGHT, UNLESS OTHERWISE INDICATED. ANCHOR FLOOR-MOUNTING
<br />SWITCHES TO CONCRETE BASE.
<br />C.<COMPLY WITH MOUNTING AND ANCHORING REQUIREMENTS SPECIFIED IN DIVISION 26
<br />SECTION "VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.">
<br />D.TEMPORARY LIFTING PROVISIONS: REMOVE TEMPORARY LIFTING EYES, CHANNELS, AND
<br />BRACKETS AND TEMPORARY BLOCKING OF MOVING PARTS FROM ENCLOSURES AND
<br />COMPONENTS.
<br />3.03 IDENTIFICATION
<br />A.IDENTIFY FIELD-INSTALLED CONDUCTORS, INTERCONNECTING WIRING, AND
<br />COMPONENTS; PROVIDE WARNING SIGNS AS SPECIFIED IN DIVISION 26 SECTION
<br />"COMMON WORK RESULTS FOR ELECTRICAL” AND IDENTIFICATION FOR ELECTRICAL
<br />SYSTEMS."
<br />B.ENCLOSURE NAMEPLATES: LABEL EACH ENCLOSURE WITH ENGRAVED METAL OR
<br />LAMINATED-PLASTIC NAMEPLATE AS SPECIFIED IN DIVISION 26 SECTION “IDENTIFICATION
<br />FOR ELECTRICAL SYSTEMS".
<br />3.04 FIELD QUALITY CONTROL
<br />A.MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY-AUTHORIZED SERVICE
<br />REPRESENTATIVE TO INSPECT TEST, AND ADJUST FIELD-ASSEMBLED COMPONENTS AND
<br />EQUIPMENT INSTALLATION, INCLUDING CONNECTIONS, AND TO ASSIST IN FIELD TESTING.
<br />REPORT RESULTS IN WRITING.
<br />1.INSPECT MECHANICAL AND ELECTRICAL CONNECTIONS.
<br />2.VERIFY SWITCH AND RELAY TYPE AND LABELING VERIFICATION.
<br />3.VERIFY RATING OF INSTALLED FUSES.
<br />4.INSPECT PROPER INSTALLATION OF TYPE, SIZE, QUANTITY, AND ARRANGEMENT OF
<br />MOUNTING OR ANCHORAGE DEVICES COMPLYING WITH MANUFACTURER'S
<br />CERTIFICATION.
<br />B.PERFORM THE FOLLOWING FIELD TESTS AND INSPECTIONS AND PREPARE TEST
<br />REPORTS:
<br />1.TEST MOUNTING AND ANCHORAGE DEVICES IN ACCORDANCE WITH REQUIREMENTS
<br />IN< DIVISION 26 SECTION "VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL
<br />WORK".
<br />2.PERFORM EACH ELECTRICAL TEST AND VISUAL AND MECHANICAL INSPECTION
<br />STATED IN NETA ATS, SECTION 7.5 FOR SWITCHES AND SECTION 7.6 FOR
<br />MOLDED-CASE CIRCUIT BREAKERS. CERTIFY COMPLIANCE WITH TEST PARAMETERS.
<br />3.CORRECT MALFUNCTIONING UNITS ON-SITE, WHERE POSSIBLE, AND RETEST TO
<br />DEMONSTRATE COMPLIANCE; OTHERWISE, REPLACE WITH NEW UNITS AND RETEST.
<br />4.INFRARED SCANNING:
<br />a.INITIAL INFRARED SCANNING: AFTER SUBSTANTIAL COMPLETION, BUT NOT MORE
<br />THAN 60 DAYS AFTER FINAL ACCEPTANCE, PERFORM AN INFRARED SCAN OF
<br />EACH ENCLOSED SWITCH AND CIRCUIT BREAKER. OPEN OR REMOVE DOORS OR
<br />PANELS SO CONNECTIONS ARE ACCESSIBLE TO PORTABLE SCANNER.
<br />b.FOLLOW-UP INFRARED SCANNING: PERFORM AN ADDITIONAL FOLLOW-UP
<br />INFRARED SCAN OF EACH UNIT 11 MONTHS AFTER DATE OF SUBSTANTIAL
<br />COMPLETION.
<br />c.INSTRUMENTS, EQUIPMENT AND REPORTS:
<br />1)USE AN INFRARED SCANNING DEVICE DESIGNED TO MEASURE TEMPERATURE
<br />OR TO DETECT SIGNIFICANT DEVIATIONS FROM NORMAL VALUES. PROVIDE
<br />CALIBRATION RECORD FOR DEVICE.
<br />2)PREPARE A CERTIFIED REPORT THAT IDENTIFIES ENCLOSED SWITCHES AND
<br />CIRCUIT BREAKERS INCLUDED AND DESCRIBES SCANNING RESULTS.
