SECTION 28 3111 <br />DIGITAL ADDRESSABLE FIRE-ALARM SYSTEM <br />PART 1 - GENERAL <br />1.01 SUMMARY <br />A.SECTION INCLUDES: <br />1.FIRE ALARM CONTROL UNIT. <br />2.MANUAL FIRE ALARM BOXES. <br />3.ANALOG SENSORS. <br />4.CONVENTIONAL DETECTORS. <br />5.MISCELLANEOUS DETECTION. <br />6.ADDRESSABLE MODULES. <br />7.NOTIFICATION APPLIANCES. <br />8.ADDRESSABLE INTERFACE MODULES. <br />1.02 DEFINITIONS <br />A.DEFINITIONS IN NFPA 72 AND UL 864 ARE INCLUSIVE TO THIS SECTION. <br />B.LED: LIGHT-EMITTING DIODE. <br />C.NICET: NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES. <br />D.FACP: MAIN FIRE ALARM CONTROL PANEL. <br />E.MINIPLEX: REMOTE INPUT/OUTPUT PANEL CONNECTED TO A FACP VIA REMOTE UNIT <br />INTERFACE. <br />F.TPS: AN ADDRESSABLE NOTIFICATION POWER SUPPLY MOUNTED IN AN FACP <br />ENCLOSURE. <br />G.RPS: REMOTE POWER SUPPLY FOR CONVENTIONAL HORNS AND STROBES. <br />1.03 SYSTEM DESCRIPTION <br />A.NON-CODED, UL 864 9TH EDITION, UL-CERTIFIED ANALOG-ADDRESSABLE SYSTEM WITH <br />AUTOMATIC SENSITIVITY CONTROL OF SYSTEM SMOKE DETECTORS AT THE MAIN PANEL <br />AND THE GCC. <br />1.04 PERFORMANCE REQUIREMENTS <br />A.COMPLY WITH NFPA 72. <br />B.UL LISTED AND LABELED. <br />C.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: LISTED AND LABELED AS <br />DEFINED IN NFPA 70, BY A QUALIFIED TESTING AGENCY, AND MARKED FOR INTENDED <br />LOCATION AND APPLICATION. <br />D.SEISMIC PERFORMANCE FACP AND RACEWAYS SHALL WITHSTAND THE EFFECTS OF <br />EARTHQUAKE MOTIONS DETERMINED ACCORDING TO THE VIBRATION AND SEISMIC <br />CONTROLS FOR ELECTRICAL SYSTEM SPECIFICATION SECTION. <br />1.05 SUBMITTALS <br />A.GENERAL SUBMITTAL REQUIREMENTS: <br />1.SUBMITTALS: PRODUCT DATA AND SYSTEM OPERATING DESCRIPTION. <br />2.SUBMITTALS TO AUTHORITIES HAVING JURISDICTION: IN ADDITION TO DISTRIBUTION <br />REQUIREMENTS FOR SUBMITTALS, MAKE AN IDENTICAL SUBMITTAL TO AUTHORITIES <br />HAVING JURISDICTION. TO FACILITATE REVIEW, INCLUDE COPIES OF ANNOTATED <br />CONTRACT DRAWINGS AS NEEDED TO DEPICT COMPONENT LOCATIONS. <br />3.SHOP DRAWINGS SHALL BE PREPARED BY PERSONS WITH THE FOLLOWING <br />QUALIFICATIONS: <br />a.TRAINED AND CERTIFIED BY MANUFACTURER IN FIRE ALARM SYSTEM DESIGN. <br />b.FIRE ALARM CERTIFIED BY NICET, MINIMUM LEVEL II. <br />B.PRODUCT DATA: <br />1.PROVIDE MANUFACTURES DATA SHEETS AND SFM LISTING SHEETS FOR ALL <br />PRODUCTS. <br />C.SHOP DRAWINGS: <br />1.FIRE ALARM SYSTEM: <br />a.INCLUDE PLANS, ELEVATIONS, SECTIONS, DETAILS, RISER DIAGRAMS GENERAL <br />NOTES, LOCATION, SCOPE OF THE WORK AND ATTACHMENTS TO OTHER WORK. <br />b.SYSTEM OPERATION DESCRIPTION: DETAILED DESCRIPTION FOR THIS PROJECT, <br />INCLUDING METHOD OF OPERATION AND SUPERVISION OF EACH TYPE OF <br />CIRCUIT AND SEQUENCE OF OPERATIONS FOR MANUALLY AND AUTOMATICALLY <br />INITIATED SYSTEM INPUTS AND OUTPUTS. MANUFACTURER'S STANDARD <br />DESCRIPTIONS FOR GENERIC SYSTEMS ARE NOT ACCEPTABLE. <br />c.COMPLY WITH RECOMMENDATIONS IN THE “DOCUMENTATION” SECTION OF THE <br />“FUNDAMENTALS OF FIRE ALARM SYSTEMS” CHAPTER IN NFPA 72. <br />d.INCLUDE VOLTAGE DROP CALCULATIONS FOR ALL NOTIFICATION APPLIANCE <br />CIRCUIT. <br />1)WORST CASE ONLY CALCULATIONS ARE NOT ACCEPTABLE. <br />e.INCLUDE BATTERY-SIZE CALCULATION(S) WITH STAND-BY AND ALARM LOADS FOR <br />ALL COMPONENTS. <br />f.INCLUDE ELECTRICAL PANEL AND CIRCUIT NUMBER FOR ALL 120VAC SOURCES. <br />g.DEVICE ADDRESS: <br />1)SHOW THE ADDRESS FOR EACH ADDRESSABLE DEVICE SHOWN ON THE <br />PLANS. <br />2)COORDINATE CUSTOM DEVICE LABEL WITH DCFM PRIOR TO PROGRAMMING <br />LABELS. <br />h.SYSTEM RISER DIAGRAM: SHOW ALL EQUIPMENT, TERMINAL CANS, DEVICES, <br />CONDUIT ROUTING, CABLE ROUTING AND CABLE TYPE AND QUANTITY. PROVIDE <br />LADDER TYPE RISER LAY-OUT WITH ALL INTERCONNECTING CONDUITS. <br />i.WIRING DIAGRAMS: PROVIDE WIRING TYPE, PART NUMBER, MANUFACTURE AND <br />COLOR CODE. <br />j.POWER, SIGNAL, AND CONTROL WIRING: INCLUDE DIAGRAMS FOR EQUIPMENT <br />AND FOR SYSTEM WITH ALL TERMINALS AND INTERCONNECTIONS IDENTIFIED. <br />k.DUCT SMOKE DETECTORS: PROVIDE PERFORMANCE PARAMETERS AND <br />INSTALLATION DETAILS FOR EACH DUCT DETECTOR OR IN-DUCT DETECTOR, <br />PROVIDE THE COMPLETE RANGE OF AIR VELOCITY, TEMPERATURE, AND <br />HUMIDITY ALLOWED FOR PROPER OPERATION. PROVIDE WEATHERPROOF DETAIL <br />FOR ALL ROOF TOP MOUNTED AND/OR EXPOSED DETECTORS. <br />l.DUCTWORK DRAWINGS: SHOW CRITICAL DIMENSIONS THAT RELATE TO <br />PLACEMENT AND SUPPORT OF SAMPLING TUBES, THE DETECTOR HOUSING, AND <br />REMOTE STATUS AND ALARM INDICATORS. LOCATE DETECTORS ON PLANS <br />ACCORDING TO MANUFACTURER'S WRITTEN RECOMMENDATIONS. <br />m.FLOOR PLANS: INDICATE FINAL OUTLET LOCATIONS SHOWING ADDRESS OF EACH <br />ADDRESSABLE DEVICE. SHOW ROUTE OF CABLE AND CONDUITS. <br />n.ROOM NUMBERS: CONFIRM ROOM NUMBERS BEING USED IN PROGRAMMING ARE <br />THE FINAL NUMBERS ASSIGNED BY FACILITIES MANAGEMENT. <br />D.SUBMITTALS TO STATE FIRE MARSHAL (SFM): IN ADDITION TO DISTRIBUTION <br />REQUIREMENTS FOR SUBMITTALS SPECIFIED IN DIVISION 01 SECTION “SUBMITTALS”, <br />MAKE AN IDENTICAL SUBMITTAL TO THE OWNER'S REPRESENTATIVE. TO FACILITATE <br />REVIEW, INCLUDE COPIES OF ANNOTATED CONTRACT DRAWINGS AS NEEDED TO DEPICT <br />COMPONENT LOCATIONS. RESUBMIT AS REQUIRED TO MAKE CLARIFICATIONS OR <br />REVISIONS TO OBTAIN APPROVAL. ON RECEIPT OF COMMENTS FROM STATE FIRE <br />MARSHAL, SUBMIT THEM TO THE OWNER'S REPRESENTATIVE FOR REVIEW. <br />E.RESUBMITTALS: MAKE CORRECTIONS AND RESUBMIT DRAWINGS AS REQUIRED UNTIL <br />THE PLANS ARE REVIEWED AND APPROVED BY THE STATE FIRE MARSHAL. <br />F.DELEGATED-DESIGN SUBMITTALS: THE MECHANICAL ENGINEER OF RECORD WILL <br />COORDINATE THE SPECIFIC LOCATION OF EACH DUCT DETECTOR WITH THE <br />MECHANICAL, ELECTRICAL AND FIRE ALARM CONTRACTORS PRIOR TO THE INSTALLATION <br />OF ANY DUCT MOUNTED DEVICE. <br />1.06 QUALITY ASSURANCE <br />A.INSTALLER QUALIFICATIONS: <br />1.PERSONNEL INSTALLING WIRE, CABLE, DEVICES OR MAKING FINAL CONNECTIONS <br />SHALL BE TRAINED OR SUPERVISED BY THE MANUFACTURER. <br />2.INSTALLERS SHALL BE LICENSED, AS REQUIRED, BY THE STATE OF CALIFORNIA. <br />B.ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES: <br />1.LISTED AND LABELED AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY <br />ACCEPTABLE TO CALIFORNIA STATE FIRE MARSHAL, AND MARKED FOR INTENDED <br />USE. <br />1.07 PROJECT CONDITIONS <br />A.INTERRUPTION OF EXISTING FIRE ALARM SERVICE: DO NOT INTERRUPT FIRE ALARM <br />SERVICE TO FACILITIES OCCUPIED BY THE OWNER OR OTHERS UNLESS PERMITTED <br />UNDER THE FOLLOWING CONDITIONS AND THEN ONLY AFTER ARRANGING TO PROVIDE <br />TEMPORARY GUARD SERVICE ACCORDING TO REQUIREMENTS INDICATED: <br />1.NOTIFY THE OWNER'S REPRESENTATIVE NO FEWER THAN FOURTEEN DAYS IN <br />ADVANCE OF PROPOSED INTERRUPTION OF FIRE ALARM SERVICE. <br />2.DO NOT PROCEED WITH INTERRUPTION OF FIRE ALARM SERVICE WITHOUT THE <br />OWNER'S REPRESENTATIVE WRITTEN PERMISSION. <br />1.08 SEQUENCING AND SCHEDULING <br />A.EXISTING FIRE ALARM EQUIPMENT: THE EXISTING FIRE ALARM CONTROL PANEL SHALL <br />REMAIN. MAINTAIN FULLY OPERATIONAL UNTIL NEW EQUIPMENT HAS BEEN TESTED AND <br />ACCEPTED. AS NEW EQUIPMENT IS INSTALLED, LABEL IT "NOT IN SERVICE" UNTIL IT IS <br />ACCEPTED. REMOVE LABELS FROM NEW EQUIPMENT WHEN PUT INTO SERVICE AND <br />LABEL EXISTING FIRE ALARM EQUIPMENT "NOT IN SERVICE" UNTIL REMOVED FROM THE <br />BUILDING. <br />1.09 SOFTWARE SERVICE AGREEMENT <br />A.AT THE COMPLETION OF THE PROJECT UPDATE THE FACP SOFTWARE AND FIRMWARE TO <br />THE LATEST VERSION REQUIRED FOR PROPER OPERATION OF THE SYSTEM. PROVIDE <br />ACCESS FOR SOFTWARE AND FIRMWARE UPGRADES VIA THE INTERNET. UPGRADE <br />SHALL INCLUDE NEW OR REVISED LICENSES FOR USE OF THE SOFTWARE. <br />1.10 EXTRA MATERIALS <br />A.FURNISH EXTRA MATERIALS THAT MATCH PRODUCTS INSTALLED AND THAT ARE <br />PACKAGED WITH PROTECTIVE COVERING FOR STORAGE AND IDENTIFIED WITH LABELS <br />DESCRIBING CONTENTS. <br />1.QUANTITIES OF THE FOLLOWING DEVICES EQUAL TO 10 PERCENT OF THE AMOUNTS <br />SHOWN FOR EACH DEVICE ON THE APPROVED PLANS BUT NO LESS THAN ONE OF <br />EACH TYPE OF DEVICE. <br />a.PULL STATION. <br />b.ADDRESSABLE MONITOR MODULE. <br />c.ADDRESSABLE CONTROL MODULE. <br />d.SMOKE DETECTOR HEAD (SENSOR). <br />e.SMOKE DETECTOR BASE. <br />f.HEAT DETECTOR HEAD (SENSOR). <br />g.HEAT DETECTOR BASE. <br />h.DUCT DETECTOR HOUSING WITH HEAD. <br />i.IN-DUCT DETECTOR HOUSING. <br />j.INDOOR INDICATING DEVICES: HORN, SPEAKER, STROBE AND/OR COMBINATION <br />DEVICES. <br />k.KEYS AND TOOLS: ONE SET OF EACH KEY AND/OR SPECIAL TOOL USED FOR <br />LOCKS AND ACCESS. <br />PART 2 - PRODUCTS <br />2.01 FIRE ALARM CONTROL PANEL (FACP) <br />A.GENERAL: EXISTING FIRE ALARM CONTROL PANEL SHALL REMAIN AND NEW DEVICES <br />SHALL BE COMPATIBLE WITH THE EXISTING FACP. <br />2.02 ADDRESSABLE MANUAL FIRE ALARM BOXES <br />A.UL 38 LISTED; FINISHED IN RED WITH MOLDED, RAISED-LETTER OPERATING <br />INSTRUCTIONS IN CONTRASTING COLOR. STATION SHALL SHOW VISIBLE INDICATION OF <br />OPERATION. MOUNTED ON RECESSED OUTLET BOX; IF INDICATED AS SURFACE <br />MOUNTED, PROVIDE MANUFACTURER'S SURFACE BACK BOX. <br />B.SINGLE-ACTION MECHANISM, PULL-LEVER TYPE. WITH INTEGRAL ADDRESSABLE <br />MODULE, ARRANGED TO COMMUNICATE INDIVIDUAL MANUAL-STATION