SECTION 28 3111
<br />DIGITAL ADDRESSABLE FIRE-ALARM SYSTEM
<br />PART 1 - GENERAL
<br />1.01 SUMMARY
<br />A.SECTION INCLUDES:
<br />1.FIRE ALARM CONTROL UNIT.
<br />2.MANUAL FIRE ALARM BOXES.
<br />3.ANALOG SENSORS.
<br />4.CONVENTIONAL DETECTORS.
<br />5.MISCELLANEOUS DETECTION.
<br />6.ADDRESSABLE MODULES.
<br />7.NOTIFICATION APPLIANCES.
<br />8.ADDRESSABLE INTERFACE MODULES.
<br />1.02 DEFINITIONS
<br />A.DEFINITIONS IN NFPA 72 AND UL 864 ARE INCLUSIVE TO THIS SECTION.
<br />B.LED: LIGHT-EMITTING DIODE.
<br />C.NICET: NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES.
<br />D.FACP: MAIN FIRE ALARM CONTROL PANEL.
<br />E.MINIPLEX: REMOTE INPUT/OUTPUT PANEL CONNECTED TO A FACP VIA REMOTE UNIT
<br />INTERFACE.
<br />F.TPS: AN ADDRESSABLE NOTIFICATION POWER SUPPLY MOUNTED IN AN FACP
<br />ENCLOSURE.
<br />G.RPS: REMOTE POWER SUPPLY FOR CONVENTIONAL HORNS AND STROBES.
<br />1.03 SYSTEM DESCRIPTION
<br />A.NON-CODED, UL 864 9TH EDITION, UL-CERTIFIED ANALOG-ADDRESSABLE SYSTEM WITH
<br />AUTOMATIC SENSITIVITY CONTROL OF SYSTEM SMOKE DETECTORS AT THE MAIN PANEL
<br />AND THE GCC.
<br />1.04 PERFORMANCE REQUIREMENTS
<br />A.COMPLY WITH NFPA 72.
<br />B.UL LISTED AND LABELED.
<br />C.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS
<br />DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED
<br />LOCATION AND APPLICATION.
<br />D.SEISMIC PERFORMANCE FACP AND RACEWAYS SHALL WITHSTAND THE EFFECTS OF
<br />EARTHQUAKE MOTIONS DETERMINED ACCORDING TO THE VIBRATION AND SEISMIC
<br />CONTROLS FOR ELECTRICAL SYSTEM SPECIFICATION SECTION.
<br />1.05 SUBMITTALS
<br />A.GENERAL SUBMITTAL REQUIREMENTS:
<br />1.SUBMITTALS: PRODUCT DATA AND SYSTEM OPERATING DESCRIPTION.
<br />2.SUBMITTALS TO AUTHORITIES HAVING JURISDICTION: IN ADDITION TO DISTRIBUTION
<br />REQUIREMENTS FOR SUBMITTALS, MAKE AN IDENTICAL SUBMITTAL TO AUTHORITIES
<br />HAVING JURISDICTION. TO FACILITATE REVIEW, INCLUDE COPIES OF ANNOTATED
<br />CONTRACT DRAWINGS AS NEEDED TO DEPICT COMPONENT LOCATIONS.
<br />3.SHOP DRAWINGS SHALL BE PREPARED BY PERSONS WITH THE FOLLOWING
<br />QUALIFICATIONS:
<br />a.TRAINED AND CERTIFIED BY MANUFACTURER IN FIRE ALARM SYSTEM DESIGN.
<br />b.FIRE ALARM CERTIFIED BY NICET, MINIMUM LEVEL II.
<br />B.PRODUCT DATA:
<br />1.PROVIDE MANUFACTURES DATA SHEETS AND SFM LISTING SHEETS FOR ALL
<br />PRODUCTS.
<br />C.SHOP DRAWINGS:
<br />1.FIRE ALARM SYSTEM:
<br />a.INCLUDE PLANS, ELEVATIONS, SECTIONS, DETAILS, RISER DIAGRAMS GENERAL
<br />NOTES, LOCATION, SCOPE OF THE WORK AND ATTACHMENTS TO OTHER WORK.
<br />b.SYSTEM OPERATION DESCRIPTION: DETAILED DESCRIPTION FOR THIS PROJECT,
<br />INCLUDING METHOD OF OPERATION AND SUPERVISION OF EACH TYPE OF
<br />CIRCUIT AND SEQUENCE OF OPERATIONS FOR MANUALLY AND AUTOMATICALLY
<br />INITIATED SYSTEM INPUTS AND OUTPUTS. MANUFACTURER'S STANDARD
<br />DESCRIPTIONS FOR GENERIC SYSTEMS ARE NOT ACCEPTABLE.
<br />c.COMPLY WITH RECOMMENDATIONS IN THE “DOCUMENTATION” SECTION OF THE
<br />“FUNDAMENTALS OF FIRE ALARM SYSTEMS” CHAPTER IN NFPA 72.
<br />d.INCLUDE VOLTAGE DROP CALCULATIONS FOR ALL NOTIFICATION APPLIANCE
<br />CIRCUIT.
<br />1)WORST CASE ONLY CALCULATIONS ARE NOT ACCEPTABLE.
<br />e.INCLUDE BATTERY-SIZE CALCULATION(S) WITH STAND-BY AND ALARM LOADS FOR
<br />ALL COMPONENTS.
<br />f.INCLUDE ELECTRICAL PANEL AND CIRCUIT NUMBER FOR ALL 120VAC SOURCES.
<br />g.DEVICE ADDRESS:
<br />1)SHOW THE ADDRESS FOR EACH ADDRESSABLE DEVICE SHOWN ON THE
<br />PLANS.
<br />2)COORDINATE CUSTOM DEVICE LABEL WITH DCFM PRIOR TO PROGRAMMING
<br />LABELS.
<br />h.SYSTEM RISER DIAGRAM: SHOW ALL EQUIPMENT, TERMINAL CANS, DEVICES,
<br />CONDUIT ROUTING, CABLE ROUTING AND CABLE TYPE AND QUANTITY. PROVIDE
<br />LADDER TYPE RISER LAY-OUT WITH ALL INTERCONNECTING CONDUITS.
<br />i.WIRING DIAGRAMS: PROVIDE WIRING TYPE, PART NUMBER, MANUFACTURE AND
<br />COLOR CODE.
<br />j.POWER, SIGNAL, AND CONTROL WIRING: INCLUDE DIAGRAMS FOR EQUIPMENT
<br />AND FOR SYSTEM WITH ALL TERMINALS AND INTERCONNECTIONS IDENTIFIED.
<br />k.DUCT SMOKE DETECTORS: PROVIDE PERFORMANCE PARAMETERS AND
<br />INSTALLATION DETAILS FOR EACH DUCT DETECTOR OR IN-DUCT DETECTOR,
<br />PROVIDE THE COMPLETE RANGE OF AIR VELOCITY, TEMPERATURE, AND
<br />HUMIDITY ALLOWED FOR PROPER OPERATION. PROVIDE WEATHERPROOF DETAIL
<br />FOR ALL ROOF TOP MOUNTED AND/OR EXPOSED DETECTORS.
<br />l.DUCTWORK DRAWINGS: SHOW CRITICAL DIMENSIONS THAT RELATE TO
<br />PLACEMENT AND SUPPORT OF SAMPLING TUBES, THE DETECTOR HOUSING, AND
<br />REMOTE STATUS AND ALARM INDICATORS. LOCATE DETECTORS ON PLANS
<br />ACCORDING TO MANUFACTURER'S WRITTEN RECOMMENDATIONS.