<br />INCLUDE NOTATION OF DEFICIENCIES DETECTED, REMEDIAL ACTION TAKEN,
<br />AND OBSERVATIONS AFTER REMEDIAL ACTION.
<br />3.05 ADJUSTING
<br />A.SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES.
<br />3.06 CLEANING
<br />A.ON COMPLETION OF INSTALLATION, VACUUM DIRT AND DEBRIS FROM INTERIORS; DO
<br />NOT USE COMPRESSED AIR TO ASSIST IN CLEANING.
<br />SECTION 26 5103
<br />INTERIOR SOLID STATE LIGHTING
<br />PART 1 - GENERAL
<br />1.01 SUMMARY
<br />B.SECTION INCLUDES:
<br />1.INTERIOR SOLID STATE LIGHTING (SSL) LUMINAIRES, LEDS, AND DRIVERS.
<br />2.LIGHTING FIXTURE SUPPORTS.
<br />1.02 DEFINITIONS
<br />A.CCT: CORRELATED COLOR TEMPERATURE.
<br />B.CRI: COLOR-RENDERING INDEX.
<br />C.LED: LIGHT EMITTING DIODE.
<br />D.LER: LUMINAIRE EFFICACY RATING.
<br />E.LUMEN: MEASURED OUTPUT OF LAMP AND LUMINAIRE.
<br />F.LPW: LUMENS PER WATT.
<br />G.LUMINAIRE: COMPLETE LIGHTING FIXTURE, INCLUDING DRIVER.
<br />1.03 ACTION SUBMITTALS
<br />A.PRODUCT DATA: FOR EACH TYPE OF LIGHTING FIXTURE, ARRANGED OF FIXTURE
<br />DESIGNATION. INCLUDE DATA ON FEATURES, ACCESSORIES, FINISHES, AND THE
<br />FOLLOWING:
<br />1.PHYSICAL DESCRIPTION OF LIGHTING FIXTURE INCLUDING DIMENSIONS.
<br />2.ENERGY-EFFICIENCY DATA.
<br />3.LIFE, OUTPUT (LUMENS, CCT, AND CRI), AND ENERGY-EFFICIENCY DATA FOR SSL.
<br />4.PHOTOMETRIC DATA AND ADJUSTMENT FACTORS BASED ON LABORATORY TESTS,
<br />COMPLYING WITH IESNA LIGHTING MEASUREMENTS TESTING & CALCULATION
<br />GUIDES, OF EACH LIGHTING FIXTURE TYPE.
<br />a.MANUFACTURER CERTIFIED DATA: PHOTOMETRIC DATA SHALL BE CERTIFIED BY
<br />A MANUFACTURER'S LABORATORY WITH A CURRENT ACCREDITATION UNDER THE
<br />NATIONAL VOLUNTARY LABORATORY ACCREDITATION PROGRAM FOR ENERGY
<br />EFFICIENT LIGHTING PRODUCTS.
<br />B.PROIVE LIGHTING CONTROL SAMPLES: FOR EACH LIGHTING FIXTURE INDICATED IN THE
<br />INTERIOR LIGHTING FIXTURE SCHEDULE. EACH SAMPLE SHALL INCLUDE A COMPLETE
<br />LUMINAIRE OR LAMP.
<br />C.INSTALLATION INSTRUCTIONS.
<br />1.04 INFORMATIONAL SUBMITTALS
<br />A.FIELD QUALITY-CONTROL REPORTS.
<br />B.WARRANTY: SAMPLE OF SPECIAL OR EXTENDED WARRANTY.
<br />C.SSL LUMINAIRE - IES LM-79 TEST REPORT: SUBMIT TEST REPORT ON MANUFACTURER'S
<br />STANDARD PRODUCTION MODEL LUMINAIRE.
<br />D.LED LIGHT SOURCE - IES LM-80 TEST REPORT: SUBMIT REPORT ON MANUFACTURER'S
<br />STANDARD PRODUCTION LED PACKAGE, ARRAY, OR MODULE.
<br />1.05 CLOSEOUT SUBMITTALS
<br />A.OPERATION AND MAINTENANCE DATA: FOR LIGHTING LUMINAIRES TO INCLUDE IN
<br />OPERATION, AND MAINTENANCE MANUALS.