STATUS (NORMAL, <br />ALARM, OR TROUBLE) TO THE FACP AND PROJECT'S GCC. <br />C.WEATHERPROOF FIRE ALARM BOXES: PROVIDE WEATHERPROOF SINGLE-ACTION <br />DEVICES WITH ADDRESSABLE MODULE. <br />D.COVERS: FACTORY-FABRICATED CLEAR PLASTIC ENCLOSURES ARE NOT PERMITTED TO <br />BE USED. <br />2.03 ADDRESSABLE ANALOG SENSORS <br />A.SMOKE SENSORS <br />1.GENERAL: COMPLY WITH UL 268, "SMOKE DETECTORS FOR FIRE PROTECTIVE <br />SIGNALING SYSTEMS." <br />2.INCLUDE THE FOLLOWING FEATURES: <br />a.FACTORY NAMEPLATE: SERIAL NUMBER AND TYPE IDENTIFICATION. <br />b.OPERATING VOLTAGE: 24 VDC, NOMINAL. <br />3.SELF-RESTORING: DETECTORS DO NOT REQUIRE RESETTING OR READJUSTMENT <br />AFTER ACTUATION TO RESTORE NORMAL OPERATION. <br />4.PLUG-IN ARRANGEMENT: SENSOR AND ASSOCIATED ELECTRONIC COMPONENTS ARE <br />MOUNTED IN A MODULE THAT CONNECTS TO A FIXED BASE WITH A TWIST-LOCKING <br />PLUG CONNECTION. BASE SHALL PROVIDE BREAK-OFF PLASTIC TAB THAT CAN BE <br />REMOVED TO ENGAGE THE HEAD/BASE LOCKING MECHANISM. NO SPECIAL TOOLS <br />SHALL BE REQUIRED TO REMOVE HEAD ONCE IT HAS BEEN LOCKED. REMOVAL OF <br />THE DETECTOR HEAD SHALL INTERRUPT THE SUPERVISORY CIRCUIT OF THE FIRE <br />ALARM DETECTION LOOP AND CAUSE A TROUBLE SIGNAL AT THE CONTROL UNIT. <br />5.EACH SENSOR BASE SHALL CONTAIN AN LED THAT WILL FLASH EACH TIME IT IS <br />SCANNED BY THE CONTROL UNIT (ONCE EVERY 4 SECONDS). IN ALARM CONDITION, <br />THE SENSOR BASE LED SHALL BE ON STEADY. <br />6.EACH SENSOR BASE SHALL CONTAIN A MAGNETICALLY ACTUATED TEST SWITCH TO <br />PROVIDE FOR EASY ALARM TESTING AT THE SENSOR LOCATION. <br />7.EACH SENSOR SHALL BE SCANNED BY THE CONTROL UNIT FOR ITS TYPE <br />IDENTIFICATION TO PREVENT INADVERTENT SUBSTITUTION OF ANOTHER SENSOR <br />TYPE. UPON DETECTION OF A "WRONG DEVICE", THE CONTROL UNIT SHALL OPERATE <br />WITH THE INSTALLED DEVICE AT THE DEFAULT ALARM SETTINGS FOR THAT SENSOR; <br />2.5% OBSCURATION FOR PHOTOELECTRIC SENSOR, 135-DEG F AND 15-DEG F <br />RATE-OF-RISE FOR THE HEAT SENSOR, BUT SHALL INDICATE A "WRONG DEVICE" <br />TROUBLE CONDITION. <br />8.THE SENSOR'S ELECTRONICS SHALL BE IMMUNE FROM FALSE ALARMS CAUSED BY <br />EMI AND RFI. <br />9.SENSORS INCLUDE A COMMUNICATION TRANSMITTER AND RECEIVER IN THE <br />MOUNTING BASE HAVING A UNIQUE IDENTIFICATION AND CAPABILITY FOR STATUS <br />REPORTING TO THE FACP. SENSOR ADDRESS SHALL BE LOCATED IN BASE TO <br />ELIMINATE FALSE ADDRESSING WHEN REPLACING SENSORS. <br />10.ENVIRONMENTAL COMPENSATION, PROGRAMMABLE SENSITIVITY SETTINGS, STATUS <br />TESTING, AND MONITORING OF SENSOR DIRT ACCUMULATION FOR THE DUCT <br />SENSOR SHALL BE PROVIDED BY THE FACP. <br />11.REMOVAL OF THE SENSOR HEAD FOR CLEANING SHALL NOT REQUIRE THE SETTING <br />OF ADDRESSES. <br />B.TYPE: SMOKE SENSORS SHALL BE OF THE PHOTOELECTRIC OR COMBINATION <br />PHOTOELECTRIC / HEAT TYPE. <br />1.WHERE ACCEPTABLE PER MANUFACTURER SPECIFICATIONS, IONIZATION TYPE <br />SENSORS MAY BE USED. <br />C.BASES: RELAY OUTPUT, REMOTE LED, SOUNDER AND ISOLATOR BASES SHALL BE <br />SUPPORTED ALTERNATIVES TO THE STANDARD BASE. <br />D.DUCT SMOKE SENSOR: <br />1.PHOTOELECTRIC TYPE, WITH HOUSING AND SAMPLING TUBE OF DESIGN AND <br />DIMENSIONS AS RECOMMENDED BY THE MANUFACTURER FOR THE SPECIFIC DUCT <br />SIZE AND INSTALLATION CONDITIONS WHERE APPLIED. SENSOR INCLUDES RELAY AS <br />REQUIRED FOR FAN SHUTDOWN. <br />2.WHEN REQUIRED THE DUCT HOUSING SHALL PROVIDE A SUPERVISED RELAY DRIVER <br />CIRCUIT FOR DRIVING UP TO 15 RELAYS WITH A SINGLE "FORM C" CONTACT RATED <br />AT 7A@ 28VDC OR 10A@ 120VAC. THIS AUXILIARY RELAY OUTPUT SHALL BE FULLY <br />PROGRAMMABLE. RELAY SHALL BE MOUNTED WITHIN 3 FEET OF HVAC CONTROL <br />CIRCUIT. <br />3.DUCT HOUSING SHALL PROVIDE A RELAY CONTROL TROUBLE INDICATOR YELLOW <br />LED. <br />4.COMPACT DUCT HOUSING SHALL HAVE A TRANSPARENT COVER TO MONITOR FOR <br />THE PRESENCE OF SMOKE. COVER SHALL SECURE TO HOUSING BY MEANS OF FOUR <br />(4) CAPTIVE FASTENING SCREWS. <br />5.DUCT HOUSING SHALL PROVIDE TWO (2) TEST PORTS FOR MEASURING AIRFLOW AND <br />FOR TESTING. THESE PORTS WILL ALLOW AEROSOL INJECTION IN ORDER TO TEST <br />THE ACTIVATION OF THE DUCT SMOKE SENSOR. <br />6.DUCT HOUSING SHALL PROVIDE A MAGNETIC TEST AREA AND RED SENSOR STATUS <br />LED. <br />7.FOR MAINTENANCE PURPOSES, IT SHALL BE POSSIBLE TO CLEAN THE DUCT HOUSING <br />SAMPLING TUBES BY ACCESSING THEM THROUGH THE DUCT HOUSING FRONT <br />COVER. <br />8.WHERE INDICATED A NEMA 4X WEATHERPROOF DUCT HOUSING ENCLOSURE SHALL <br />PROVIDE FOR THE CIRCULATION OF CONDITIONED AIR AROUND THE INTERNALLY <br />MOUNTED ADDRESSABLE DUCT SENSOR HOUSING TO MAINTAIN THE SENSOR <br />HOUSING AT ITS RATED TEMPERATURE RANGE. THE HOUSING SHALL BE UL LISTED <br />TO STANDARD 268A. <br />9.PROVIDE IN-DUCT DETECTOR ASSEMBLY(IES) WITH PHOTOELECTRIC SENSOR: <br />a.WHERE SAMPLING TUBE DESIGNS ARE NOT APPROPRIATE. <br />b.WHERE AIR FLOW COVERAGE IS FROM 35-600 FT/MIN. <br />10.PROVIDE A REMOTE TEST SWITCH (RTS), ON ALL DUCT TYPE DETECTORS WHEN THE <br />DEVICE'S ALARM LED IS OBSTRUCTED FROM BEING CLEARLY VISIBLE FROM THE <br />FLOOR OR THE DEVICE IS MOUNTED HIGHER THAN 9' A.F.F. <br />a.MOUNT RTS BELOW DETECTOR IN THE CEILING OR ON THE NEAREST SIDEWALL <br />AS DIRECTED BY THE DSFM. <br />2.04 CONVENTIONAL SYSTEM SMOKE DETECTORS <br />A.UNLESS OTHERWISE INDICATED, DETECTORS SHALL BE ANALOG-ADDRESSABLE TYPE, <br />INDIVIDUALLY MONITORED AT THE FACP FOR CALIBRATION, SENSITIVITY, AND ALARM <br />CONDITION, AND INDIVIDUALLY ADJUSTABLE FOR SENSITIVITY FROM THE FACP, <br />INTERNET AND PROJECT'S GCC. <br />2.05 ADDRESSABLE CIRCUIT INTERFACE MODULES <br />A.ADDRESSABLE CIRCUIT INTERFACE MODULES: ARRANGE TO MONITOR ONE OR MORE <br />SYSTEM COMPONENTS THAT ARE NOT OTHERWISE EQUIPPED FOR ADDRESSABLE <br />COMMUNICATION. MODULES SHALL BE USED FOR MONITORING OF WATER FLOW, VALVE <br />TAMPER, NON-ADDRESSABLE DEVICES, AND FOR CONTROL OF EVACUATION INDICATING <br />APPLIANCES AND AHU SYSTEMS. <br />B.ADDRESSABLE CIRCUIT INTERFACE MODULES WILL BE CAPABLE OF MOUNTING IN A <br />STANDARD ELECTRIC OUTLET BOX. MODULES WILL INCLUDE COVER PLATES TO ALLOW <br />SURFACE OR FLUSH MOUNTING. MODULES WILL RECEIVE THEIR OPERATING POWER <br />FROM THE SIGNALING LINE OR A SEPARATE TWO WIRE PAIR RUNNING FROM AN <br />APPROPRIATE POWER SUPPLY AS REQUIRED. <br />C.THERE SHALL BE THE FOLLOWING TYPES OF MODULES: <br />1.TYPE 1: MONITOR CIRCUIT INTERFACE MODULE: <br />a.FOR CONVENTIONAL 2-WIRE SMOKE DETECTOR AND/OR CONTACT DEVICE <br />MONITORING WITH CLASS B OR CLASS A WIRING SUPERVISION. THE SUPERVISION <br />OF THE ZONE WIRING WILL BE CLASS B. THIS MODULE WILL COMMUNICATE <br />STATUS (NORMAL, ALARM, TROUBLE) TO THE FACP. <br />b.FOR CONVENTIONAL 4-WIRE SMOKE DETECTOR WITH CLASS B WIRING <br />SUPERVISION. THE MODULE WILL PROVIDE DETECTOR RESET CAPABILITY AND <br />OVER-CURRENT POWER PROTECTION FOR THE 4-WIRE DETECTOR. THIS MODULE <br />WILL COMMUNICATE STATUS (NORMAL, ALARM, TROUBLE) TO THE FACP. <br />2.TYPE 2: LINE POWERED MONITOR CIRCUIT INTERFACE MODULE: <br />a.THIS TYPE OF MODULE IS AN INDIVIDUALLY ADDRESSABLE MODULE THAT HAS <br />BOTH ITS POWER AND ITS COMMUNICATIONS SUPPLIED BY THE TWO WIRE <br />MULTIPLEXING SIGNALING LINE CIRCUIT. IT PROVIDES LOCATION SPECIFIC <br />ADDRESSABILITY TO AN INITIATING DEVICE BY MONITORING NORMALLY OPEN <br />DRY CONTACTS. THIS MODULE SHALL HAVE THE CAPABILITY OF COMMUNICATING <br />FOUR ZONE STATUS CONDITIONS (NORMAL, ALARM, CURRENT LIMITED, TROUBLE) <br />TO THE FACP. <br />b.THIS MODULE SHALL PROVIDE LOCATION SPECIFIC ADDRESSABILITY FOR UP TO <br />FIVE INITIATING DEVICES BY MONITORING NORMALLY CLOSED OR NORMALLY <br />OPEN DRY CONTACT SECURITY DEVICES. THE MODULE SHALL COMMUNICATE <br />FOUR ZONE STATUS CONDITIONS (OPEN, NORMAL, ABNORMAL, AND SHORT). THE <br />TWO-WIRE SIGNALING LINE CIRCUIT SHALL SUPPLY POWER AND <br />COMMUNICATIONS TO THE MODULE. <br />3.TYPE 3: SINGLE ADDRESS MULTI-POINT INTERFACE MODULES: <br />a.THIS MULTIPOINT MODULE SHALL PROVIDE LOCATION SPECIFIC ADDRESSABILITY <br />FOR FOUR INITIATING CIRCUITS AND CONTROL TWO OUTPUT RELAYS FROM A <br />SINGLE ADDRESS. INPUTS SHALL PROVIDE SUPERVISED MONITORING OF <br />NORMALLY OPEN, DRY CONTACTS AND BE CAPABLE OF COMMUNICATING FOUR <br />ZONE STATUS CONDITIONS (NORMAL, OPEN, CURRENT LIMITED, AND SHORT). THE <br />INPUT CIRCUITS AND OUTPUT RELAY OPERATION SHALL BE CONTROLLED <br />INDEPENDENTLY AND DISABLED SEPARATELY. <br />b.THIS DUAL POINT MODULE SHALL PROVIDE A SUPERVISED MULTI-STATE INPUT <br />AND A RELAY OUTPUT, USING A SINGLE ADDRESS. THE INPUT SHALL PROVIDE <br />SUPERVISED MONITORING OF TWO NORMALLY OPEN, DRY CONTACTS WITH A <br />SINGLE POINT AND BE CAPABLE OF COMMUNICATING FOUR ZONE STATUS <br />CONDITIONS (NORMAL, OPEN, CURRENT LIMITED, AND SHORT). THE TWO-WIRE <br />SIGNALING LINE CIRCUIT SHALL SUPPLY POWER AND COMMUNICATIONS TO THE <br />MODULE. <br />c.THIS DUAL POINT MODULE SHALL MONITOR AN UNSUPERVISED NORMALLY OPEN, <br />DRY CONTACT WITH ONE POINT AND CONTROL AN OUTPUT RELAY WITH THE <br />OTHER POINT, USING A SINGLE ADDRESS. THE TWO-WIRE SIGNALING LINE <br />CIRCUIT SHALL SUPPLY POWER AND COMMUNICATIONS TO THE MODULE. <br />4.TYPE 4: LINE POWERED CONTROL CIRCUIT INTERFACE MODULE: THIS MODULE SHALL <br />PROVIDE CONTROL AND STATUS TRACKING OF A