<br />m.FLOOR PLANS: INDICATE FINAL OUTLET LOCATIONS SHOWING ADDRESS OF EACH
<br />ADDRESSABLE DEVICE. SHOW ROUTE OF CABLE AND CONDUITS.
<br />n.ROOM NUMBERS: CONFIRM ROOM NUMBERS BEING USED IN PROGRAMMING ARE
<br />THE FINAL NUMBERS ASSIGNED BY FACILITIES MANAGEMENT.
<br />D.SUBMITTALS TO STATE FIRE MARSHAL (SFM): IN ADDITION TO DISTRIBUTION
<br />REQUIREMENTS FOR SUBMITTALS SPECIFIED IN DIVISION 01 SECTION “SUBMITTALS”,
<br />MAKE AN IDENTICAL SUBMITTAL TO THE OWNER'S REPRESENTATIVE. TO FACILITATE
<br />REVIEW, INCLUDE COPIES OF ANNOTATED CONTRACT DRAWINGS AS NEEDED TO DEPICT
<br />COMPONENT LOCATIONS. RESUBMIT AS REQUIRED TO MAKE CLARIFICATIONS OR
<br />REVISIONS TO OBTAIN APPROVAL. ON RECEIPT OF COMMENTS FROM STATE FIRE
<br />MARSHAL, SUBMIT THEM TO THE OWNER'S REPRESENTATIVE FOR REVIEW.
<br />E.RESUBMITTALS: MAKE CORRECTIONS AND RESUBMIT DRAWINGS AS REQUIRED UNTIL
<br />THE PLANS ARE REVIEWED AND APPROVED BY THE STATE FIRE MARSHAL.
<br />F.DELEGATED-DESIGN SUBMITTALS: THE MECHANICAL ENGINEER OF RECORD WILL
<br />COORDINATE THE SPECIFIC LOCATION OF EACH DUCT DETECTOR WITH THE
<br />MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS PRIOR TO THE INSTALLATION
<br />OF ANY DUCT MOUNTED DEVICE.
<br />1.06 QUALITY ASSURANCE
<br />A.INSTALLER QUALIFICATIONS:
<br />1.PERSONNEL INSTALLING WIRE, CABLE, DEVICES OR MAKING FINAL CONNECTIONS
<br />SHALL BE TRAINED OR SUPERVISED BY THE MANUFACTURER.
<br />2.INSTALLERS SHALL BE LICENSED, AS REQUIRED, BY THE STATE OF CALIFORNIA.
<br />B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES:
<br />1.LISTED AND LABELED AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY
<br />ACCEPTABLE TO CALIFORNIA STATE FIRE MARSHAL, AND MARKED FOR INTENDED
<br />USE.
<br />1.07 PROJECT CONDITIONS
<br />A.INTERRUPTION OF EXISTING FIRE ALARM SERVICE: DO NOT INTERRUPT FIRE ALARM
<br />SERVICE TO FACILITIES OCCUPIED BY THE OWNER OR OTHERS UNLESS PERMITTED
<br />UNDER THE FOLLOWING CONDITIONS AND THEN ONLY AFTER ARRANGING TO PROVIDE
<br />TEMPORARY GUARD SERVICE ACCORDING TO REQUIREMENTS INDICATED:
<br />1.NOTIFY THE OWNER'S REPRESENTATIVE NO FEWER THAN FOURTEEN DAYS IN
<br />ADVANCE OF PROPOSED INTERRUPTION OF FIRE ALARM SERVICE.
<br />2.DO NOT PROCEED WITH INTERRUPTION OF FIRE ALARM SERVICE WITHOUT THE
<br />OWNER'S REPRESENTATIVE WRITTEN PERMISSION.
<br />1.08 SEQUENCING AND SCHEDULING
<br />A.EXISTING FIRE ALARM EQUIPMENT: THE EXISTING FIRE ALARM CONTROL PANEL SHALL
<br />REMAIN. MAINTAIN FULLY OPERATIONAL UNTIL NEW EQUIPMENT HAS BEEN TESTED AND
<br />ACCEPTED. AS NEW EQUIPMENT IS INSTALLED, LABEL IT "NOT IN SERVICE" UNTIL IT IS
<br />ACCEPTED. REMOVE LABELS FROM NEW EQUIPMENT WHEN PUT INTO SERVICE AND
<br />LABEL EXISTING FIRE ALARM EQUIPMENT "NOT IN SERVICE" UNTIL REMOVED FROM THE
<br />BUILDING.
<br />1.09 SOFTWARE SERVICE AGREEMENT
<br />A.AT THE COMPLETION OF THE PROJECT UPDATE THE FACP SOFTWARE AND FIRMWARE TO
<br />THE LATEST VERSION REQUIRED FOR PROPER OPERATION OF THE SYSTEM. PROVIDE
<br />ACCESS FOR SOFTWARE AND FIRMWARE UPGRADES VIA THE INTERNET. UPGRADE
<br />SHALL INCLUDE NEW OR REVISED LICENSES FOR USE OF THE SOFTWARE.
<br />1.10 EXTRA MATERIALS
<br />A.FURNISH EXTRA MATERIALS THAT MATCH PRODUCTS INSTALLED AND THAT ARE
<br />PACKAGED WITH PROTECTIVE COVERING FOR STORAGE AND IDENTIFIED WITH LABELS
<br />DESCRIBING CONTENTS.
<br />1.QUANTITIES OF THE FOLLOWING DEVICES EQUAL TO 10 PERCENT OF THE AMOUNTS
<br />SHOWN FOR EACH DEVICE ON THE APPROVED PLANS BUT NO LESS THAN ONE OF
<br />EACH TYPE OF DEVICE.
<br />a.PULL STATION.
<br />b.ADDRESSABLE MONITOR MODULE.
<br />c.ADDRESSABLE CONTROL MODULE.
<br />d.SMOKE DETECTOR HEAD (SENSOR).
<br />e.SMOKE DETECTOR BASE.
<br />f.HEAT DETECTOR HEAD (SENSOR).
<br />g.HEAT DETECTOR BASE.
<br />h.DUCT DETECTOR HOUSING WITH HEAD.
<br />i.IN-DUCT DETECTOR HOUSING.
<br />j.INDOOR INDICATING DEVICES: HORN, SPEAKER, STROBE AND/OR COMBINATION
<br />DEVICES.
<br />k.KEYS AND TOOLS: ONE SET OF EACH KEY AND/OR SPECIAL TOOL USED FOR
<br />LOCKS AND ACCESS.
<br />PART 2 - PRODUCTS
<br />2.01 FIRE ALARM CONTROL PANEL (FACP)
<br />A.GENERAL: EXISTING FIRE ALARM CONTROL PANEL SHALL REMAIN AND NEW DEVICES
<br />SHALL BE COMPATIBLE WITH THE EXISTING FACP.
<br />2.02 ADDRESSABLE MANUAL FIRE ALARM BOXES
<br />A.UL 38 LISTED; FINISHED IN RED WITH MOLDED, RAISED-LETTER OPERATING
<br />INSTRUCTIONS IN CONTRASTING COLOR. STATION SHALL SHOW VISIBLE INDICATION OF
<br />OPERATION. MOUNTED ON RECESSED OUTLET BOX; IF INDICATED AS SURFACE
<br />MOUNTED, PROVIDE MANUFACTURER'S SURFACE BACK BOX.
<br />B.SINGLE-ACTION MECHANISM, PULL-LEVER TYPE. WITH INTEGRAL ADDRESSABLE
<br />MODULE, ARRANGED TO COMMUNICATE INDIVIDUAL MANUAL-STATION STATUS (NORMAL,
<br />ALARM, OR TROUBLE) TO THE FACP AND PROJECT'S GCC.