<br />1.06 QUALITY ASSURANCE
<br />A.LAMPS SHALL BE LISTED ON THE SOUTHERN CALIFORNIA EDISON LIST OF APPROVED
<br />LAMP MANUFACTURERS, ENERGY STAR (ES) APPROVED LAMPS AND FIXTURE LISTS AT
<br />FOLLOWING WEBSITE:
<br />HTTP://WWW.ENERGYSTAR.GOV/PRODUCTFINDER/PRODUCT/CERTIFIED-LIGHT-BULBS
<br />HTTP://WWW.ENERGYSTAR.GOV/PRODUCTFINDER/PRODUCT/CERTIFIED-LIGHT-FIXTURES/RESULTS
<br />OR THE DESIGNLIGHTS™ CONSORTIUM (DLC) QUALIFIED PRODUCTS LIST WHICH IS
<br />AVAILABLE AT THE FOLLOWING WEBSITE
<br />HTTP://WWW.DESIGNLIGHTS.ORG/SOLIDSTATE.ABOUT.QUALIFIEDPRODUCTSLIST_PUBLICV2.PHP.
<br />B.THE OWNER HAS ENDEAVORED TO PROVIDE THE MOST ENERGY LIGHT SOURCE AND
<br />LOWER LIFE CYCLE COST LAMPS AND LUMINARIES. THE OWNER NO LONGER ALLOWS
<br />THE USE OF FLUORESCENT TUBES, U-TUBE LAMPS, METAL HALIDE, HIGH OR LOW
<br />PRESSURE SODIUM OR INCANDESCENT LAMPS. USE OF SSL IS THE OWNER'S STANDARD.
<br />C.LUMINAIRE PHOTOMETRIC DATA TESTING LABORATORY QUALIFICATIONS: PROVIDED BY
<br />MANUFACTURERS' LABORATORIES THAT ARE ACCREDITED UNDER THE NATIONAL
<br />VOLUNTEER LABORATORY ACCREDITATION PROGRAM FOR ENERGY EFFICIENT LIGHTING
<br />PRODUCTS.
<br />D.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS
<br />DEFINED IN CALIFORNIA ELECTRIC CODE BY A QUALIFIED TESTING AGENCY, AND
<br />MARKED FOR INTENDED LOCATION AND APPLICATION.
<br />E.UL COMPLIANCE: LIGHTING FIXTURES FOR HAZARDOUS LOCATIONS SHALL BE LISTED
<br />AND LABELED FOR INDICATED CLASS AND DIVISION BY UL.
<br />F.SSL LIGHT FIXTURES SHALL BE REDUCTION OF HAZARDOUS SUBSTANCES
<br />(ROHS)-COMPLIANT.
<br />G.STRUCTURAL SEISMIC PERFORMANCE: REFER TO DIVISION 26 SECTION “VIBRATION AND
<br />SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.”
<br />1.07 COORDINATION
<br />A.COORDINATE LAYOUT AND INSTALLATION OF LIGHTING FIXTURES AND SUSPENSION
<br />SYSTEM WITH OTHER CONSTRUCTION THAT PENETRATES CEILINGS OR IS SUPPORTED
<br />BY THEM, INCLUDING HVAC EQUIPMENT, FIRE-SUPPRESSION SYSTEM, AND PARTITION
<br />ASSEMBLIES.
<br />1.08 WARRANTY
<br />A.SPECIAL WARRANTY FOR EMERGENCY LIGHTING BATTERIES: MANUFACTURER'S
<br />STANDARD FORM IN WHICH MANUFACTURER OF BATTERY-POWERED EMERGENCY
<br />LIGHTING UNIT AGREES TO REPAIR OR REPLACE COMPONENTS OF RECHARGEABLE
<br />BATTERIES THAT FAIL IN MATERIALS OR WORKMANSHIP WITHIN SPECIFIED WARRANTY
<br />PERIOD.
<br />1.WARRANTY PERIOD FOR EMERGENCY LIGHTING UNIT BATTERIES: 10 YEARS FROM
<br />DATE OF SUBSTANTIAL COMPLETION. FULL WARRANTY SHALL APPLY FOR FIRST
<br />YEAR, AND PRORATED WARRANTY FOR THE REMAINING NINE YEARS.
<br />B.LED LUMINAIRES: SUBMIT A WARRANTY, EXECUTED BY THE INSTALLER AGREEING TO
<br />INSTALL REPLACEMENT LED LUMINARIES THAT FAIL WITHIN TWO YEARS, BEGINNING ON
<br />THE DATE OF SUBSTANTIAL COMPLETION. THIS WARRANTY IS IN ADDITION TO, AND NOT
<br />A LIMITATION OF, OTHER RIGHTS AND REMEDIES THE OWNER MAY HAVE UNDER THE
<br />CONTRACTED DOCUMENTS.
