20 AMP, 125V, NEMA 5-20R DUPLEX RECEPTACLE
<br />20 AMP, 125V, NEMA 5-20R DUPLEX RECEPTACLE, MOUNTED 6" ABOVE
<br />COUNTER AND/OR ABOVE BACKSPLASH, UNLESS OTHERWISE NOTED
<br />20 AMP, 125V, NEMA 5-20R QUAD RECEPTACLE
<br />20 AMP, 125V, NEMA 5-20R CEILING MOUNTED SIMPLEX RECEPTACLE
<br />20 AMP, 125V, NEMA 5-20R DUPLEX FLOOR RECEPTACLE, 3/4" CONDUIT RUN
<br />CONCEALED IN FLOOR SLAB
<br />20 AMP, 125V, NEMA 5-20R QUAD FLOOR RECEPTACLE, 3/4" CONDUIT RUN
<br />CONCEALED IN FLOOR SLAB
<br />JUNCTION BOX, CEILING MOUNTED
<br />JUNCTION BOX, WALL MOUNTED
<br />SPECIAL RECEPTACLE, WALL MOUNTED, CONFIGURATION AS NOTED ON
<br />PLAN
<br />MOTOR: HORSEPOWER AS INDICATED ON PLANS OR DIAGRAMS
<br />PANELBOARD, ELECTRICAL DISTRIBUTION PANEL, OR LOAD CENTER
<br />SURFACE MOUNTED
<br />PANELBOARD, ELECTRICAL DISTRIBUTION PANEL, OR LOAD CENTER RECESS
<br />MOUNTED
<br />SINGLE POLE SWITCH; 3= THREE WAY SWITCH, 4= FOUR WAY SWITCH, K=
<br />KEY SWITCH, D= DIMMER SWITCH, T0= MOTOR RATED SWITCH, OS=
<br />OCCUPANCY SENSING, 3D= THREE WAY DIMMER SWITCH, T0= MOTOR
<br />RATED SWITCH.
<br />PLUGMOLD, REFER TO DRAWING FOR LENGTHS
<br />SAFETY SWITCH, NON-FUSED, 240V, U.N.O.
<br />COMBINATION STARTER/DISCONNECT (SIZE AS INDICATED)
<br />FUSED DISCONNECT
<br />PHOTOCELL
<br />KEY NOTE DESIGNATION
<br />SHORT CIRCUIT TAG DESIGNATION
<br />FEEDER TAG DESIGNATION
<br />NEW TO EXISTING CONNECTION
<br />NEW CONSTRUCTION
<br />EXISTING CONDITIONS
<br />DEMOLITION WORK
<br />BRANCH CIRCUITS HOMERUN USE NUMBER 12 AWG WIRE, UNLESS
<br />OTHERWISE NOTED. ALL CIRCUITS SHALL CONTAIN A GROUND AND
<br />NEUTRAL CONDUCTOR, UNLESS NOTED OTHERWISE. CONTRACTOR SHALL
<br />PROVIDE MULTI-WIRE CIRCUIT HANDLE TIES AS FINAL FIELD INSTALLED
<br />WIRING REQUIRES.
<br />CONDUIT AND WIRE CONCEALED, 3/4" UNLESS OTHERWISE NOTED,
<br />CONDUIT USED FOR SWITCH LEGS, AND CONDUIT USED FOR
<br />CONTROL WIRING
<br />CONDUIT AND WIRE EMBEDDED IN CONCRETE OR BELOW GRADE
<br />CONDUIT TURNING DOWN
<br />CONDUIT TURNING UP
<br />REVISION NUMBER DESIGNATION
<br />M
<br />M
<br />SPD
<br />800A3P
<br />400A FRN
<br />800A3P
<br />SAFETY SWITCH, NON-FUSED, 240V, U.N.O.