<br />C.WEATHERPROOF FIRE ALARM BOXES: PROVIDE WEATHERPROOF SINGLE-ACTION
<br />DEVICES WITH ADDRESSABLE MODULE.
<br />D.COVERS: FACTORY-FABRICATED CLEAR PLASTIC ENCLOSURES ARE NOT PERMITTED TO
<br />BE USED.
<br />2.03 ADDRESSABLE ANALOG SENSORS
<br />A.SMOKE SENSORS
<br />1.GENERAL: COMPLY WITH UL 268, "SMOKE DETECTORS FOR FIRE PROTECTIVE
<br />SIGNALING SYSTEMS."
<br />2.INCLUDE THE FOLLOWING FEATURES:
<br />a.FACTORY NAMEPLATE: SERIAL NUMBER AND TYPE IDENTIFICATION.
<br />b.OPERATING VOLTAGE: 24 VDC, NOMINAL.
<br />3.SELF-RESTORING: DETECTORS DO NOT REQUIRE RESETTING OR READJUSTMENT
<br />AFTER ACTUATION TO RESTORE NORMAL OPERATION.
<br />4.PLUG-IN ARRANGEMENT: SENSOR AND ASSOCIATED ELECTRONIC COMPONENTS ARE
<br />MOUNTED IN A MODULE THAT CONNECTS TO A FIXED BASE WITH A TWIST-LOCKING
<br />PLUG CONNECTION. BASE SHALL PROVIDE BREAK-OFF PLASTIC TAB THAT CAN BE
<br />REMOVED TO ENGAGE THE HEAD/BASE LOCKING MECHANISM. NO SPECIAL TOOLS
<br />SHALL BE REQUIRED TO REMOVE HEAD ONCE IT HAS BEEN LOCKED. REMOVAL OF
<br />THE DETECTOR HEAD SHALL INTERRUPT THE SUPERVISORY CIRCUIT OF THE FIRE
<br />ALARM DETECTION LOOP AND CAUSE A TROUBLE SIGNAL AT THE CONTROL UNIT.
<br />5.EACH SENSOR BASE SHALL CONTAIN AN LED THAT WILL FLASH EACH TIME IT IS
<br />SCANNED BY THE CONTROL UNIT (ONCE EVERY 4 SECONDS). IN ALARM CONDITION,
<br />THE SENSOR BASE LED SHALL BE ON STEADY.
<br />6.EACH SENSOR BASE SHALL CONTAIN A MAGNETICALLY ACTUATED TEST SWITCH TO
<br />PROVIDE FOR EASY ALARM TESTING AT THE SENSOR LOCATION.
<br />7.EACH SENSOR SHALL BE SCANNED BY THE CONTROL UNIT FOR ITS TYPE
<br />IDENTIFICATION TO PREVENT INADVERTENT SUBSTITUTION OF ANOTHER SENSOR
<br />TYPE. UPON DETECTION OF A "WRONG DEVICE", THE CONTROL UNIT SHALL OPERATE
<br />WITH THE INSTALLED DEVICE AT THE DEFAULT ALARM SETTINGS FOR THAT SENSOR;
<br />2.5% OBSCURATION FOR PHOTOELECTRIC SENSOR, 135-DEG F AND 15-DEG F
<br />RATE-OF-RISE FOR THE HEAT SENSOR, BUT SHALL INDICATE A "WRONG DEVICE"
<br />TROUBLE CONDITION.
<br />8.THE SENSOR'S ELECTRONICS SHALL BE IMMUNE FROM FALSE ALARMS CAUSED BY
<br />EMI AND RFI.
<br />9.SENSORS INCLUDE A COMMUNICATION TRANSMITTER AND RECEIVER IN THE
<br />MOUNTING BASE HAVING A UNIQUE IDENTIFICATION AND CAPABILITY FOR STATUS
<br />REPORTING TO THE FACP. SENSOR ADDRESS SHALL BE LOCATED IN BASE TO
<br />ELIMINATE FALSE ADDRESSING WHEN REPLACING SENSORS.
<br />10.ENVIRONMENTAL COMPENSATION, PROGRAMMABLE SENSITIVITY SETTINGS, STATUS
<br />TESTING, AND MONITORING OF SENSOR DIRT ACCUMULATION FOR THE DUCT
<br />SENSOR SHALL BE PROVIDED BY THE FACP.
<br />11.REMOVAL OF THE SENSOR HEAD FOR CLEANING SHALL NOT REQUIRE THE SETTING
<br />OF ADDRESSES.
<br />B.TYPE: SMOKE SENSORS SHALL BE OF THE PHOTOELECTRIC OR COMBINATION
<br />PHOTOELECTRIC / HEAT TYPE.
<br />1.WHERE ACCEPTABLE PER MANUFACTURER SPECIFICATIONS, IONIZATION TYPE
<br />SENSORS MAY BE USED.
<br />C.BASES: RELAY OUTPUT, REMOTE LED, SOUNDER AND ISOLATOR BASES SHALL BE
<br />SUPPORTED ALTERNATIVES TO THE STANDARD BASE.
<br />D.DUCT SMOKE SENSOR:
<br />1.PHOTOELECTRIC TYPE, WITH HOUSING AND SAMPLING TUBE OF DESIGN AND
<br />DIMENSIONS AS RECOMMENDED BY THE MANUFACTURER FOR THE SPECIFIC DUCT
<br />SIZE AND INSTALLATION CONDITIONS WHERE APPLIED. SENSOR INCLUDES RELAY AS
<br />REQUIRED FOR FAN SHUTDOWN.
<br />2.WHEN REQUIRED THE DUCT HOUSING SHALL PROVIDE A SUPERVISED RELAY DRIVER
<br />CIRCUIT FOR DRIVING UP TO 15 RELAYS WITH A SINGLE "FORM C" CONTACT RATED
<br />AT 7A@ 28VDC OR 10A@ 120VAC. THIS AUXILIARY RELAY OUTPUT SHALL BE FULLY
<br />PROGRAMMABLE. RELAY SHALL BE MOUNTED WITHIN 3 FEET OF HVAC CONTROL
<br />CIRCUIT.
<br />3.DUCT HOUSING SHALL PROVIDE A RELAY CONTROL TROUBLE INDICATOR YELLOW
<br />LED.
<br />4.COMPACT DUCT HOUSING SHALL HAVE A TRANSPARENT COVER TO MONITOR FOR
<br />THE PRESENCE OF SMOKE. COVER SHALL SECURE TO HOUSING BY MEANS OF FOUR
<br />(4) CAPTIVE FASTENING SCREWS.
<br />5.DUCT HOUSING SHALL PROVIDE TWO (2) TEST PORTS FOR MEASURING AIRFLOW AND
<br />FOR TESTING. THESE PORTS WILL ALLOW AEROSOL INJECTION IN ORDER TO TEST
<br />THE ACTIVATION OF THE DUCT SMOKE SENSOR.
<br />6.DUCT HOUSING SHALL PROVIDE A MAGNETIC TEST AREA AND RED SENSOR STATUS
<br />LED.
<br />7.FOR MAINTENANCE PURPOSES, IT SHALL BE POSSIBLE TO CLEAN THE DUCT HOUSING
<br />SAMPLING TUBES BY ACCESSING THEM THROUGH THE DUCT HOUSING FRONT
<br />COVER.
<br />8.WHERE INDICATED A NEMA 4X WEATHERPROOF DUCT HOUSING ENCLOSURE SHALL
<br />PROVIDE FOR THE CIRCULATION OF CONDITIONED AIR AROUND THE INTERNALLY
<br />MOUNTED ADDRESSABLE DUCT SENSOR HOUSING TO MAINTAIN THE SENSOR
<br />HOUSING AT ITS RATED TEMPERATURE RANGE. THE HOUSING SHALL BE UL LISTED
<br />TO STANDARD 268A.