<br />C.SPECIAL WARRANTY: MANUFACTURER'S STANDARD FORM IN WHICH MANUFACTURER
<br />AGREES TO REPAIR OR REPLACE LUMINAIRES OR COMPONENTS OF LUMINAIRES,
<br />DIODES, DRIVERS AND LAMPS THAT FAIL IN MATERIALS OR WORKMANSHIP; CORRODE;
<br />OR FADE, WITHIN SPECIFIED WARRANTY PERIOD IN THE FIXTURE SCHEDULE.
<br />MANUFACTURER MAY EXCLUDE LIGHTNING DAMAGE, VANDALISM, ABUSE, OR
<br />UNAUTHORIZED REPAIRS OR ALTERATIONS FROM SPECIAL WARRANTY COVERAGE.
<br />1.LUMEN MAINTENANCE VALUE FOR THE PRODUCT SHALL NOT FALL BELOW 70% OF
<br />THE LUMEN MAINTENANCE VALUE SPECIFIED.
<br />2.FINISH WARRANTY SHALL INCLUDE WARRANTY AGAINST FAILURE AND AGAINST
<br />SUBSTANTIAL DETERIORATION SUCH AS BLISTERING, CRACKING, PEELING,
<br />CHALKING, OR FADING.
<br />3.MATERIAL WARRANTY SHALL INCLUDE:
<br />a.POWER SUPPLY UNITS (DRIVERS).
<br />b.REPLACEMENT WHEN MORE THAN 10 PERCENT OF LED SOURCES IN ANY LIGHT
<br />BAR OR SUBASSEMBLY(S) ARE DEFECTIVE OR NON-STARTING.
<br />4.WARRANTY PERIOD MUST BEGIN ON DATE OF BENEFICIAL OCCUPANCY.
<br />CONTRACTOR SHALL PROVIDE THE OWNER'S REPRESENTATIVE SIGNED WARRANTY
<br />CERTIFICATES.
<br />D.EXTENDED WARRANTY FOR LED LAMPS:
<br />1.PROVIDE A MANUFACTURER'S WRITTEN 10 YEAR REPLACEMENT WARRANTY FOR
<br />MATERIAL AND WORKMANSHIP.
<br />2.LUMEN MAINTENANCE VALUE FOR THE PRODUCT SHALL NOT FALL BELOW 70% OF
<br />THE LUMEN MAINTENANCE VALUE SPECIFIED.
<br />3.MATERIAL WARRANTY SHALL INCLUDE:
<br />a.POWER SUPPLY UNITS (DRIVERS).
<br />b.REPLACEMENT WHEN MORE THAN 10 PERCENT OF LED SOURCES IN ANY
<br />LIGHTBAR OR SUBASSEMBLY(S) ARE DEFECTIVE OR NON-STARTING.
<br />4.WARRANTY PERIOD MUST BEGIN ON DATE OF BENEFICIAL OCCUPANCY.
<br />CONTRACTOR SHALL PROVIDE THE OWNER'S REPRESENTATIVE SIGNED WARRANTY
<br />CERTIFICATES.
<br />PART 2 - PRODUCTS
<br />2.01 MANUFACTURERS
<br />A.IN OTHER PART 2 ARTICLES WHERE TITLES BELOW INTRODUCE LISTS, THE FOLLOWING
<br />REQUIREMENTS APPLY TO PRODUCT SELECTION:
<br />1.PRODUCTS: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE PRODUCTS
<br />BY ONE OF THE MANUFACTURERS SPECIFIED.
<br />2.OR EQUAL: WHERE PRODUCTS ARE SPECIFIED BY MANUFACTURERS NAME AND
<br />ACCOMPANIED BY THE TERM "OR EQUAL", COMPLY WITH PROVISIONS IN DIVISION 01.
<br />SPECIFIC PROCEDURES MUST BE FOLLOWED BEFORE USE OF AN UNNAMED
<br />PRODUCT OR MANUFACTURER.
<br />2.02 GENERAL REQUIREMENTS FOR LIGHTING FIXTURES AND COMPONENTS
<br />A.RECESSED FIXTURES: COMPLY WITH NEMA LE 4 FOR CEILING COMPATIBILITY FOR
<br />RECESSED FIXTURES.
<br />B.METAL PARTS: FREE OF BURRS AND SHARP CORNERS AND EDGES.
<br />C.SHEET METAL COMPONENTS: STEEL UNLESS OTHERWISE INDICATED. FORM AND
<br />SUPPORT TO PREVENT WARPING AND SAGGING.
<br />D.DOORS, FRAMES, AND OTHER INTERNAL ACCESS: SMOOTH OPERATING, FREE OF LIGHT
<br />LEAKAGE UNDER OPERATING CONDITIONS, AND DESIGNED TO PERMIT ACCESS TO
<br />COMPONENTS WITHOUT USE OF TOOLS. DESIGNED TO PREVENT DOORS, FRAMES,
<br />LENSES, DIFFUSERS, AND OTHER COMPONENTS FROM FALLING ACCIDENTALLY WHEN
<br />SECURED IN OPERATING POSITION.