<br />COMBINATION STARTER/DISCONNECT (SIZE AS INDICATED)
<br />FUSED DISCONNECT
<br />FIRE ALARM REMOTE ANNUNCIATOR PANEL
<br />FIRE ALARM CONTROL PANEL
<br />SMOKE DETECTOR, ADDRESSABLE PHOTO ELECTRIC
<br />HEAT DETECTOR
<br />DUCT SMOKE DETECTOR, ADDRESSABLE PHOTO ELECTRIC
<br />FIRE ADA ALARM STROBE MOUNTED AT 80" AFF OR 6" BELOW CEILING
<br />WHICHEVER IS LOWER
<br />FIRE ADA ALARM HORN MOUNTED AT 80" AFF OR 6" BELOW CEILING
<br />WHICHEVER IS LOWER
<br />MAGNETIC DOOR HOLDER
<br />FIRE ALARM TAMPER SWITCH
<br />FIRE ALARM FLOW SWITCH
<br />FIRE ALARM AUDIBLE AND ADA STROBE LIGHT MOUNTED AT 80" AFF OR 6"
<br />BELOW CEILING, WHICHEVER IS LOWER
<br />FIRE ALARM MANUAL PULL STATION, ADDRESSABLE DOUBLE ACTION
<br />FARA
<br />FACP CEILING MOUNTED OCCUPANCY SENSOR
<br />2' X 4' RECESSED LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE SCHEDULE,
<br />HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH EMERGENCY BATTERY
<br />BACKUP.
<br />2' X 4' SURFACE MOUNTED LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE
<br />SCHEDULE, HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH
<br />EMERGENCY BATTERY BACKUP.
<br />STRIP TYPE LUMINAIRE, LENGTHS AS NOTED ON LUMINAIRE SCHEDULE,
<br />HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH EMERGENCY BATTERY
<br />BACKUP.
<br />EMERGENCY BATTERY LUMINAIRE (2 HEAD) 84" AFF, UNLESS OTHERWISE
<br />NOTED, LETTER DENOTES LUMINAIRE TYPE.
<br />SINGLE POLE SWITCH; 3= THREE WAY SWITCH, 4= FOUR WAY SWITCH, K= KEY
<br />SWITCH, D= DIMMER SWITCH, FAN= CEILING FAN SWITCH, TO= MOTOR RATED
<br />SWITCH, 3D= THREE WAY DIMMER SWITCH, P= PILOT LIGHT, OS= OCCUPANCY
<br />SENSOR; LOWER CASE LETTER INDICATES LUMINAIRES CONTROLLED
<br />2' X 2' RECESSED LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE SCHEDULE,
<br />HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH EMERGENCY BATTERY
<br />BACKUP.
<br />2' X 2' SURFACE MOUNTED LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE
<br />SCHEDULE, HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH
<br />EMERGENCY BATTERY BACKUP.
<br />1' X 4' SURFACE MOUNTED FLUORESCENT LUMINAIRE, MOUNTING IS NOTED ON
<br />LUMINAIRE SCHEDULE, HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH
<br />EMERGENCY BATTERY BACKUP.
<br />1' X 4' RECESSED LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE SCHEDULE,
<br />HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH EMERGENCY BATTERY
<br />BACKUP.
<br />1' X 4' WALL MOUNTED LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE
<br />SCHEDULE, HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH
<br />EMERGENCY BATTERY BACKUP.
<br />RECESSED MOUNTED DOWNLIGHT, MOUNTING IS NOTED ON LUMINAIRE
<br />SCHEDULE, HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH
<br />EMERGENCY BATTERY BACKUP.
<br />WALL MOUNTED LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE SCHEDULE,
<br />HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH EMERGENCY BATTERY
<br />BACKUP.
<br />WALL WASH LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE SCHEDULE,
<br />HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH EMERGENCY BATTERY
<br />BACKUP.
<br />CEILING MOUNTED EXIT SIGN. PROVIDE DIRECTIONAL ARROWS AS REQUIRED
<br />WALL MOUNTED EXIT SIGN. PROVIDE DIRECTIONAL ARROWS AS REQUIRED
<br />TRACK LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE SCHEDULE
<br />SINGLE POLE MOUNTED, EXTERIOR LUMINAIRE
<br />DOUBLE POLE MOUNTED, EXTERIOR LUMINAIRE
<br />QUAD POLE MOUNTED, EXTERIOR LUMINAIRE
<br />CEILING FAN
<br />BOLLARD LUMINAIRE
<br />EMERGENCY BATTERY LUMINAIRE (2 HEAD) WITH MOUNTED EXIT SIGN. PROVIDE
<br />DIRECTIONAL ARROWS AS REQUIRED MOUNT AT 84" AFF, UNLESS OTHERWISE
<br />NOTED. LETTER DENOTES LUMINAIRE TYPE.