<br />9.PROVIDE IN-DUCT DETECTOR ASSEMBLY(IES) WITH PHOTOELECTRIC SENSOR:
<br />a.WHERE SAMPLING TUBE DESIGNS ARE NOT APPROPRIATE.
<br />b.WHERE AIR FLOW COVERAGE IS FROM 35-600 FT/MIN.
<br />10.PROVIDE A REMOTE TEST SWITCH (RTS), ON ALL DUCT TYPE DETECTORS WHEN THE
<br />DEVICE'S ALARM LED IS OBSTRUCTED FROM BEING CLEARLY VISIBLE FROM THE
<br />FLOOR OR THE DEVICE IS MOUNTED HIGHER THAN 9' A.F.F.
<br />a.MOUNT RTS BELOW DETECTOR IN THE CEILING OR ON THE NEAREST SIDEWALL
<br />AS DIRECTED BY THE DSFM.
<br />2.04 CONVENTIONAL SYSTEM SMOKE DETECTORS
<br />A.UNLESS OTHERWISE INDICATED, DETECTORS SHALL BE ANALOG-ADDRESSABLE TYPE,
<br />INDIVIDUALLY MONITORED AT THE FACP FOR CALIBRATION, SENSITIVITY, AND ALARM
<br />CONDITION, AND INDIVIDUALLY ADJUSTABLE FOR SENSITIVITY FROM THE FACP,
<br />INTERNET AND PROJECT'S GCC.
<br />2.05 ADDRESSABLE CIRCUIT INTERFACE MODULES
<br />A.ADDRESSABLE CIRCUIT INTERFACE MODULES: ARRANGE TO MONITOR ONE OR MORE
<br />SYSTEM COMPONENTS THAT ARE NOT OTHERWISE EQUIPPED FOR ADDRESSABLE
<br />COMMUNICATION. MODULES SHALL BE USED FOR MONITORING OF WATER FLOW, VALVE
<br />TAMPER, NON-ADDRESSABLE DEVICES, AND FOR CONTROL OF EVACUATION INDICATING
<br />APPLIANCES AND AHU SYSTEMS.
<br />B.ADDRESSABLE CIRCUIT INTERFACE MODULES WILL BE CAPABLE OF MOUNTING IN A
<br />STANDARD ELECTRIC OUTLET BOX. MODULES WILL INCLUDE COVER PLATES TO ALLOW
<br />SURFACE OR FLUSH MOUNTING. MODULES WILL RECEIVE THEIR OPERATING POWER
<br />FROM THE SIGNALING LINE OR A SEPARATE TWO WIRE PAIR RUNNING FROM AN
<br />APPROPRIATE POWER SUPPLY AS REQUIRED.
<br />C.THERE SHALL BE THE FOLLOWING TYPES OF MODULES:
<br />1.TYPE 1: MONITOR CIRCUIT INTERFACE MODULE:
<br />a.FOR CONVENTIONAL 2-WIRE SMOKE DETECTOR AND/OR CONTACT DEVICE
<br />MONITORING WITH CLASS B OR CLASS A WIRING SUPERVISION. THE SUPERVISION
<br />OF THE ZONE WIRING WILL BE CLASS B. THIS MODULE WILL COMMUNICATE
<br />STATUS (NORMAL, ALARM, TROUBLE) TO THE FACP.
<br />b.FOR CONVENTIONAL 4-WIRE SMOKE DETECTOR WITH CLASS B WIRING
<br />SUPERVISION. THE MODULE WILL PROVIDE DETECTOR RESET CAPABILITY AND
<br />OVER-CURRENT POWER PROTECTION FOR THE 4-WIRE DETECTOR. THIS MODULE
<br />WILL COMMUNICATE STATUS (NORMAL, ALARM, TROUBLE) TO THE FACP.
<br />2.TYPE 2: LINE POWERED MONITOR CIRCUIT INTERFACE MODULE:
<br />a.THIS TYPE OF MODULE IS AN INDIVIDUALLY ADDRESSABLE MODULE THAT HAS
<br />BOTH ITS POWER AND ITS COMMUNICATIONS SUPPLIED BY THE TWO WIRE
<br />MULTIPLEXING SIGNALING LINE CIRCUIT. IT PROVIDES LOCATION SPECIFIC
<br />ADDRESSABILITY TO AN INITIATING DEVICE BY MONITORING NORMALLY OPEN
<br />DRY CONTACTS. THIS MODULE SHALL HAVE THE CAPABILITY OF COMMUNICATING
<br />FOUR ZONE STATUS CONDITIONS (NORMAL, ALARM, CURRENT LIMITED, TROUBLE)
<br />TO THE FACP.
<br />b.THIS MODULE SHALL PROVIDE LOCATION SPECIFIC ADDRESSABILITY FOR UP TO
<br />FIVE INITIATING DEVICES BY MONITORING NORMALLY CLOSED OR NORMALLY
<br />OPEN DRY CONTACT SECURITY DEVICES. THE MODULE SHALL COMMUNICATE
<br />FOUR ZONE STATUS CONDITIONS (OPEN, NORMAL, ABNORMAL, AND SHORT). THE
<br />TWO-WIRE SIGNALING LINE CIRCUIT SHALL SUPPLY POWER AND
<br />COMMUNICATIONS TO THE MODULE.
<br />3.TYPE 3: SINGLE ADDRESS MULTI-POINT INTERFACE MODULES:
<br />a.THIS MULTIPOINT MODULE SHALL PROVIDE LOCATION SPECIFIC ADDRESSABILITY
<br />FOR FOUR INITIATING CIRCUITS AND CONTROL TWO OUTPUT RELAYS FROM A
<br />SINGLE ADDRESS. INPUTS SHALL PROVIDE SUPERVISED MONITORING OF
<br />NORMALLY OPEN, DRY CONTACTS AND BE CAPABLE OF COMMUNICATING FOUR
<br />ZONE STATUS CONDITIONS (NORMAL, OPEN, CURRENT LIMITED, AND SHORT). THE
<br />INPUT CIRCUITS AND OUTPUT RELAY OPERATION SHALL BE CONTROLLED
<br />INDEPENDENTLY AND DISABLED SEPARATELY.
<br />b.THIS DUAL POINT MODULE SHALL PROVIDE A SUPERVISED MULTI-STATE INPUT
<br />AND A RELAY OUTPUT, USING A SINGLE ADDRESS. THE INPUT SHALL PROVIDE
<br />SUPERVISED MONITORING OF TWO NORMALLY OPEN, DRY CONTACTS WITH A
<br />SINGLE POINT AND BE CAPABLE OF COMMUNICATING FOUR ZONE STATUS
<br />CONDITIONS (NORMAL, OPEN, CURRENT LIMITED, AND SHORT). THE TWO-WIRE
<br />SIGNALING LINE CIRCUIT SHALL SUPPLY POWER AND COMMUNICATIONS TO THE
<br />MODULE.
<br />c.THIS DUAL POINT MODULE SHALL MONITOR AN UNSUPERVISED NORMALLY OPEN,
<br />DRY CONTACT WITH ONE POINT AND CONTROL AN OUTPUT RELAY WITH THE
<br />OTHER POINT, USING A SINGLE ADDRESS. THE TWO-WIRE SIGNALING LINE
<br />CIRCUIT SHALL SUPPLY POWER AND COMMUNICATIONS TO THE MODULE.