<br />E.DIFFUSERS AND GLOBES:
<br />1.ACRYLIC LIGHTING DIFFUSERS: 100 PERCENT VIRGIN ACRYLIC PLASTIC. HIGH
<br />RESISTANCE TO YELLOWING AND OTHER CHANGES DUE TO AGING, EXPOSURE TO
<br />HEAT, AND UV RADIATION.
<br />a.LENS THICKNESS: ⅛ INCH, MINIMUM, UNLESS OTHERWISE INDICATED.
<br />b.UV STABILIZED.
<br />2.GLASS: ANNEALED CRYSTAL GLASS UNLESS OTHERWISE INDICATED.
<br />2.03 SOLID STATE LIGHTING LUMINAIRES
<br />A.PROVIDE LUMINAIRES AS INDICATED IN LIGHTING FIXTURE SCHEDULE OR DETAILS ON
<br />PROJECT PLANS. PROVIDE LUMINAIRES COMPLETE WITH LIGHT SOURCES OF QUANTITY,
<br />TYPE, AND WATTAGE INDICATED. LUMINAIRES OF THE SAME TYPE SHALL BE PROVIDED
<br />BY THE SAME MANUFACTURER.
<br />B.GENERAL REQUIREMENTS
<br />1.SSL LUMINAIRE HOUSINGS SHALL BE DIE CAST OR EXTRUDED ALUMINUM
<br />2.SSL LUMINAIRES SHALL BE RATED FOR OPERATION WITHIN AN AMBIENT
<br />TEMPERATURE RANGE OF MINUS 22 DEGREES F TO 104°F.
<br />3.LUMINAIRES SHALL BE UL LISTED FOR WET LOCATIONS PER UL 1598 IF INDICATED.
<br />4.SSL LUMINAIRES SHALL PRODUCE A MINIMUM EFFICACY AS SHOWN IN SCHEDULE OR
<br />SPECIFIED, TESTED PER IES LM-79. THEORETICAL MODELS OF INITIAL RAW LED
<br />LUMENS PER WATT ARE NOT ACCEPTABLE.
<br />5.LUMINAIRES SHALL HAVE IES DISTRIBUTION AND NEMA FIELD ANGLE
<br />CLASSIFICATIONS AS INDICATED IN LUMINAIRE SCHEDULE ON PROJECT PLANS PER
<br />IES HB-10.
<br />6.HOUSING FINISH SHALL BE BAKED-ON ENAMEL, ANODIZED, OR BAKED-ON POWDER
<br />COAT PAINT.
<br />7.LUMINAIRES SHALL BE FULLY ASSEMBLED AND ELECTRICALLY TESTED PRIOR TO
<br />SHIPMENT FROM FACTORY.
<br />8.THE FINISH COLOR SHALL BE AS INDICATED IN THE LUMINAIRE SCHEDULE OR DETAIL
<br />ON THE PROJECT PLANS.
<br />9.LUMINAIRES SHALL HAVE A NAMEPLATE BEARING THE MANUFACTURER'S NAME,
<br />ADDRESS, MODEL NUMBER, DATE OF MANUFACTURE, AND SERIAL NUMBER
<br />SECURELY AFFIXED IN A CONSPICUOUS PLACE. THE NAMEPLATE OF THE
<br />DISTRIBUTING AGENT WILL NOT BE ACCEPTABLE.
<br />C.LED LIGHT SOURCES
<br />1.CCT SHALL BE IN ACCORDANCE WITH NEMA ANSLG C78.377: NOMINAL CCT: 3,500
<br />DEGREES K.
<br />2.CRI SHALL BE: GREATER THAN OR EQUAL TO 90 FOR 3,500 DEGREES K LIGHT
<br />SOURCES.
<br />3.COLOR CONSISTENCY: MANUFACTURER SHALL USE A MAXIMUM 4-STEP MACADAM
<br />ELLIPSE BINNING TOLERANCE FOR COLOR CONSISTENCY OF LEDS USED IN
<br />LUMINAIRES.
<br />D.LED DRIVERS SHALL MEET UL 1310 AND THE FOLLOWING REQUIREMENTS:
<br />1.MINIMUM EFFICIENCY SHALL BE 85 PERCENT.
<br />2.DRIVE CURRENT TO EACH INDIVIDUAL LED SHALL NOT EXCEED 600 MA, PLUS OR
<br />MINUS 10 PERCENT.