<br />LINEAR PENDANT LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE SCHEDULE,
<br />HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH EMERGENCY BATTERY
<br />BACKUP.
<br />PENDANT LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE SCHEDULE,
<br />HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH EMERGENCY BATTERY
<br />BACKUP.
<br />RECESSED STEP LIGHT LUMINAIRE, MOUNTING IS NOTED ON LUMINAIRE
<br />SCHEDULE, HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH
<br />EMERGENCY BATTERY BACKUP.
<br />NOTE: UPPER CASE LETTER DENOTES LUMINAIRE TYPE. LOWER CASE LETTER ADJACENT
<br />TO LUMINAIRE INDICATES SWITCH THAT CONTROLS LUMINAIRES A AMPS, AIR (COMPRESSED)
<br />AC ABOVE COUNTER
<br />AFC ABOVE FINISHED CEILING
<br />AFEA AREA FOR EVACUATION ASSISTANCE
<br />AFF ABOVE FINISHED FLOOR
<br />AFG ABOVE FINISHED GRADE
<br />AHU AIR HANDLING UNIT
<br />AIC AMPERE INTERRUPTING CURRENT
<br />AL ALUMINUM
<br />ATS AUTOMATIC TRANSFER SWITCH
<br />AWG AMERICAN WIRE GAUGE
<br />AV FOR AUDIO VISUAL MEDIA CABINET
<br />BFF BELOW FINISHED FLOOR
<br />BKR BREAKER
<br />BOS BOTTOM OF STRUCTURE
<br />BTU BRITISH THERMAL UNIT
<br />C CONDUIT
<br />CATV CABLE TELEVISION SYSTEM
<br />CCTV CLOSED CIRCUIT TELEVISION
<br />CFM CUBIC FEET PER MINUTE
<br />CKT CIRCUIT
<br />CLG CEILING
<br />CM COFFEE MAKER
<br />CU COPPER, CONDENSING UNIT
<br />DDC DIRECT DIGITAL CONTROL
<br />DN DOWN
<br />DPDT DOUBLE POLE, DOUBLE THROW
<br />DPST DOUBLE POLE, SINGLE THROW
<br />DW DISHWASHER
<br />DX DIRECT EXPANSION
<br />(E)EXISTING
<br />EPO EMERGENCY POWER OFF
<br />ETR EXISTING TO REMAIN
<br />FBO FURNISHED BY OTHERS
<br />FF FINISHED FLOOR
<br />FHC FIRE HOSE CABINET
<br />FLA FULL LOAD AMPS
<br />FLR FLOOR
<br />FVNR FULL VOLTAGE, NON REVERSING
<br />GD GARBAGE DISPOSAL
<br />GFI GROUND FAULT CIRCUIT INTERRUPTER
<br />(PERSONAL PROTECTION ON DEVICE)
<br />GFP GROUND FAULT PROTECTED FROM UPSTREAM GFI
<br />RECEPTACLE OR CIRCUIT BREAKER
<br />GFR GROUND FAULT RELAY
<br />GND GROUND
<br />HOA HAND OFF AUTOMATIC
<br />HPS HIGH PRESSURE SODIUM
<br />HSTAT HUMIDISTAT
<br />HTG HEATING
<br />HTR HEATER
<br />IG ISOLATED GROUND
<br />KCMIL 1000 CIRCULAR MILS
<br />KV KILOVOLT
<br />KVA KILOVOLT AMPS
<br />KVAR KILOVOLT AMPS REACTIVE
<br />KW KILOWATT
<br />KWH KILOWATT HOUR
<br />LF LINEAR FEET
<br />LRA LOCKED ROTOR AMPS
<br />MATV MASTER ANTENNA TELEVISION SYSTEM
<br />MBH 1000 BTU PER HOUR
<br />MCA MINIMUM CIRCUIT AMPACITY
<br />MCB MAIN CIRCUIT BREAKER
<br />MCC MOTOR CONTROL CENTER
<br />MD MOTORIZED DAMPER
<br />MDP MAIN DISTRIBUTION PANEL