<br />4.TYPE 4: LINE POWERED CONTROL CIRCUIT INTERFACE MODULE: THIS MODULE SHALL
<br />PROVIDE CONTROL AND STATUS TRACKING OF A FORM "C" CONTACT. THE TWO-WIRE
<br />SIGNALING LINE CIRCUIT SHALL SUPPLY POWER AND COMMUNICATIONS TO THE
<br />MODULE.
<br />5.TYPE 5: 4-20 MA ANALOG MONITOR CIRCUIT INTERFACE MODULE: THIS MODULE
<br />SHALL COMMUNICATE THE STATUS OF A COMPATIBLE 4-20 MA SENSOR TO THE FACP.
<br />THE FACP SHALL ANNUNCIATE UP TO THREE THRESHOLD LEVELS, EACH WITH
<br />CUSTOM ACTION MESSAGE; DISPLAY AND ARCHIVE ACTUAL SENSOR ANALOG
<br />LEVELS; AND PERMIT SENSOR CALIBRATION DATE RECORDING.
<br />D.ALL CIRCUIT INTERFACE MODULES SHALL BE SUPERVISED AND UNIQUELY IDENTIFIED BY
<br />THE CONTROL UNIT. MODULE IDENTIFICATION SHALL BE TRANSMITTED TO THE CONTROL
<br />UNIT FOR PROCESSING ACCORDING TO THE PROGRAM INSTRUCTIONS. MODULES SHALL
<br />HAVE AN ON-BOARD LED TO PROVIDE AN INDICATION THAT THE MODULE IS POWERED
<br />AND COMMUNICATING WITH THE FACP. THE LEDS SHALL PROVIDE A TROUBLESHOOTING
<br />AID SINCE THE LED BLINKS ON POLL WHENEVER THE PERIPHERAL IS POWERED AND
<br />COMMUNICATING.
<br />2.06 ADDRESSABLE ALARM NOTIFICATION APPLIANCES
<br />A.ADDRESSABLE NOTIFICATION APPLIANCES:
<br />1.THE CONTRACTOR SHALL FURNISH AND INSTALL ADDRESSABLE NOTIFICATION
<br />APPLIANCES AND ACCESSORIES TO OPERATE ON COMPATIBLE SIGNALING LINE
<br />CIRCUITS (SLC).
<br />2.ADDRESSABLE NOTIFICATION APPLIANCE OPERATION SHALL PROVIDE POWER,
<br />SUPERVISION AND SEPARATE CONTROL OF HORNS AND STROBES OVER A SINGLE
<br />PAIR OF WIRES. THE CONTROLLING CHANNEL (SLC) DIGITALLY COMMUNICATES WITH
<br />EACH APPLIANCE AND RECEIVES A RESPONSE TO VERIFY THE APPLIANCE'S
<br />PRESENCE ON THE CHANNEL. THE CHANNEL PROVIDES A DIGITAL COMMAND TO
<br />CONTROL APPLIANCE OPERATION. SLC CHANNEL WIRING SHALL BE UNSHIELDED
<br />TWISTED PAIR (UTP), WITH A CAPACITANCE RATING OF LESS THAN 60PF/FT. AND A
<br />MINIMUM 3 TWISTS (TURNS) PER FOOT.
<br />3.CLASS B (STYLE 4) NOTIFICATION APPLIANCES SHALL BE WIRED WITHOUT REQUIRING
<br />TRADITIONAL IN/OUT WIRING METHODS; ADDRESSABLE "T" TAPPING SHALL BE
<br />PERMITTED. UP TO 63 APPLIANCES CAN BE SUPPORTED ON A SINGLE CHANNEL.
<br />4.EACH ADDRESSABLE NOTIFICATION APPLIANCE SHALL CONTAIN AN ELECTRONIC
<br />MODULE AND A SELECTABLE ADDRESS SETTING TO ALLOW IT TO OCCUPY A UNIQUE
<br />LOCATION ON THE CHANNEL. THIS ON-BOARD MODULE SHALL ALSO ALLOW THE
<br />CHANNEL TO PERFORM APPLIANCE DIAGNOSTICS THAT ASSIST WITH INSTALLATION
<br />AND SUBSEQUENT TEST OPERATIONS. A VISIBLE LED ON EACH APPLIANCE SHALL
<br />PROVIDE VERIFICATION OF COMMUNICATIONS AND SHALL FLASH WITH THE
<br />APPLIANCES ADDRESS SETTING WHEN LOCALLY REQUESTED USING A MAGNETIC
<br />TEST TOOL.
<br />5.ADDRESSABLE CONTROLLER:
<br />a.ADDRESSABLE CONTROLLER SHALL SUPERVISE CHANNEL (SLC) WIRING,
<br />COMMUNICATE WITH AND CONTROL ADDRESSABLE NOTIFICATION APPLIANCES.
<br />IT SHALL BE POSSIBLE TO PROGRAM THE HIGH/LOW SETTING OF THE AUDIBLE
<br />(HORN) APPLIANCES BY CHANNEL FROM THE ADDRESSABLE CONTROLLER.
<br />6.HORN:
<br />a.ADDRESSABLE HORN SHALL BE LISTED TO UL 464. HORN APPLIANCES SHALL
<br />HAVE A HIGH/LOW SETTING, PROGRAMMABLE BY CHANNEL FROM THE
<br />ADDRESSABLE CONTROLLER OR BY APPLIANCE FROM THE HOST FACP. THE
<br />HORN SHALL HAVE A MINIMUM SOUND PRESSURE LEVEL OF 83 OR 89 DBA @
<br />24VDC. THE HORN SHALL MOUNT DIRECTLY TO A STANDARD SINGLE GANG,
<br />DOUBLE GANG OR 4" SQUARE ELECTRICAL BOX, WITHOUT THE USE OF SPECIAL
<br />ADAPTER OR TRIM RINGS.
<br />b.APPLIANCES SHALL BE WIRED WITH UTP CONDUCTORS, HAVING A MINIMUM OF 3
<br />TWISTS PER FOOT.
<br />7.VISIBLE/ONLY:
<br />a.ADDRESSABLE STROBE SHALL BE LISTED TO UL 1971. THE V/O SHALL CONSIST OF
<br />A XENON FLASH TUBE AND ASSOCIATED LENS/REFLECTOR SYSTEM. THE WALL
<br />MOUNT V/O ENCLOSURE SHALL MOUNT DIRECTLY TO STANDARD SINGLE GANG,
<br />DOUBLE GANG OR 4" SQUARE ELECTRICAL BOX, WITHOUT THE USE OF SPECIAL
<br />ADAPTERS OR TRIM RINGS. THE CEILING MOUNT V/O SHALL MOUNT TO A SINGLE
<br />GANG ELECTRICAL BOX.
<br />b.APPLIANCES SHALL BE WIRED WITH UTP CONDUCTORS, HAVING A MINIMUM OF 3
<br />TWISTS PER FOOT. V/O APPLIANCES SHALL BE PROVIDED WITH DIFFERENT
<br />MINIMUM FLASH INTENSITIES OF 15CD, 75CD AND 110CD. PROVIDE A LABEL INSIDE
<br />THE STROBE LENS TO INDICATE THE LISTED CANDELA RATING OF THE SPECIFIC
<br />VISIBLE/ONLY APPLIANCE.
<br />8.AUDIBLE/VISIBLE:
<br />a.ADDRESSABLE COMBINATION AUDIBLE/VISIBLE (A/V) NOTIFICATION APPLIANCES
<br />SHALL BE LISTED TO UL 1971 AND UL 464. THE STROBE LIGHT SHALL CONSIST OF
<br />A XENON FLASH TUBE AND ASSOCIATED LENS/REFLECTOR SYSTEM. PROVIDE A
<br />LABEL INSIDE THE STROBE LENS TO INDICATE THE LISTED CANDELA RATING OF
<br />THE SPECIFIC STROBE. THE HORN SHALL HAVE A MINIMUM SOUND PRESSURE
<br />LEVEL OF 83 OR 89 DBA @ 24VDC. THE AUDIBLE/VISIBLE ENCLOSURE SHALL
<br />MOUNT DIRECTLY TO STANDARD SINGLE GANG, DOUBLE GANG OR 4" SQUARE
<br />ELECTRICAL BOX, WITHOUT THE USE OF SPECIAL ADAPTERS OR TRIM RINGS.