FORM "C" CONTACT. THE TWO-WIRE <br />SIGNALING LINE CIRCUIT SHALL SUPPLY POWER AND COMMUNICATIONS TO THE <br />MODULE. <br />5.TYPE 5: 4-20 MA ANALOG MONITOR CIRCUIT INTERFACE MODULE: THIS MODULE <br />SHALL COMMUNICATE THE STATUS OF A COMPATIBLE 4-20 MA SENSOR TO THE FACP. <br />THE FACP SHALL ANNUNCIATE UP TO THREE THRESHOLD LEVELS, EACH WITH <br />CUSTOM ACTION MESSAGE; DISPLAY AND ARCHIVE ACTUAL SENSOR ANALOG <br />LEVELS; AND PERMIT SENSOR CALIBRATION DATE RECORDING. <br />D.ALL CIRCUIT INTERFACE MODULES SHALL BE SUPERVISED AND UNIQUELY IDENTIFIED BY <br />THE CONTROL UNIT. MODULE IDENTIFICATION SHALL BE TRANSMITTED TO THE CONTROL <br />UNIT FOR PROCESSING ACCORDING TO THE PROGRAM INSTRUCTIONS. MODULES SHALL <br />HAVE AN ON-BOARD LED TO PROVIDE AN INDICATION THAT THE MODULE IS POWERED <br />AND COMMUNICATING WITH THE FACP. THE LEDS SHALL PROVIDE A TROUBLESHOOTING <br />AID SINCE THE LED BLINKS ON POLL WHENEVER THE PERIPHERAL IS POWERED AND <br />COMMUNICATING. <br />2.06 ADDRESSABLE ALARM NOTIFICATION APPLIANCES <br />A.ADDRESSABLE NOTIFICATION APPLIANCES: <br />1.THE CONTRACTOR SHALL FURNISH AND INSTALL ADDRESSABLE NOTIFICATION <br />APPLIANCES AND ACCESSORIES TO OPERATE ON COMPATIBLE SIGNALING LINE <br />CIRCUITS (SLC). <br />2.ADDRESSABLE NOTIFICATION APPLIANCE OPERATION SHALL PROVIDE POWER, <br />SUPERVISION AND SEPARATE CONTROL OF HORNS AND STROBES OVER A SINGLE <br />PAIR OF WIRES. THE CONTROLLING CHANNEL (SLC) DIGITALLY COMMUNICATES WITH <br />EACH APPLIANCE AND RECEIVES A RESPONSE TO VERIFY THE APPLIANCE'S <br />PRESENCE ON THE CHANNEL. THE CHANNEL PROVIDES A DIGITAL COMMAND TO <br />CONTROL APPLIANCE OPERATION. SLC CHANNEL WIRING SHALL BE UNSHIELDED <br />TWISTED PAIR (UTP), WITH A CAPACITANCE RATING OF LESS THAN 60PF/FT. AND A <br />MINIMUM 3 TWISTS (TURNS) PER FOOT. <br />3.CLASS B (STYLE 4) NOTIFICATION APPLIANCES SHALL BE WIRED WITHOUT REQUIRING <br />TRADITIONAL IN/OUT WIRING METHODS; ADDRESSABLE "T" TAPPING SHALL BE <br />PERMITTED. UP TO 63 APPLIANCES CAN BE SUPPORTED ON A SINGLE CHANNEL. <br />4.EACH ADDRESSABLE NOTIFICATION APPLIANCE SHALL CONTAIN AN ELECTRONIC <br />MODULE AND A SELECTABLE ADDRESS SETTING TO ALLOW IT TO OCCUPY A UNIQUE <br />LOCATION ON THE CHANNEL. THIS ON-BOARD MODULE SHALL ALSO ALLOW THE <br />CHANNEL TO PERFORM APPLIANCE DIAGNOSTICS THAT ASSIST WITH INSTALLATION <br />AND SUBSEQUENT TEST OPERATIONS. A VISIBLE LED ON EACH APPLIANCE SHALL <br />PROVIDE VERIFICATION OF COMMUNICATIONS AND SHALL FLASH WITH THE <br />APPLIANCES ADDRESS SETTING WHEN LOCALLY REQUESTED USING A MAGNETIC <br />TEST TOOL. <br />5.ADDRESSABLE CONTROLLER: <br />a.ADDRESSABLE CONTROLLER SHALL SUPERVISE CHANNEL (SLC) WIRING, <br />COMMUNICATE WITH AND CONTROL ADDRESSABLE NOTIFICATION APPLIANCES. <br />IT SHALL BE POSSIBLE TO PROGRAM THE HIGH/LOW SETTING OF THE AUDIBLE <br />(HORN) APPLIANCES BY CHANNEL FROM THE ADDRESSABLE CONTROLLER. <br />6.HORN: <br />a.ADDRESSABLE HORN SHALL BE LISTED TO UL 464. HORN APPLIANCES SHALL <br />HAVE A HIGH/LOW SETTING, PROGRAMMABLE BY CHANNEL FROM THE <br />ADDRESSABLE CONTROLLER OR BY APPLIANCE FROM THE HOST FACP. THE <br />HORN SHALL HAVE A MINIMUM SOUND PRESSURE LEVEL OF 83 OR 89 DBA @ <br />24VDC. THE HORN SHALL MOUNT DIRECTLY TO A STANDARD SINGLE GANG, <br />DOUBLE GANG OR 4" SQUARE ELECTRICAL BOX, WITHOUT THE USE OF SPECIAL <br />ADAPTER OR TRIM RINGS. <br />b.APPLIANCES SHALL BE WIRED WITH UTP CONDUCTORS, HAVING A MINIMUM OF 3 <br />TWISTS PER FOOT. <br />7.VISIBLE/ONLY: <br />a.ADDRESSABLE STROBE SHALL BE LISTED TO UL 1971. THE V/O SHALL CONSIST OF <br />A XENON FLASH TUBE AND ASSOCIATED LENS/REFLECTOR SYSTEM. THE WALL <br />MOUNT V/O ENCLOSURE SHALL MOUNT DIRECTLY TO STANDARD SINGLE GANG, <br />DOUBLE GANG OR 4" SQUARE ELECTRICAL BOX, WITHOUT THE USE OF SPECIAL <br />ADAPTERS OR TRIM RINGS. THE CEILING MOUNT V/O SHALL MOUNT TO A SINGLE <br />GANG ELECTRICAL BOX. <br />b.APPLIANCES SHALL BE WIRED WITH UTP CONDUCTORS, HAVING A MINIMUM OF 3 <br />TWISTS PER FOOT. V/O APPLIANCES SHALL BE PROVIDED WITH DIFFERENT <br />MINIMUM FLASH INTENSITIES OF 15CD, 75CD AND 110CD. PROVIDE A LABEL INSIDE <br />THE STROBE LENS TO INDICATE THE LISTED CANDELA RATING OF THE SPECIFIC <br />VISIBLE/ONLY APPLIANCE. <br />8.AUDIBLE/VISIBLE: <br />a.ADDRESSABLE COMBINATION AUDIBLE/VISIBLE (A/V) NOTIFICATION APPLIANCES <br />SHALL BE LISTED TO UL 1971 AND UL 464. THE STROBE LIGHT SHALL CONSIST OF <br />A XENON FLASH TUBE AND ASSOCIATED LENS/REFLECTOR SYSTEM. PROVIDE A <br />LABEL INSIDE THE STROBE LENS TO INDICATE THE LISTED CANDELA RATING OF <br />THE SPECIFIC STROBE. THE HORN SHALL HAVE A MINIMUM SOUND PRESSURE <br />LEVEL OF 