<br />MFR MANUFACTURER
<br />MG MOTOR GENERATOR
<br />MH MANHOLE
<br />MSB MAIN SWITCHBOARD
<br />MTD MOUNTED
<br />MW MICROWAVE
<br />N/A NOT APPLICABLE
<br />NIC NOT IN CONTRACT
<br />N/O NORMALLY OPEN
<br />N/C NORMALLY CLOSED
<br />N/L NIGHT LIGHT
<br />OC ON CENTER
<br />OV OVEN
<br />PDU POWER DISTRIBUTION UNIT
<br />PH,Ø PHASE
<br />PIV POST INDICATOR VALVE
<br />PJ MOUNTED ON CEILING FOR PROJECTOR
<br />PNL PANEL
<br />PT POTENTIAL TRANSFORMER
<br />QTY QUANTITY
<br />(R)REMOVE
<br />(RL)RELOCATE
<br />RA RETURN AIR
<br />RCP REFLECTED CEILING PLAN
<br />REF REFRIGERATOR
<br />REV REVISION
<br />RH RELATIVE HUMIDITY
<br />RLA RUNNING LOAD AMPS
<br />RPM REVOLUTIONS PER MINUTE
<br />SA SUPPLY AIR
<br />SD SMOKE DETECTOR
<br />SF SQUARE FEET
<br />SPDT SINGLE POLE, DOUBLE THROW
<br />SPST SINGLE POLE, SINGLE THROW
<br />SP STATIC PRESSURE
<br />STO SHORT TOGGLE OPERATOR
<br />SWBD SWITCHBOARD
<br />TSTAT THERMOSTAT
<br />TL TWISTLOCK
<br />TV TELEVISION
<br />TYP TYPICAL
<br />U/F UNDERFLOOR
<br />U/G UNDERGROUND
<br />U/S UNDER SLAB
<br />UL UNDERWRITERS LABORATORIES, INC.
<br />UNO UNLESS NOTED OTHERWISE
<br />UPS UNINTERRUPTIBLE POWER SUPPLY
<br />VAC VOLTS ALTERNATING CURRENT, VACUUM
<br />VAV VARIABLE AIR VOLUME
<br />VM VENDING MACHINE
<br />W/WITH
<br />W/O WITHOUT
<br />WP WEATHERPROOF
<br />WT WATERTIGHT, WEIGHT
<br />XFMR TRANSFORMER
<br />XP EXPLOSION PROOF
<br />ARCHITECTURAL DRAWINGS SHALL TAKE PRECEDENCE OVER MOUNTING HEIGHTS
<br />INDICATED ON ELECTRICAL DRAWINGS.
<br />M
<br />OS
<br />J
<br />FS
<br />TS
<br />X
<br />X
<br />X
<br />1
<br />DAYLIGHT SENSORDS
<br />SURFACE MOUNTED DOWNLIGHT, MOUNTING IS NOTED ON LUMINAIRE
<br />SCHEDULE, HATCHING DENOTES FIXTURE SHALL BE PROVIDED WITH
<br />EMERGENCY BATTERY BACKUP.
<br />ELECTRICAL SYMBOLS
<br />NOTE:
<br />ELECTRICAL GENERAL NOTES
<br />POWER LIGHTING
<br />ONE LINE AND RISER
<br />MISCELLANEOUS
<br />CONDUIT DESIGNATIONS
<br />FIRE ALARM
<br />FURNITURE FEED RECEPTACLE, WALL MOUNTED, CONFIGURATION AS
<br />NOTED ON PLAN
<br />ABBREVIATIONS
<br />DUAL LEVEL SWITCH
<br />1.DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND
<br />IN FIELD PRIOR TO COMMENCEMENT OF WORK. REFER TO MECHANICAL PLANS FOR
<br />LOCATION OF ALL MECHANICAL EQUIPMENT. REVIEW ARCHITECTURAL, STRUCTURAL,
<br />MECHANICAL AND OTHER DRAWINGS PRIOR TO BID. COORDINATE ELECTRICAL WORK
<br />REQUIRED BY OTHER DISCIPLINES.
<br />2.PROVIDE ELECTRICAL DEMOLITION REQUIRED. REFER TO ARCHITECTURAL
<br />DEMOLITION DRAWINGS FOR LOCATION AND EXTENT OF DEMOLITION REQUIRED.