<br />b.APPLIANCES SHALL BE WIRED WITH UTP CONDUCTORS, HAVING A MINIMUM OF 3
<br />TWISTS PER FOOT.
<br />c.THE APPLIANCE SHALL BE CAPABLE OF TWO-WIRE SYNCHRONIZATION WITH ONE
<br />OF THE FOLLOWING OPTIONS:
<br />1)SYNCHRONIZED STROBE WITH HORN ON STEADY.
<br />2)SYNCHRONIZED STROBE WITH TEMPORAL CODE PATTERN ON HORN.
<br />3)SYNCHRONIZED STROBE WITH MARCH TIME CADENCE ON HORN.
<br />4)SYNCHRONIZED STROBE FIRING TO NAC SYNC SIGNAL WITH HORN SILENCED.
<br />9.SPEAKER/VISIBLE:
<br />a.COMBINATION SPEAKER/VISIBLE (S/V) UNITS COMBINE THE SPEAKER AND VISIBLE
<br />FUNCTIONS INTO A COMMON HOUSING. THE S/V SHALL BE LISTED TO UL 1971 AND
<br />UL 1480. ADDRESSABLE FUNCTIONALITY CONTROLS VISIBLE OPERATION, WHILE
<br />THE SPEAKER OPERATES ON A 25VRMS OR 70.7VRMS NAC.
<br />b.TWISTED/SHIELDED WIRE IS REQUIRED FOR SPEAKER CONNECTIONS ON A
<br />STANDARD 25VRMS OR 70.7VRMS NAC USING AND UTP CONDUCTORS, HAVING A
<br />MINIMUM OF 3 TWISTS PER FOOT IS REQUIRED FOR ADDRESSABLE STROBE
<br />CONNECTIONS.
<br />c.AT THE 1.0W TAP, THE SPEAKER SHALL HAVE A MINIMUM UL RATED SOUND
<br />PRESSURE LEVEL OF 84DBA AT 10 FEET.
<br />d.THE S/V SHALL HAVE A FREQUENCY RESPONSE OF 400 TO 4000 HZ FOR FIRE
<br />ALARM AND 125 TO 12KHZ FOR GENERAL SIGNALING.
<br />e.THE S/V INSTALLS DIRECTLY TO A 4" SQUARE, 1 1/2 IN. DEEP ELECTRICAL BOX
<br />WITH 1 1/2" EXTENSION.
<br />10.ISOLATOR MODULE:
<br />a.ISOLATOR MODULE PROVIDES SHORT CIRCUIT ISOLATION FOR ADDRESSABLE
<br />NOTIFICATION APPLIANCE SLC WIRING. ISOLATOR SHALL BE LISTED TO UL 864.
<br />THE ISOLATOR SHALL MOUNT DIRECTLY TO A MINIMUM 2 1/8" DEEP, STANDARD 4"
<br />SQUARE ELECTRICAL BOX, WITHOUT THE USE OF SPECIAL ADAPTER OR TRIM
<br />RINGS.
<br />b.POWER AND COMMUNICATIONS SHALL BE SUPPLIED BY THE ADDRESSABLE
<br />CONTROLLER CHANNEL SLC; DUAL PORT DESIGN SHALL ACCEPT
<br />COMMUNICATIONS AND POWER FROM EITHER PORT AND SHALL AUTOMATICALLY
<br />ISOLATE ONE PORT FROM THE OTHER WHEN A SHORT CIRCUIT OCCURS.
<br />c.THE FOLLOWING FUNCTIONALITY SHALL BE INCLUDED IN THE ISOLATOR MODULE:
<br />1)REPORT FAULTS TO THE HOST FACP.
<br />2)ON-BOARD YELLOW LED PROVIDES MODULE STATUS.
<br />3)AFTER THE WIRING FAULT IS REPAIRED, THE ISOLATOR MODULES SHALL TEST
<br />THE LINES AND AUTOMATICALLY RESTORE THE CONNECTION.
<br />B.TRUEALERT ADDRESSABLE APPLIANCES NAC POWER EXTENDER:
<br />1.THE TRUEALERT ADDRESSABLE CONTROLLER SHALL BE A STAND-ALONE PANEL
<br />CAPABLE OF POWERING A MINIMUM OF 3 TRUEALERT SIGNALING LINE CIRCUITS.
<br />EACH CHANNEL SHALL BE RATED FOR 2.5 AMPS AND SUPPORT UP TO 63 TRUEALERT
<br />ADDRESSABLE NOTIFICATION APPLIANCES. POWER AND COMMUNICATION FOR THE
<br />NOTIFICATION APPLIANCES SHALL BE PROVIDED ON THE SAME PAIR OF WIRES.
<br />2.ADDRESSABLE SLC NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B STYLE 4.
<br />UNLESS NOTED ELSEWHERE.
<br />3.THE INTERNAL POWER SUPPLY & BATTERY CHARGER SHALL BE CAPABLE OF
<br />CHARGING UP 12.7 AH BATTERIES INTERNALLY MOUNTED OR 18AH BATTERIES
<br />MOUNTED IN AN EXTERNAL CABINET.
<br />4.THE NAC EXTENDER PANEL MAY BE MOUNTED CLOSE TO THE HOST CONTROL PANEL
<br />OR CAN BE REMOTELY LOCATED.
<br />2.07 NON ADDRESSABLE NOTIFICATION APPLIANCES
<br />A.DESCRIPTION:
<br />1.EQUIPPED FOR MOUNTING AS INDICATED AND WITH SCREW TERMINALS FOR SYSTEM
<br />CONNECTIONS.
<br />a.COMBINATION DEVICES:
<br />b.FACTORY-INTEGRATED AUDIBLE AND VISIBLE DEVICES IN A SINGLE-MOUNTING
<br />ASSEMBLY.
<br />2.GENERAL ALARM HORN:
<br />a.ELECTRIC-VIBRATING-POLARIZED TYPE, 24-V DC; HORNS SHALL PRODUCE A
<br />SOUND-PRESSURE LEVEL OF 87 DBA, MEASURED 10 FEET FROM THE HORN.
<br />SOUND LEVEL FOR EACH DEVICE SHALL BE SELECTABLE AT THE DEVICE. HORNS
<br />SHALL BE PROVIDED WITH WEATHERPROOF BACK BOX WHERE INDICATED.
<br />2.08 GUARDS FOR PHYSICAL PROTECTION
<br />A.DESCRIPTION:
<br />4.WELDED WIRE MESH OF SIZE AND SHAPE FOR THE MANUAL STATION, SMOKE
<br />DETECTOR, GONG, OR OTHER DEVICE REQUIRING PROTECTION.
<br />5.FACTORY FABRICATED AND FURNISHED BY MANUFACTURER OF THE DEVICE.
<br />6.FINISH: PAINT OF COLOR TO MATCH THE PROTECTED DEVICE.
<br />2.09 WIRE, CABLE, AND FIBER
<br />A. WIRE AND CABLE FOR FIRE ALARM SYSTEMS SHALL BE UL LISTED AND LABELED AS
<br />COMPLYING WITH NFPA 70, ARTICLE 760.
<br />B. SIGNALING LINE CIRCUITS: TWISTED, SHIELDED PAIR, SIZED AS RECOMMENDED BY
<br />SYSTEM MANUFACTURER.