<br />3.SHALL BE RATED TO OPERATE BETWEEN AMBIENT TEMPERATURES OF MINUS 22°F
<br />AND 104°F
<br />4.SHALL BE DESIGNED TO OPERATE ON THE VOLTAGE SYSTEM TO WHICH THEY ARE
<br />CONNECTED, TYPICALLY RANGING FROM 120 V TO 480 V NOMINAL.
<br />5.OPERATING FREQUENCY SHALL BE: 60 HZ.
<br />6.POWER FACTOR (PF) SHALL BE GREATER THAN OR EQUAL TO 0.90.
<br />7.TOTAL HARMONIC DISTORTION (THD) CURRENT SHALL BE LESS THAN OR EQUAL TO
<br />20 PERCENT.
<br />8.SHALL MEET REQUIREMENTS OF 47 CFR 15, CLASS B.
<br />9.SHALL BE ROHS-COMPLIANT.
<br />10.SHALL BE MOUNTED INTEGRAL TO LUMINAIRE. REMOTE MOUNTING OF POWER
<br />SUPPLY IS NOT ALLOWED.
<br />11.DRIVERS WHERE APPROPRIATE SHALL BE UL LISTED WITH A SOUND RATING OF A.
<br />12.SHALL BE DIMMABLE WHERE INDICATED, AND COMPATIBLE WITH A STANDARD
<br />DIMMING CONTROL CIRCUIT OF 0 - 10V OR OTHER APPROVED DIMMING SYSTEM.
<br />13.SHALL BE EQUIPPED WITH OVER-TEMPERATURE PROTECTION CIRCUIT THAT TURNS
<br />LIGHT SOURCE OFF UNTIL NORMAL OPERATING TEMPERATURE IS ACHIEVED.
<br />E.LED LUMINAIRE SURGE PROTECTION
<br />1.PROVIDE SURGE PROTECTION INTEGRAL TO LUMINAIRE TO MEET C LOW
<br />WAVEFORMS AS DEFINED BY IEEE C62.41.2, SCENARIO 1, AND LOCATION CATEGORY
<br />C.
<br />2.04 LIGHTING FIXTURE SUPPORT COMPONENTS
<br />A.COMPLY WITH CALIFORNIA BUILDING CODE FOR CHANNEL- AND ANGLE-IRON SUPPORTS
<br />AND NONMETALLIC CHANNEL AND ANGLE SUPPORTS.
<br />B.SINGLE-STEM HANGERS: ½-INCH STEEL TUBING WITH SWIVEL BALL FITTINGS AND
<br />CEILING CANOPY. FINISH SAME AS FIXTURE.
<br />C.TWIN-STEM HANGERS: TWO, ½-INCH STEEL TUBES WITH SINGLE CANOPY DESIGNED TO
<br />MOUNT A SINGLE FIXTURE. FINISH SAME AS FIXTURE.
<br />D.WIRES: ASTM A641, CLASS 3, SOFT TEMPER, ZINC-COATED STEEL, 12 GAUGE SIZE.
<br />E.WIRES FOR HUMID SPACES: ASTM A 580/A 580M, COMPOSITION 302 OR 304, ANNEALED
<br />STAINLESS STEEL, 12 GAUGE.
<br />F.ROD HANGERS: 3/16-INCH MINIMUM DIAMETER, CADMIUM-PLATED, THREADED STEEL
<br />ROD.
<br />G.HOOK HANGERS: INTEGRATED ASSEMBLY MATCHED TO FIXTURE AND LINE VOLTAGE
<br />AND EQUIPPED WITH THREADED ATTACHMENT, CORD, AND LOCKING-TYPE PLUG.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION
<br />A.LIGHTING FIXTURES:
<br />1.SET LEVEL, PLUMB, AND SQUARE WITH CEILINGS AND WALLS UNLESS OTHERWISE
<br />INDICATED.
<br />2.INSTALL DIODES IN EACH LUMINAIRE.
<br />B.TEMPORARY LIGHTING: IF IT IS NECESSARY, AND APPROVED BY OWNER'S
<br />REPRESENTATIVE, TO USE PERMANENT LUMINAIRES FOR TEMPORARY LIGHTING,
<br />INSTALL AND ENERGIZE THE MINIMUM NUMBER OF LUMINAIRES NECESSARY. WHEN
<br />CONSTRUCTION IS SUFFICIENTLY COMPLETE, DISASSEMBLE LUMINAIRES USED DURING
<br />CONSTRUCTION, AND CLEAN THOROUGHLY.
<br />C.LAY-IN CEILING LIGHTING FIXTURES SUPPORTS: USE GRID AS A SUPPORT ELEMENT.