<br />CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORK
<br />INVOLVED. PROVIDE LABOR AND MATERIALS AS REQUIRED TO MAINTAIN AND/OR
<br />RESTORE CONTINUITY OF SERVICE TO EXISTING CIRCUITS.
<br />3.FIELD VERIFY EXISTING EQUIPMENT OR CIRCUITS THAT ARE REMAINING TO BE
<br />RECONNECTED TO NEW OR EXISTING SWITCHBOARDS/PANELBOARDS. PROVIDE
<br />SWITCHES, RECEPTACLES, CONDUIT, WIRE, ETC. AS REQUIRED TO RESTORE
<br />CONTINUITY OF CIRCUITS.
<br />4.PROVIDE ALL DEMOLITION REQUIRED TO REMOVE EXISTING UNUSED CONDUIT, WIRE,
<br />CABLE, J-BOXES, RECEPTACLES, SWITCHES, LIGHTS, FIRE ALARM DEVICES, ETC.
<br />COMPLETE WITH ASSOCIATED CIRCUITING TO SOURCE OR NEAREST ACTIVE DEVICE.
<br />WHERE IT IS NOT FEASIBLE TO REMOVE THE ABOVE AND WITH PERMISSION FROM
<br />THE OWNER, OUTLET SHALL BE ABANDONED, WIRE REMOVED AND BLANK COVER
<br />PLATES PROVIDED. IN ALL CONDUIT ABANDONED IN PLACE INSTALL A PULL STRING
<br />LABELED AT BOTH ENDS.
<br />5.CONTRACTOR SHALL MAKE ALL FINAL CONNECTIONS TO EQUIPMENT. FINAL
<br />CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S
<br />APPROVED WIRING DIAGRAMS, DETAILS, AND INSTRUCTIONS. COORDINATE
<br />EQUIPMENT CONNECTION REQUIREMENTS WITH DIVISION 22 AND 23 CONTRACTOR.
<br />CONTRACTOR SHALL PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH
<br />EQUIPMENT SUPPLIED.
<br />6.COORDINATE EQUIPMENT SIZES WITH ROOM SIZES. CONTRACTOR SHALL VERIFY
<br />THAT ELECTRICAL EQUIPMENT ORDERED CAN BE INSTALLED IN THE SPACE PROVIDED
<br />WHILE MAINTAINING CODE REQUIRED CLEARANCES.
<br />7.EXISTING SYSTEMS AND CONDITIONS SHOWN ON DRAWINGS FOR EXISTING
<br />BUILDINGS ARE TO BE NOTED "FOR GUIDANCE ONLY". THE ELECTRICAL
<br />CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO BIDDING
<br />AND TO INCLUDE IN HIS BID AN ALLOWANCE FOR REMOVAL AND/OR RELOCATION OF
<br />EXISTING CONDUITS, WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT AS
<br />INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND
<br />EXISTING ELECTRICAL SYSTEM TO ALL OTHER WORK.
<br />8.SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER IN
<br />WRITING. WORK WHICH COULD RESULT IN AN ACCIDENTAL OUTAGE SHALL BE
<br />PERFORMED WITH THE OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH
<br />WORK.
<br />9.REVIEW ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND REPORT
<br />ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO STARTING WORK IN THESE
<br />AREAS.
<br />10.WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF
<br />THE ARCHITECT.
<br />11.WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF
<br />LOCAL, STATE, AND NATIONAL CODES AND ORDINANCES. COORDINATE WORK WITH
<br />LOCAL FIRE DEPARTMENT.
<br />12.PROVIDE PERMITS AND INSPECTIONS REQUIRED.
<br />13.SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK
<br />IS DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS NECESSARY AT NO COST
<br />TO OWNER.
<br />14.WIRE SHALL BE COPPER, 60 DEGREES C RATED UP TO 30 AMPS AND 75 DEGREES C
<br />RATED ABOVE 30 AMPS. SIZES INDICATED ARE FOR INSTALLATION IN A MAXIMUM 30
<br />DEGREES C AMBIENT. CONDUCTOR AMPACITY SHALL BE DERATED FOR HIGHER
<br />AMBIENT INSTALLATIONS.