<br />C.NON-POWER-LIMITED CIRCUITS: SOLID-COPPER CONDUCTORS WITH 600-V RATED, 75
<br />DEGREES C, COLOR-CODED INSULATION.
<br />1.LOW-VOLTAGE COMMUNICATION CIRCUITS: NO. 18 AWG, MINIMUM.
<br />2.LOW-VOLTAGE POWER CIRCUITS: NO. 14 AWG, MINIMUM.
<br />3.LINE-VOLTAGE CIRCUITS: NO. 12 AWG, MINIMUM.
<br />4.MULTI-CONDUCTOR ARMORED CABLE: NFPA 70 RED LIGHTWEIGHT STEEL TYPE MC,
<br />COPPER CONDUCTORS, TFN/THHN CONDUCTOR INSULATION, COPPER DRAIN WIRE,
<br />COPPER ARMOR WITH RED IDENTIFIER STRIPE, UL LISTED FOR FIRE ALARM AND
<br />CABLE TRAY INSTALLATION, PLENUM RATED, AND COMPLYING WITH REQUIREMENTS
<br />IN UL 2196 FOR A 2-HOUR RATING.
<br />PART 3 - EXECUTION
<br />3.01 EQUIPMENT INSTALLATION
<br />A.COMPLY WITH THE LATEST EDITION OF NFPA 72 AND UL 864 REQUIREMENTS FOR
<br />INSTALLATION OF FIRE-ALARM SYSTEM.
<br />B.EQUIPMENT MOUNTING: INSTALL FIRE ALARM DEVICES AND CONTROLLERS AS
<br />RECOMMENDED BY THE MANUFACTURER.
<br />C.INSTALL SEISMIC BRACING: COMPLY WITH THE REQUIREMENTS IN DIVISION 26 SECTION
<br />REGARDING VIBRATION AND SEISMIC CONTROL FOR ELECTRICAL SYSTEMS.
<br />D.SMOKE OR HEAT DETECTOR SPACING:
<br />1.SMOOTH CEILING SPACING SHALL NOT EXCEED THE RATING OF THE DETECTOR.
<br />2.SPACING OF HEAT DETECTORS FOR IRREGULAR AREAS, FOR IRREGULAR CEILING
<br />CONSTRUCTION, AND FOR HIGH CEILING AREAS, SHALL BE DETERMINED ACCORDING
<br />TO APPENDIX A IN NFPA 72.
<br />3.SPACING OF HEAT DETECTORS SHALL BE DETERMINED BASED ON GUIDELINES AND
<br />RECOMMENDATIONS IN NFPA 72.
<br />E.SMOKE DETECTOR LOCATION: LOCATE DETECTORS NOT CLOSER THAN 3 FEET FROM
<br />AIR-SUPPLY DIFFUSER OR RETURN-AIR OPENING. LOCATE DETECTOR NOT CLOSER THAN
<br />12 INCHES FROM ANY PART OF A LIGHTING FIXTURE.
<br />F.DUCT SMOKE DETECTORS: COMPLY WITH NFPA 72, NFPA 90A AND THE MANUFACTURE
<br />RECOMMENDATIONS. INSTALL SAMPLING TUBES SO THEY EXTEND THE FULL WIDTH OF
<br />THE DUCT.
<br />G.SINGLE-STATION SMOKE DETECTORS: WHERE MORE THAN ONE SMOKE ALARM IS
<br />INSTALLED WITHIN A DWELLING OR SUITE, THEY SHALL BE CONNECTED SO THAT THE
<br />OPERATION OF ANY SMOKE ALARM IN THE DWELLING OR SUITE CAUSES ALL THE SMOKE
<br />ALARM IN THE DWELLING OR SUIT TO SOUND A TEMPORAL PATTERN.
<br />H.REMOTE STATUS AND ALARM INDICATORS: INSTALL NEAR EACH SMOKE DETECTOR AND
<br />EACH SPRINKLER WATER-FLOW SWITCH AND VALVE-TAMPER SWITCH THAT IS NOT
<br />READILY VISIBLE FROM NORMAL VIEWING POSITION.
<br />I.AUDIBLE ALARM-INDICATING DEVICES: INSTALL NOT LESS THAN 6 INCHES BELOW THE
<br />CEILING. INSTALL HORNS ON FLUSH-MOUNTED BACK BOXES. WEATHERPROOF DEVICES
<br />ARE TO BE MOUNTED ON WEATHERPROOF SURFACE BACK BOX.
<br />J.VISIBLE ALARM-INDICATING DEVICES (STROBES): INSTALL SO THAT THE ENTIRE LENS IS
<br />MORE THAN 80 INCHES BUT LESS THAN 96 INCHES ABOVE THE FINISHED FLOOR.
<br />1.EXCEPTION: WALL MOUNTED STROBES IN SLEEPING AREAS SHALL BE MOUNTED AT
<br />LEAST 24 INCHES BELOW THE CEILING AND WITHIN 16FT OF THE OCCUPANT'S
<br />PILLOW.
<br />L.COMBINATION AUDIBLE/VISUAL DEVICES: MOUNT AT VISIBLE DEVICE HEIGHTS.
<br />3.02 FIBER AND WIRING INSTALLATION
<br />A.INSTALL WIRING ACCORDING TO THE FOLLOWING:
<br />1.NECA 1.
<br />2.TIA/EIA 568-A.
<br />3.NFPA, CBC, FCC, RFI/EMI.
<br />B.WIRING METHOD:
<br />1.INSTALL WIRING IN METAL RACEWAY ACCORDING TO DIVISION 26 SECTION
<br />"RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS."
<br />2.FIRE ALARM CIRCUITS AND EQUIPMENT CONTROL WIRING ASSOCIATED WITH THE
<br />FIRE ALARM SYSTEM SHALL BE INSTALLED IN A DEDICATED RACEWAY SYSTEM. THIS
<br />SYSTEM SHALL NOT BE USED FOR ANY OTHER WIRE OR CABLE.
<br />C.WIRING METHOD:
<br />1.FIRE-RATED CABLES: USE OF 2-HOUR FIRE-RATED FIRE ALARM CABLES, NFPA 70
<br />TYPES MI AND CI, IS NOT PERMITTED.
<br />2.SIGNALING LINE CIRCUITS: POWER-LIMITED FIRE ALARM CABLES SHALL BE INSTALLED
<br />IN THE SAME CABLE OR RACEWAY AS SIGNALING LINE CIRCUITS.
<br />D.WIRING WITHIN ENCLOSURES: SEPARATE POWER-LIMITED AND NON-POWER-LIMITED
<br />CONDUCTORS AS RECOMMENDED BY MANUFACTURER. INSTALL CONDUCTORS
<br />PARALLEL WITH OR AT RIGHT ANGLES TO SIDES AND BACK OF THE ENCLOSURE.
<br />BUNDLE, LACE, AND TRAIN CONDUCTORS TO TERMINAL POINTS WITH NO EXCESS.
<br />CONNECT CONDUCTORS THAT ARE TERMINATED, SPLICED, OR INTERRUPTED IN ANY
<br />ENCLOSURE ASSOCIATED WITH THE FIRE ALARM SYSTEM TO TERMINAL BLOCKS. MARK
<br />EACH TERMINAL ACCORDING TO THE SYSTEM'S WIRING DIAGRAMS. MAKE ALL
<br />CONNECTIONS WITH APPROVED CRIMP-ON TERMINAL SPADE LUGS, PRESSURE-TYPE
<br />TERMINAL BLOCKS, OR PLUG CONNECTORS.