<br />1.INSTALL CEILING SUPPORT SYSTEM RODS OR WIRES, INDEPENDENT OF THE CEILING
<br />SUSPENSION DEVICES, FOR EACH FIXTURE. LOCATE NOT MORE THAN 6 INCHES
<br />FROM LIGHTING FIXTURE CORNERS.
<br />2.SUPPORT CLIPS: FASTEN TO LIGHTING FIXTURES AND TO CEILING GRID MEMBERS AT
<br />OR NEAR EACH FIXTURE CORNER WITH CLIPS THAT ARE UL LISTED FOR THE
<br />APPLICATION.
<br />3.FIXTURES OF SIZES LESS THAN CEILING GRID: INSTALL AS INDICATED ON REFLECTED
<br />CEILING PLANS OR CENTER IN ACOUSTICAL PANEL, AND SUPPORT FIXTURES
<br />INDEPENDENTLY WITH AT LEAST TWO 3/4-INCH METAL CHANNELS SPANNING AND
<br />SECURED TO CEILING TEES.
<br />4.INSTALL AT LEAST ONE INDEPENDENT SUPPORT ROD OR WIRE FROM STRUCTURE TO
<br />A TAB ON LIGHTING FIXTURE. WIRE OR ROD SHALL HAVE BREAKING STRENGTH OF
<br />THE WEIGHT OF FIXTURE AT A SAFETY FACTOR OF 3.
<br />D.SUSPENDED LIGHTING FIXTURE SUPPORT:
<br />1.PENDANTS AND RODS: WHERE LONGER THAN 48 INCHES, BRACE TO LIMIT SWINGING.
<br />2.STEM-MOUNTED, SINGLE-UNIT FIXTURES: SUSPEND WITH TWIN-STEM HANGERS.
<br />3.CONTINUOUS ROWS: USE TUBING OR STEM FOR WIRING AT ONE POINT AND TUBING
<br />OR ROD FOR SUSPENSION FOR EACH UNIT LENGTH OF FIXTURE CHASSIS, INCLUDING
<br />ONE AT EACH END.
<br />4.DO NOT USE GRID AS SUPPORT FOR PENDANT LUMINAIRES. CONNECT SUPPORT
<br />WIRES OR RODS TO BUILDING STRUCTURE.
<br />E.CONNECT WIRING IN ACCORDANCE WITH CALIFORNIA ELECTRIC CODE.
<br />3.02 FIELD QUALITY CONTROL
<br />A.TEST FOR EMERGENCY LIGHTING: INTERRUPT POWER SUPPLY TO DEMONSTRATE
<br />PROPER OPERATION. VERIFY TRANSFER FROM NORMAL POWER TO EMERGENCY
<br />POWER AND RETRANSFER TO NORMAL.
<br />B.PREPARE A WRITTEN REPORT OF TESTS, INSPECTIONS, OBSERVATIONS, AND
<br />VERIFICATIONS INDICATING AND INTERPRETING RESULTS. IF ADJUSTMENTS ARE MADE
<br />TO LIGHTING SYSTEM, RETEST TO DEMONSTRATE COMPLIANCE WITH STANDARDS.
<br />3.03 HAZARDOUS LAMP DISPOSAL
<br />A.HAZARDOUS LAMPS SHALL BE REMOVED FROM FIXTURES AND DISPOSED PER CITY
<br />REQUIREMENTS.
<br />B.COMPLY WITH ADDITIONAL INFORMATION AT THE CITY WEBSITE FOR CONSTRUCTION
<br />RELATED HAZARDOUS WASTE GUIDELINES.
<br />C.AS A CONTRACTOR OPTION, BOX UP AND TRANSPORT THE HAZARDOUS LAMPS TO THE
<br />CITY'S HAZARDOUS WASTE FACILITY.
<br />SECTION 26 0563
<br />ELECTRICAL TESTING
<br />PART 1 - GENERAL
<br />1.01 SUMMARY
<br />A.SECTION INCLUDES GENERAL REQUIREMENTS FOR ELECTRICAL FIELD TESTING AND
<br />INSPECTING. DETAILED REQUIREMENTS ARE SPECIFIED IN EACH SECTION CONTAINING
<br />COMPONENTS THAT REQUIRE TESTING. GENERAL REQUIREMENTS INCLUDE THE
<br />FOLLOWING:
<br />1.QUALIFICATIONS OF TESTING AGENCIES AND THEIR PERSONNEL.
<br />2.SUITABILITY OF TEST EQUIPMENT.
<br />3.CALIBRATION OF TEST INSTRUMENTS.
<br />4.COORDINATION REQUIREMENTS FOR TESTING AND INSPECTING.
<br />5.REPORTING REQUIREMENTS FOR TESTING AND INSPECTING.