<br />15.PROVIDE SHOP DRAWINGS AND/OR SUBMITTALS FOR ITEMS NOTED IN THE
<br />SPECIFICATIONS. SHOP DRAWINGS NOT REQUIRED BY THE SPECIFICATIONS WILL NOT
<br />BE REVIEWED.
<br />16.CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS
<br />DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER THIS SECTION, OR
<br />FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION.
<br />17.CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR
<br />EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO SUBSTITUTE ALTERNATE
<br />MATERIALS, EQUIPMENT, OR INSTALLATION METHODS.
<br />18.SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS
<br />OPERATION. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC. SHALL BE
<br />CONNECTED AND OPERABLE.
<br />19.NEW RECESSED FIXTURES INSTALLED INDOORS SHALL BE THERMALLY PROTECTED.
<br />20.PROVIDE NEW TYPED UPDATED PANELBOARD DIRECTORIES FOR EXISTING AND NEW
<br />CIRCUITS BEING UTILIZED FOR COMPLETION OF PROJECT.
<br />21.CONDUITS PENETRATING THROUGH ROOF SHALL HAVE ROOF FLASHING WITH CAULK
<br />TYPE COUNTER FLASHING SLEEVE. INSTALLATION SHALL BE WATERTIGHT.
<br />22.FINAL CONNECTIONS TO MOTORS, TRANSFORMERS AND OTHER VIBRATING
<br />EQUIPMENT SHALL BE MADE WITH LIQUID TIGHT FLEXIBLE CONDUIT AND APPROVED
<br />FITTINGS. DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK
<br />OR MECHANICAL EQUIPMENT. PROVIDE VIBRATION ISOLATION PADS FOR ALL
<br />TRANSFORMERS AND MOTORS.
<br />23.WHERE PANELS ARE INSTALLED FLUSH WITH WALLS, EMPTY CONDUITS SHALL BE
<br />EXTENDED FROM THE PANEL TO AN ACCESSIBLE SPACE ABOVE OR BELOW. A
<br />MINIMUM OF ONE 3/4" CONDUIT SHALL BE INSTALLED FOR EVERY THREE SINGLE POLE
<br />SPARE CIRCUIT BREAKERS OR SPACES, OR FRACTION THEREOF, BUT NOT LESS THAN
<br />TWO CONDUITS.
<br />24.WIRE TERMINATION PROVISIONS FOR PANELBOARDS, CIRCUIT BREAKERS, SAFETY
<br />SWITCHES, AND ALL OTHER ELECTRICAL APPARATUS SHALL BE LISTED AS 75
<br />DEGREES C.
<br />25.ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED BY UL.
<br />26.IF REQUIRED, FIRE ALARM SYSTEM SHALL BE DESIGNED AND SUBMITTED AS
<br />DELEGATED DESIGN SUBMITTAL. PROVIDE SYSTEM DEVICES, CONDUIT, WIRES, AND
<br />CABLE AS DIRECTED BY EQUIPMENT MANUFACTURER. MATERIALS, EQUIPMENT, AND
<br />WORKMANSHIP SHALL MEET PREVAILING CODES. THE SYSTEM SHALL BE COMPLETE
<br />AND OPERABLE IN EVERY RESPECT. SUBMIT SHOP DRAWINGS ACCORDING TO
<br />SPECIFICATIONS. SHOP DRAWINGS SHALL INCLUDE A SINGLE LINE DIAGRAM THAT
<br />SHOWS DEVICES, CONDUIT, WIRE, CABLE SIZES AND EQUIPMENT TO BE USED. SHOP
<br />DRAWINGS SHALL BE STAMPED AND SIGNED BY A REGISTERED ENGINEER PROVIDED
<br />BY THE FIRE ALARM VENDOR. SYSTEM CALIBRATION AND TESTING SHALL BE BY
<br />FACTORY CERTIFIED TECHNICIAN.
<br />27.BACK-TO-BACK OUTLETS IN THE SAME WALL, OR “THRU-WALL” TYPE BOXES SHALL
<br />NOT BE PERMITTED. PROVIDE 24-INCH SEPARATION TO OFFSET OUTLETS SHOWN ON
<br />OPPOSITE SIDES OF A COMMON WALL TO MINIMIZE SOUND TRANSMISSION. COVER
<br />BACKBOXES WITH EITHER FIRE OR SOUND PUTTY PAD.