<br />E.CABLE TAPS: USE NUMBERED TERMINAL STRIPS IN JUNCTION, PULL, AND OUTLET BOXES,
<br />CABINETS, OR EQUIPMENT ENCLOSURES WHERE CIRCUIT CONNECTIONS ARE MADE.
<br />F.COLOR-CODING: COLOR-CODE FIRE ALARM CONDUCTORS AS SHOWN ON THE FIRE
<br />ALARM PLANS. USE ONE COLOR-CODE FOR ALARM CIRCUIT WIRING AND A DIFFERENT
<br />COLOR-CODE FOR SUPERVISORY CIRCUITS. COLOR-CODE AUDIBLE ALARM-INDICATING
<br />CIRCUITS DIFFERENTLY FROM ALARM-INITIATING CIRCUITS. USE DIFFERENT COLORS
<br />FOR VISIBLE ALARM-INDICATING DEVICES. PAINT FIRE ALARM SYSTEM JUNCTION BOXES
<br />AND COVERS RED.
<br />G.WIRING TO REMOTE ALARM TRANSMITTING DEVICE:
<br />1.3/4-INCH CONDUIT BETWEEN THE FACP AND THE TRANSMITTER.
<br />2.INSTALL NUMBER OF CONDUCTORS AND ELECTRICAL SUPERVISION FOR
<br />CONNECTING WIRING AS NEEDED TO SUIT MONITORING FUNCTION.
<br />3.03 IDENTIFICATION
<br />A.IDENTIFY SYSTEM COMPONENTS, WIRING, CABLING, AND TERMINALS ACCORDING TO
<br />DIVISION 26.
<br />B.OPERATING INSTRUCTIONS: FRAME IN A LOCATION VISIBLE FROM THE FACP.
<br />C.PAINT POWER-SUPPLY DISCONNECT SWITCH RED AND LABEL "FIRE ALARM."
<br />3.04 GROUNDING
<br />A.GROUND THE FACP AND ASSOCIATED CIRCUITS; COMPLY WITH IEEE 1100. INSTALL A
<br />GROUND WIRE FROM MAIN SERVICE GROUND TO THE FACP.
<br />3.05 FIELD QUALITY CONTROL
<br />A.FINAL ACCEPTANCE TESTING SHALL BE WITNESSED BY THE OWNER'S REPRESENTATIVE.
<br />B.A FINAL PRE-TEST SHALL BE WITNESSED BY THE OWNER'S REPRESENTATIVE.
<br />C.MANUFACTURER'S FIELD SERVICE:
<br />1.ENGAGE A FACTORY-AUTHORIZED INSTALLATION REPRESENTATIVE TO ASSIST
<br />DURING THE INSTALLATION, PRE-TESTING AND ADJUST OF THE FIRE ALARM SYSTEM
<br />AND FIELD DEVICES, COMPONENTS AND EQUIPMENT.
<br />2.INCLUDE A MANUFACTURER'S FIELD REPRESENTATIVE DURING ALL FINAL
<br />ACCEPTANCE TESTING.
<br />D.PERFORM THE FOLLOWING FIELD TESTS AND INSPECTIONS AND PREPARE TEST
<br />REPORTS:
<br />1.BEFORE REQUESTING FINAL ACCEPTANCE TESTING AND APPROVAL OF THE
<br />INSTALLATION, SUBMIT A WRITTEN STATEMENT USING THE FORM FOR RECORD OF
<br />COMPLETION SHOWN IN NFPA 72.
<br />2.PERFORM EACH ELECTRICAL TEST AND VISUAL AND MECHANICAL INSPECTION
<br />LISTED IN NFPA 72. CERTIFY COMPLIANCE WITH TEST PARAMETERS. ALL TESTS
<br />SHALL BE CONDUCTED UNDER THE DIRECT SUPERVISION OF A NICET TECHNICIAN
<br />CERTIFIED UNDER THE FIRE ALARM SYSTEMS PROGRAM AT LEVEL II.
<br />3.VISUAL INSPECTION: CONDUCT A VISUAL INSPECTION BEFORE ANY TESTING. USE
<br />AS-BUILT DRAWINGS AND SYSTEM DOCUMENTATION FOR THE INSPECTION. IDENTIFY
<br />IMPROPERLY LOCATED, DAMAGED, OR NONFUNCTIONAL EQUIPMENT, AND CORRECT
<br />BEFORE BEGINNING TESTS.
<br />4.TESTING: FOLLOW PROCEDURE AND RECORD RESULTS COMPLYING WITH
<br />REQUIREMENTS IN NFPA 72. DETECTORS THAT ARE OUTSIDE THEIR MARKED
<br />SENSITIVITY RANGE SHALL BE REPLACED.
<br />5.TEST AND INSPECTION RECORDS:
<br />a.PREPARE ACCORDING TO NFPA 72, INCLUDING DEMONSTRATION OF SEQUENCES
<br />OF OPERATION BY USING THE MATRIX-STYLE FORM IN APPENDIX A IN NFPA 70.
<br />b.PROVIDE REPORT RESULTS IN WRITING ON COMPUTER GENERATED FORMS.
<br />3.06 ADJUSTING
<br />A.OCCUPANCY ADJUSTMENTS: WHEN REQUESTED WITHIN 12 MONTHS OF DATE OF
<br />SUBSTANTIAL COMPLETION, PROVIDE ON-SITE ASSISTANCE IN ADJUSTING SYSTEM TO
<br />SUIT ACTUAL OCCUPIED CONDITIONS. PROVIDE UP TO TWO VISITS TO PROJECT OUTSIDE
<br />NORMAL OCCUPANCY HOURS FOR THIS PURPOSE.
<br />B.FOLLOW-UP TESTS AND INSPECTIONS: AFTER DATE OF SUBSTANTIAL COMPLETION, TEST
<br />THE FIRE ALARM SYSTEM COMPLYING WITH TESTING AND VISUAL INSPECTION
<br />REQUIREMENTS IN NFPA 72.
<br />3.07 DEMONSTRATION
<br />A.ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN THE OWNER'S
<br />MAINTENANCE PERSONNEL TO ADJUST, OPERATE, AND MAINTAIN THE FIRE ALARM
<br />SYSTEM, APPLIANCES, AND DEVICES.
<br />Sheet No.
<br />Project
<br />Agency Plan Check / Permit No.
<br />Petersen Design Project No.
<br />Consultant
<br />5082.1
<br />652 East Dyer Drive
<br />Santa Ana, CA 92705
<br />DYER WAREHOUSE
<br />Staging & Set-Up Space
<br />Tenant Improvements
<br />Sheet Title
<br />Revision / Submittal History
<br />Scale
<br />Status
<br />.
<br />architecture + planning
<br />Agency Approval
<br />Petersen Design Architects, Inc.
<br />17582 Fiesta Way, Tustin, CA 92780
<br />M: 714.904.6720 E: mike@mpdarch.com
<br />www.mpdarch.com
<br />Architect's Stamp
<br />.
<br />255 E. Rincon St., Suite 301
<br />Corona, CA 92879
<br />P 951.340.1977 | F 951.340.1090
<br />www.gossengineering.com
<br />CALOFI
<br />GI
<br />RE
<br />NG
<br />A
<br />E
<br />S
<br />No. E17083
<br />T
<br />E
<br />ET
<br />SAT L CE A
<br />F
<br />RIC L
<br />ORNI
<br />EPR
<br />RAET
<br />RED D.D
<br />OF ONABR
<br />L
<br />SSI
<br />NE
<br />RE
<br />IWD
<br />UT
<br />HCE
<br />Project Number: 125-09-07
<br />Date Signed 01-09-2026
<br />1 01/09/2026 PLAN CHECK RESUBMITTAL
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />E7.4
|