<br />1.02 QUALITY ASSURANCE
<br />A.TESTING AGENCY QUALIFICATIONS: AS SPECIFIED IN EACH SECTION CONTAINING
<br />ELECTRICAL TESTING REQUIREMENTS AND IN SUBPARAGRAPH AND ASSOCIATED
<br />SUBPARAGRAPH BELOW.
<br />1.INDEPENDENT TESTING AGENCIES: INDEPENDENT OF MANUFACTURERS, SUPPLIERS,
<br />AND INSTALLERS OF COMPONENTS TO BE TESTED OR INSPECTED.
<br />a.TESTING AGENCY'S FIELD SUPERVISOR FOR POWER COMPONENT TESTING:
<br />PERSON CURRENTLY CERTIFIED BY THE INTERNATIONAL ELECTRICAL TESTING
<br />ASSOCIATION OR THE NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING
<br />TECHNOLOGIES TO SUPERVISE ON-SITE TESTING SPECIFIED IN DIVISION 26
<br />POWER COMPONENT SECTIONS.
<br />B.TEST EQUIPMENT SUITABILITY: COMPLY WITH NETA ATS, SECTION 5.2.
<br />C.TEST EQUIPMENT CALIBRATION: COMPLY WITH NETA ATS, SECTION 5.3.
<br />PART 2 - NOT USED
<br />PART 3 - EXECUTION
<br />3.01 GENERAL TESTS AND INSPECTIONS
<br />A.IF A GROUP OF TESTS ARE SPECIFIED TO BE PERFORMED BY AN INDEPENDENT TESTING
<br />AGENCY, PREPARE SYSTEMS, EQUIPMENT, AND COMPONENTS FOR TESTS AND
<br />INSPECTIONS, AND PERFORM PRELIMINARY TESTS TO ENSURE THAT SYSTEMS,
<br />EQUIPMENT, AND COMPONENTS ARE READY FOR INDEPENDENT AGENCY TESTING.
<br />INCLUDE THE FOLLOWING MINIMUM PREPARATIONS AS APPROPRIATE:
<br />1.PERFORM INSULATION-RESISTANCE TESTS.
<br />2.PERFORM CONTINUITY TESTS.
<br />3.PERFORM ROTATION TEST (FOR MOTORS TO BE TESTED).
<br />4.PROVIDE A STABLE SOURCE OF SINGLE-PHASE, 208/120-V ELECTRICAL POWER FOR
<br />TEST INSTRUMENTATION AT EACH TEST LOCATION.
<br />B.TEST AND INSPECTION REPORTS: IN ADDITION TO REQUIREMENTS SPECIFIED
<br />ELSEWHERE, REPORT THE FOLLOWING:
<br />1.MANUFACTURER'S WRITTEN TESTING AND INSPECTING INSTRUCTIONS.
<br />2.CALIBRATION AND ADJUSTMENT SETTINGS OF ADJUSTABLE AND INTERCHANGEABLE
<br />DEVICES INVOLVED IN TESTS.
<br />3.TABULATION OF EXPECTED MEASUREMENT RESULTS MADE BEFORE
<br />MEASUREMENTS.
<br />4.TABULATION OF "AS-FOUND" AND "AS-LEFT" MEASUREMENT AND OBSERVATION
<br />RESULTS.
<br />Sheet No.
<br />Project
<br />Agency Plan Check / Permit No.
<br />Petersen Design Project No.
<br />Consultant
<br />5082.1
<br />652 East Dyer Drive
<br />Santa Ana, CA 92705
<br />DYER WAREHOUSE
<br />Staging & Set-Up Space
<br />Tenant Improvements
<br />Sheet Title
<br />Revision / Submittal History
<br />Scale
<br />Status
<br />.
<br />architecture + planning
<br />Agency Approval
<br />Petersen Design Architects, Inc.
<br />17582 Fiesta Way, Tustin, CA 92780
<br />M: 714.904.6720 E: mike@mpdarch.com
<br />www.mpdarch.com
<br />Architect's Stamp
<br />.
<br />255 E. Rincon St., Suite 301
<br />Corona, CA 92879
<br />P 951.340.1977 | F 951.340.1090
<br />www.gossengineering.com
<br />CALOFI
<br />GI
<br />RE
<br />NG
<br />A
<br />E
<br />S
<br />No. E17083
<br />T
<br />E
<br />ET
<br />SAT L CE A
<br />F
<br />RIC L
<br />ORNI
<br />EPR
<br />RAET
<br />RED D.D
<br />OF ONABR
<br />L
<br />SSI
<br />NE
<br />RE
<br />IWD
<br />UT
<br />HCE
<br />Project Number: 125-09-07
<br />Date Signed 01-09-2026
<br />1 01/09/2026 PLAN CHECK RESUBMITTAL
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />E7.3
|