<br />
<br />28.OUTLET BOXES ON OPPOSITE SIDES OF FIRE-RATED WALLS AND PARTITIONS SHALL
<br />BE SEPARATED BY A HORIZONTAL DISTANCE OF AT LEAST 24 INCHES.
<br />26.BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED TO PREVENT A VOLTAGE DROP
<br />EXCEEDING 3%.
<br />CLOCK, 84" (CENTERLINE) A.F.F. OR 8" (CENTERLINE) BELOW CEILINGS THAT
<br />ARE 8'-0" OR LOWER, UNLESS NOTED OTHERWISE.
<br />SPEAKER, CEILING MOUNTED
<br />HORN SPEAKER
<br />SPEAKER, WALL MOUNTED, 84" (CENTERLINE) A.F.F. OR 8" (CENTERLINE)
<br />BELOW CEILINGS THAT ARE 8'-0" OR LOWER, UNLESS NOTED OTHERWISE.
<br />JUNCTION BOX FOR INSTALLATION OF TV OUTLET. MOUNTED 18" AFF,
<br />UNLESS OTHERWISE NOTED. INSTALL 1" CONDUIT FROM BOX TO 3" INTO
<br />ACCESSIBLE LOCATION ABOVE FINISHED CEILING. COORDINATE MOUNTING
<br />HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN.
<br />JUNCTION BOX FOR INSTALLATION OF COMMUNICATION OR DATA OUTLET,
<br />MOUNTED 18" AFF, UNLESS OTHERWISE NOTED. INSTALL 1" CONDUIT FROM
<br />BOX TO 3" INTO ACCESSIBLE LOCATION ABOVE FINISHED CEILING.
<br />FLOOR JUNCTION BOX FOR INSTALLATION OF COMMUNICATION OR DATA
<br />OUTLET. INSTALL 1" CONDUIT FROM BOX CONCEALED IN FLOOR SLAB TO
<br />WALL AND TO 3" INTO ACCESSIBLE LOCATION ABOVE FINISHED CEILING.
<br />COMMUNICATIONS
<br />20 AMP, 125V, NEMA 5-20R SWITCHED DUPLEX RECEPTACLE
<br />SPECIAL RECEPTACLE, CEILING MOUNTED, CONFIGURATION AS NOTED ON
<br />PLAN
<br />WALL MOUNTED TIMECLOCKTC
<br />ENCLOSED CIRCUIT BREAKER
<br />20 AMP, 125V, NEMA 5-20R CEILING MOUNTED DUPLEX RECEPTACLE
<br />20 AMP, 125V, NEMA 5-20R SIMPLEX RECEPTACLE
<br />ENCLOSED CIRCUIT BREAKER
<br />G
<br />GROUND BAR
<br />R RELAY
<br />EMERGENCY POWER OFF (EPO) PUSH BUTTON
<br />POWER POLEPP
<br />JUNCTION BOX, FLOOR MOUNTED
<br />CODE SUMMARY
<br />TITLE 24 C.C.R., PART1 2025 CALIFORNIA BUILDING STANDARDS ADMINISTRATIVE CODE.
<br />TITLE 24 C.C.R., PART2 2025 CALIFORNIA BUILDING CODE (CBC)
<br />TITLE 24 C.C.R., PART3 2025 CALIFORNIA ELECTRICAL CODE (CEC)
<br />TITLE 24 C.C.R., PART4 2025 CALIFORNIA MECHANICAL CODE (CMC)
<br />TITLE 24 C.C.R., PART5 2025 CALIFORNIA PLUMBING CODE (CPC)
<br />TITLE 24 C.C.R., PART6 2025 CALIFORNIA ENERGY CODE
<br />TITLE 24 C.C.R., PART7 (NO LONGER PUBLISHED IN TITLE 24. SEE TITLE 8, CCR)
<br />TITLE 24 C.C.R., PART8 2025 CALIFORNIA HISTORICAL BUILDING CODE
<br />TITLE 24 C.C.R., PART9 2025 CALIFORNIA FIRE CODE (CFC)
<br />TITLE 24 C.C.R., PART10 2025 CALIFORNIA EXISTING BUILDING CODE
<br />TITLE 24 C.C.R., PART11 2025 CALIFORNIA GREEN BUILDING STANDARDS CODE
<br />TITLE 24 C.C.R., PART12 2025 CALIFORNIA REFERENCED STANDARDS CODE
<br />TITLE 19 C.C.R., PUBLIC SAFETY, STATE FIRE MARSHAL REGULATIONS.