83 OR 89 DBA @ 24VDC. THE AUDIBLE/VISIBLE ENCLOSURE SHALL <br />MOUNT DIRECTLY TO STANDARD SINGLE GANG, DOUBLE GANG OR 4" SQUARE <br />ELECTRICAL BOX, WITHOUT THE USE OF SPECIAL ADAPTERS OR TRIM RINGS. <br />b.APPLIANCES SHALL BE WIRED WITH UTP CONDUCTORS, HAVING A MINIMUM OF 3 <br />TWISTS PER FOOT. <br />c.THE APPLIANCE SHALL BE CAPABLE OF TWO-WIRE SYNCHRONIZATION WITH ONE <br />OF THE FOLLOWING OPTIONS: <br />1)SYNCHRONIZED STROBE WITH HORN ON STEADY. <br />2)SYNCHRONIZED STROBE WITH TEMPORAL CODE PATTERN ON HORN. <br />3)SYNCHRONIZED STROBE WITH MARCH TIME CADENCE ON HORN. <br />4)SYNCHRONIZED STROBE FIRING TO NAC SYNC SIGNAL WITH HORN SILENCED. <br />9.SPEAKER/VISIBLE: <br />a.COMBINATION SPEAKER/VISIBLE (S/V) UNITS COMBINE THE SPEAKER AND VISIBLE <br />FUNCTIONS INTO A COMMON HOUSING. THE S/V SHALL BE LISTED TO UL 1971 AND <br />UL 1480. ADDRESSABLE FUNCTIONALITY CONTROLS VISIBLE OPERATION, WHILE <br />THE SPEAKER OPERATES ON A 25VRMS OR 70.7VRMS NAC. <br />b.TWISTED/SHIELDED WIRE IS REQUIRED FOR SPEAKER CONNECTIONS ON A <br />STANDARD 25VRMS OR 70.7VRMS NAC USING AND UTP CONDUCTORS, HAVING A <br />MINIMUM OF 3 TWISTS PER FOOT IS REQUIRED FOR ADDRESSABLE STROBE <br />CONNECTIONS. <br />c.AT THE 1.0W TAP, THE SPEAKER SHALL HAVE A MINIMUM UL RATED SOUND <br />PRESSURE LEVEL OF 84DBA AT 10 FEET. <br />d.THE S/V SHALL HAVE A FREQUENCY RESPONSE OF 400 TO 4000 HZ FOR FIRE <br />ALARM AND 125 TO 12KHZ FOR GENERAL SIGNALING. <br />e.THE S/V INSTALLS DIRECTLY TO A 4" SQUARE, 1 1/2 IN. DEEP ELECTRICAL BOX <br />WITH 1 1/2" EXTENSION. <br />10.ISOLATOR MODULE: <br />a.ISOLATOR MODULE PROVIDES SHORT CIRCUIT ISOLATION FOR ADDRESSABLE <br />NOTIFICATION APPLIANCE SLC WIRING. ISOLATOR SHALL BE LISTED TO UL 864. <br />THE ISOLATOR SHALL MOUNT DIRECTLY TO A MINIMUM 2 1/8" DEEP, STANDARD 4" <br />SQUARE ELECTRICAL BOX, WITHOUT THE USE OF SPECIAL ADAPTER OR TRIM <br />RINGS. <br />b.POWER AND COMMUNICATIONS SHALL BE SUPPLIED BY THE ADDRESSABLE <br />CONTROLLER CHANNEL SLC; DUAL PORT DESIGN SHALL ACCEPT <br />COMMUNICATIONS AND POWER FROM EITHER PORT AND SHALL AUTOMATICALLY <br />ISOLATE ONE PORT FROM THE OTHER WHEN A SHORT CIRCUIT OCCURS. <br />c.THE FOLLOWING FUNCTIONALITY SHALL BE INCLUDED IN THE ISOLATOR MODULE: <br />1)REPORT FAULTS TO THE HOST FACP. <br />2)ON-BOARD YELLOW LED PROVIDES MODULE STATUS. <br />3)AFTER THE WIRING FAULT IS REPAIRED, THE ISOLATOR MODULES SHALL TEST <br />THE LINES AND AUTOMATICALLY RESTORE THE CONNECTION. <br />B.TRUEALERT ADDRESSABLE APPLIANCES NAC POWER EXTENDER: <br />1.THE TRUEALERT ADDRESSABLE CONTROLLER SHALL BE A STAND-ALONE PANEL <br />CAPABLE OF POWERING A MINIMUM OF 3 TRUEALERT SIGNALING LINE CIRCUITS. <br />EACH CHANNEL SHALL BE RATED FOR 2.5 AMPS AND SUPPORT UP TO 63 TRUEALERT <br />ADDRESSABLE NOTIFICATION APPLIANCES. POWER AND COMMUNICATION FOR THE <br />NOTIFICATION APPLIANCES SHALL BE PROVIDED ON THE SAME PAIR OF WIRES. <br />2.ADDRESSABLE SLC NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B STYLE 4. <br />UNLESS NOTED ELSEWHERE. <br />3.THE INTERNAL POWER SUPPLY & BATTERY CHARGER SHALL BE CAPABLE OF <br />CHARGING UP 12.7 AH BATTERIES INTERNALLY MOUNTED OR 18AH BATTERIES <br />MOUNTED IN AN EXTERNAL CABINET. <br />4.THE NAC EXTENDER PANEL MAY BE MOUNTED CLOSE TO THE HOST CONTROL PANEL <br />OR CAN BE REMOTELY LOCATED. <br />2.07 NON ADDRESSABLE NOTIFICATION APPLIANCES <br />A.DESCRIPTION: <br />1.EQUIPPED FOR MOUNTING AS INDICATED AND WITH SCREW TERMINALS FOR SYSTEM <br />CONNECTIONS. <br />a.COMBINATION DEVICES: <br />b.FACTORY-INTEGRATED AUDIBLE AND VISIBLE DEVICES IN A SINGLE-MOUNTING <br />ASSEMBLY. <br />2.GENERAL ALARM HORN: <br />a.ELECTRIC-VIBRATING-POLARIZED TYPE, 24-V DC; HORNS SHALL PRODUCE A <br />SOUND-PRESSURE LEVEL OF 87 DBA, MEASURED 10 FEET FROM THE HORN. <br />SOUND LEVEL FOR EACH DEVICE SHALL BE SELECTABLE AT THE DEVICE. HORNS <br />SHALL BE PROVIDED WITH WEATHERPROOF BACK BOX WHERE INDICATED. <br />2.08 GUARDS FOR PHYSICAL PROTECTION <br />A.DESCRIPTION: <br />4.WELDED WIRE MESH OF SIZE AND SHAPE FOR THE MANUAL STATION, SMOKE <br />DETECTOR, GONG, OR OTHER DEVICE REQUIRING PROTECTION. <br />5.FACTORY FABRICATED AND FURNISHED BY MANUFACTURER OF THE DEVICE. <br />6.FINISH: PAINT OF COLOR TO MATCH THE PROTECTED DEVICE. <br />2.09 WIRE, CABLE, AND FIBER <br />A. WIRE AND CABLE FOR FIRE ALARM SYSTEMS SHALL BE UL LISTED AND LABELED AS <br />COMPLYING WITH NFPA 70, ARTICLE 760. <br />B. SIGNALING LINE CIRCUITS: TWISTED, SHIELDED PAIR, SIZED AS RECOMMENDED BY <br />SYSTEM MANUFACTURER. <br />C.NON-POWER-LIMITED CIRCUITS: SOLID-COPPER CONDUCTORS WITH 600-V RATED, 75 <br />DEGREES C, COLOR-CODED INSULATION. <br />1.LOW-VOLTAGE COMMUNICATION CIRCUITS: NO. 18 AWG, MINIMUM. <br />2.LOW-VOLTAGE POWER CIRCUITS: NO. 14 AWG, MINIMUM. <br />3.LINE-VOLTAGE CIRCUITS: NO. 12 AWG, MINIMUM. <br />4.MULTI-CONDUCTOR ARMORED CABLE: NFPA 70 RED LIGHTWEIGHT STEEL TYPE MC, <br />COPPER CONDUCTORS, TFN/THHN CONDUCTOR INSULATION, COPPER DRAIN WIRE, <br />COPPER ARMOR WITH RED IDENTIFIER STRIPE, UL LISTED FOR FIRE ALARM AND <br />CABLE TRAY INSTALLATION, PLENUM RATED, AND COMPLYING WITH REQUIREMENTS <br />IN UL 2196 FOR A 2-HOUR RATING. <br />PART 3 - EXECUTION <br />3.01 EQUIPMENT INSTALLATION <br />A.COMPLY WITH THE LATEST EDITION OF NFPA 72 AND UL 864 REQUIREMENTS FOR <br />INSTALLATION OF FIRE-ALARM SYSTEM. <br />B.EQUIPMENT MOUNTING: INSTALL FIRE ALARM DEVICES AND CONTROLLERS AS <br />RECOMMENDED BY THE MANUFACTURER. <br />C.INSTALL SEISMIC BRACING: COMPLY WITH THE REQUIREMENTS IN DIVISION 26 SECTION <br />REGARDING VIBRATION AND SEISMIC CONTROL FOR ELECTRICAL SYSTEMS. <br />D.SMOKE OR HEAT DETECTOR SPACING: <br />1.SMOOTH CEILING SPACING SHALL NOT EXCEED THE RATING OF THE DETECTOR. <br />2.SPACING OF HEAT DETECTORS FOR IRREGULAR AREAS, FOR IRREGULAR CEILING <br />CONSTRUCTION, AND FOR HIGH CEILING AREAS, SHALL BE DETERMINED ACCORDING <br />TO APPENDIX A IN NFPA 72. <br />3.SPACING OF HEAT DETECTORS SHALL BE DETERMINED BASED ON GUIDELINES AND <br />RECOMMENDATIONS IN NFPA 72. <br />E.SMOKE DETECTOR LOCATION: LOCATE DETECTORS NOT CLOSER THAN 3 FEET FROM <br />AIR-SUPPLY DIFFUSER OR RETURN-AIR OPENING. LOCATE DETECTOR NOT CLOSER THAN <br />12 INCHES FROM ANY PART OF A LIGHTING FIXTURE. <br />F.DUCT SMOKE DETECTORS: COMPLY WITH NFPA 72, NFPA 90A AND THE MANUFACTURE <br />RECOMMENDATIONS. INSTALL SAMPLING TUBES SO THEY EXTEND THE FULL WIDTH OF <br />THE DUCT. <br />G.SINGLE-STATION SMOKE DETECTORS: WHERE MORE THAN ONE SMOKE ALARM IS <br />INSTALLED WITHIN A DWELLING OR SUITE, THEY SHALL BE CONNECTED SO THAT THE <br />OPERATION OF ANY SMOKE ALARM IN THE DWELLING OR SUITE CAUSES ALL THE SMOKE <br />ALARM IN THE DWELLING OR SUIT TO SOUND A TEMPORAL PATTERN. <br />H.REMOTE STATUS AND ALARM INDICATORS: INSTALL NEAR EACH SMOKE DETECTOR AND <br />EACH SPRINKLER WATER-FLOW SWITCH AND VALVE-TAMPER SWITCH THAT IS NOT <br />READILY VISIBLE FROM NORMAL VIEWING POSITION. <br />I.AUDIBLE ALARM-INDICATING DEVICES: INSTALL NOT LESS THAN 6 INCHES BELOW THE <br />CEILING. INSTALL HORNS ON FLUSH-MOUNTED BACK BOXES. WEATHERPROOF DEVICES <br />ARE TO BE MOUNTED ON WEATHERPROOF SURFACE BACK BOX. <br />J.VISIBLE ALARM-INDICATING DEVICES (STROBES): INSTALL SO THAT THE ENTIRE LENS IS <br />MORE THAN 80 INCHES BUT LESS THAN 96 INCHES ABOVE THE FINISHED FLOOR. <br />1.EXCEPTION: WALL MOUNTED STROBES IN SLEEPING AREAS SHALL BE MOUNTED AT <br />LEAST 24 INCHES BELOW THE CEILING AND WITHIN 16FT OF THE OCCUPANT'S <br />PILLOW. <br />L.COMBINATION AUDIBLE/VISUAL DEVICES: MOUNT AT VISIBLE DEVICE HEIGHTS. <br />3.02 FIBER AND WIRING INSTALLATION <br />A.INSTALL WIRING ACCORDING TO THE FOLLOWING: <br />1.NECA 1. <br />2.TIA/EIA 568-A. <br />3.NFPA, CBC, FCC, RFI/EMI. <br />B.WIRING METHOD: <br />1.INSTALL WIRING IN METAL RACEWAY ACCORDING TO DIVISION 26 SECTION <br />"RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS." <br />2.FIRE ALARM CIRCUITS AND EQUIPMENT CONTROL WIRING ASSOCIATED WITH THE <br />FIRE ALARM SYSTEM SHALL BE INSTALLED IN A DEDICATED RACEWAY SYSTEM. THIS <br />SYSTEM SHALL NOT BE USED FOR ANY OTHER WIRE OR CABLE. <br />C.WIRING METHOD: <br />1.FIRE-RATED CABLES: USE OF 2-HOUR FIRE-RATED FIRE ALARM CABLES, NFPA 70 <br />TYPES MI AND CI, IS NOT PERMITTED. <br />2.SIGNALING LINE CIRCUITS: POWER-LIMITED FIRE ALARM CABLES SHALL BE INSTALLED <br />IN THE SAME CABLE OR RACEWAY AS SIGNALING LINE CIRCUITS. <br />D.WIRING WITHIN ENCLOSURES: SEPARATE POWER-LIMITED AND NON-POWER-LIMITED <br />CONDUCTORS AS RECOMMENDED BY MANUFACTURER. INSTALL CONDUCTORS <br />PARALLEL WITH OR AT RIGHT ANGLES TO SIDES AND BACK OF THE ENCLOSURE. <br />BUNDLE, LACE, AND TRAIN CONDUCTORS TO TERMINAL POINTS WITH NO EXCESS. <br />CONNECT CONDUCTORS THAT ARE TERMINATED, SPLICED, OR INTERRUPTED IN ANY <br />ENCLOSURE ASSOCIATED WITH THE FIRE ALARM SYSTEM TO TERMINAL BLOCKS. MARK <br />EACH TERMINAL ACCORDING TO THE SYSTEM'S WIRING DIAGRAMS. MAKE ALL <br />CONNECTIONS WITH APPROVED CRIMP-ON TERMINAL SPADE LUGS, PRESSURE-TYPE <br />TERMINAL BLOCKS, OR PLUG CONNECTORS. <br />E.CABLE TAPS: USE NUMBERED TERMINAL STRIPS IN JUNCTION, PULL, AND OUTLET BOXES, <br />CABINETS, OR EQUIPMENT ENCLOSURES WHERE CIRCUIT CONNECTIONS ARE MADE. <br />F.COLOR-CODING: COLOR-CODE FIRE ALARM CONDUCTORS AS SHOWN ON THE FIRE <br />ALARM PLANS. USE ONE COLOR-CODE FOR ALARM CIRCUIT WIRING AND A DIFFERENT <br />COLOR-CODE FOR SUPERVISORY CIRCUITS. COLOR-CODE AUDIBLE ALARM-INDICATING <br />CIRCUITS DIFFERENTLY FROM ALARM-INITIATING CIRCUITS. USE DIFFERENT COLORS <br />FOR VISIBLE ALARM-INDICATING DEVICES. PAINT FIRE ALARM SYSTEM JUNCTION BOXES <br />AND COVERS RED. <br />G.WIRING TO REMOTE ALARM TRANSMITTING DEVICE: <br />1.3/4-INCH CONDUIT BETWEEN THE FACP AND THE TRANSMITTER. <br />2.INSTALL NUMBER OF CONDUCTORS AND ELECTRICAL SUPERVISION FOR <br />CONNECTING WIRING AS NEEDED TO SUIT MONITORING FUNCTION. <br />3.03 IDENTIFICATION <br />A.IDENTIFY SYSTEM COMPONENTS, WIRING, CABLING, AND TERMINALS ACCORDING TO <br />DIVISION 26. <br />B.OPERATING INSTRUCTIONS: FRAME IN A LOCATION VISIBLE FROM THE FACP. <br />C.PAINT POWER-SUPPLY DISCONNECT SWITCH RED AND LABEL "FIRE ALARM." <br />3.04 GROUNDING <br />A.GROUND THE FACP AND ASSOCIATED CIRCUITS; COMPLY WITH IEEE 1100. INSTALL A <br />GROUND WIRE FROM MAIN SERVICE GROUND TO THE FACP. <br />3.05 FIELD QUALITY CONTROL <br />A.FINAL ACCEPTANCE TESTING SHALL BE WITNESSED BY THE OWNER'S REPRESENTATIVE. <br />B.A FINAL PRE-TEST SHALL BE WITNESSED BY THE OWNER'S REPRESENTATIVE. <br />C.MANUFACTURER'S FIELD SERVICE: <br />1.ENGAGE A FACTORY-AUTHORIZED INSTALLATION REPRESENTATIVE TO ASSIST <br />DURING THE INSTALLATION, PRE-TESTING AND ADJUST OF THE FIRE ALARM SYSTEM <br />AND FIELD DEVICES, COMPONENTS AND EQUIPMENT. <br />2.INCLUDE A MANUFACTURER'S FIELD REPRESENTATIVE DURING ALL FINAL <br />ACCEPTANCE TESTING. <br />D.PERFORM THE FOLLOWING FIELD TESTS AND INSPECTIONS AND PREPARE TEST <br />REPORTS: <br />1.BEFORE REQUESTING FINAL ACCEPTANCE TESTING AND APPROVAL OF THE <br />INSTALLATION, SUBMIT A WRITTEN STATEMENT USING THE FORM FOR RECORD OF <br />COMPLETION SHOWN IN NFPA 72. <br />2.PERFORM EACH ELECTRICAL TEST AND VISUAL AND MECHANICAL INSPECTION <br />LISTED IN NFPA 72. CERTIFY COMPLIANCE WITH TEST PARAMETERS. ALL TESTS <br />SHALL BE CONDUCTED UNDER THE DIRECT SUPERVISION OF A NICET TECHNICIAN <br />CERTIFIED UNDER THE FIRE ALARM SYSTEMS PROGRAM AT LEVEL II. <br />3.VISUAL INSPECTION: CONDUCT A VISUAL INSPECTION BEFORE ANY TESTING. USE <br />AS-BUILT DRAWINGS AND SYSTEM DOCUMENTATION FOR THE INSPECTION. IDENTIFY <br />IMPROPERLY LOCATED, DAMAGED, OR NONFUNCTIONAL EQUIPMENT, AND CORRECT <br />BEFORE BEGINNING TESTS. <br />4.TESTING: FOLLOW PROCEDURE AND RECORD RESULTS COMPLYING WITH <br />REQUIREMENTS IN NFPA 72. DETECTORS THAT ARE OUTSIDE THEIR MARKED <br />SENSITIVITY RANGE SHALL BE REPLACED. <br />5.TEST AND INSPECTION RECORDS: <br />a.PREPARE ACCORDING TO NFPA 72, INCLUDING DEMONSTRATION OF SEQUENCES <br />OF OPERATION BY USING THE MATRIX-STYLE FORM IN APPENDIX A IN NFPA 70. <br />b.PROVIDE REPORT RESULTS IN WRITING ON COMPUTER GENERATED FORMS. <br />3.06 ADJUSTING <br />A.OCCUPANCY ADJUSTMENTS: WHEN REQUESTED WITHIN 12 MONTHS OF DATE OF <br />SUBSTANTIAL COMPLETION, PROVIDE ON-SITE ASSISTANCE IN ADJUSTING SYSTEM TO <br />SUIT ACTUAL OCCUPIED CONDITIONS. PROVIDE UP TO TWO VISITS TO PROJECT OUTSIDE <br />NORMAL OCCUPANCY HOURS FOR THIS PURPOSE. <br />B.FOLLOW-UP TESTS AND INSPECTIONS: AFTER DATE OF SUBSTANTIAL COMPLETION, TEST <br />THE FIRE ALARM SYSTEM COMPLYING WITH TESTING AND VISUAL INSPECTION <br />REQUIREMENTS IN NFPA 72. <br />3.07 DEMONSTRATION <br />A.ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO TRAIN THE OWNER'S <br />MAINTENANCE PERSONNEL TO ADJUST, OPERATE, AND MAINTAIN THE FIRE ALARM <br />SYSTEM, APPLIANCES, AND DEVICES. <br />Sheet No. <br />Project <br />Agency Plan Check / Permit No. <br />Petersen Design Project No. <br />Consultant <br />5082.1 <br />652 East Dyer Drive <br />Santa Ana, CA 92705 <br />DYER WAREHOUSE <br />Staging & Set-Up Space <br />Tenant Improvements <br />Sheet Title <br />Revision / Submittal History <br />Scale <br />Status <br />. <br />architecture + planning <br />Agency Approval <br />Petersen Design Architects, Inc. <br />17582 Fiesta Way, Tustin, CA 92780 <br />M: 714.904.6720 E: mike@mpdarch.com <br />www.mpdarch.com <br />Architect's Stamp <br />. <br />255 E. Rincon St., Suite 301 <br />Corona, CA 92879 <br />P 951.340.1977 | F 951.340.1090 <br />www.gossengineering.com <br />CALOFI <br />GI <br />RE <br />NG <br />A <br />E <br />S <br />No. E17083 <br />T <br />E <br />ET <br />SAT L CE A <br />F <br />RIC L <br />ORNI <br />EPR <br />RAET <br />RED D.D <br />OF ONABR <br />L <br />SSI <br />NE <br />RE <br />IWD <br />UT <br />HCE <br />Project Number: 125-09-07 <br />Date Signed 01-09-2026 <br />1 01/09/2026 PLAN CHECK RESUBMITTAL <br />ELECTRICAL <br />SPECIFICATIONS <br />E7.4