<br />NFPA 70 NATIONAL ELECTRICAL CODE
<br />NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
<br />NFPA 80 FIRE DOORS AND OTHER OPENING PROTECTIVE
<br />NFPA 101 LIFE SAFETY CODE
<br />CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE CODES WEATHER INDICATES HERE IN OR
<br />NOT.
<br />RECEPTACLES (CENTERLINE)
<br />RECEPTACLES IN EQUIP. RMS.
<br />RECEPTACLES (EXTERIOR)
<br />RECEPTACLES (GARAGES)
<br />ALARMS, SWITCHES AND CONTROLS (CENTERLINE)
<br />TELEPHONE (PUBLIC)
<br />TELEPHONE OUTLETS (CENTERLINE)
<br />TELEPHONE TERMINAL BOARD (BTM.)
<br />SAFETY SWITCHES
<br />STARTERS
<br />PANELS (TOP)
<br />CLOCK OUTLETS (CENTERLINE)
<br />FIRE ALARM PULL STATIONS (HANDLE)
<br />STROBES (CENTERLINE)
<br />FIRE ALARM BELLS (EXTERIOR)
<br />CONTROLS (FIRE ALARM CONTROL PANEL)
<br />ANNUNCIATION PANELS
<br />INTERCOM (AFEA ONLY)
<br />REMOTE INDICATING LIGHT (EQUIP. RMS.)
<br />REMOTE INDICATING LIGHT (FIN. AREAS)
<br />EXIT SIGNS (WALL MOUNTED BTM.)
<br />TELEVISION OUTLETS
<br />INTERCOMS
<br />PHOTOCELLS
<br />18"
<br />48"
<br />24"
<br />24"
<br />48"
<br />1@48" AND 1@36"
<br />18"
<br />6"
<br />48"
<br />48"
<br />72"
<br />90"
<br />44"
<br />80"*
<br />12'-0"
<br />48"
<br />48"
<br />36"
<br />48"
<br />CEILING
<br />80"
<br />18"
<br />48"
<br />12'-0"
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />AAA
<br />A
<br />A
<br />A A
<br />A
<br />A
<br />A
<br />A
<br />A
<br />STANDARD MOUNTING HEIGHT U.N.O.
<br />PANEL
<br />PANEL
<br />XXX
<br />CURRENT TRANSFORMER, RATED AS SPECIFIED OR REQUIRED
<br />MOTOR
<br />SURGE PROTECTION DEVICE
<br />GROUND CONNECTION
<br />SWITCH, RATING AS SHOWN
<br />FUSE, FUSE AMPACITY AND TYPE AS SHOWN
<br />CIRCUIT BREAKER, RATING AS SHOWN
<br />UTILITY METER (AS REQUIRED BY UTILITY)
<br />TRANSFORMER, TYPE AND RATING AS SHOWN
<br />CONDUIT CONNECTION
<br />CIRCUIT BREAKER WITH GROUND FAULT PROTECTION
<br />FUSE WITH GROUND FAULT PROTECTION
<br />GROUND CONNECTION WITH TEST WELL
<br />GROUND ROD
<br />WEATHER HEAD
<br />GENERATOR
<br />THIS IS A MASTER SYMBOLS LIST. ALL SYMBOLS, ABBREVIATIONS, ETC. MAY NOT
<br />NECESSARILY BE USED ON ALL DRAWINGS.
<br />T-XX
<br />20 AMP, 125V, NEMA 5-20R GFCI RECEPTACLE
<br />OS WALL MOUNTED OCCUPANCY SENSOR
<br />PC
<br />D
<br />20 AMP, 125V, NEMA 5-20R DUPLEX TAMPER RESISTANT RECEPTACLETR
<br />AS NOTED
<br />DRAWN CHECKEDDATE
<br />SCALE
<br />PROJECT NUMBER
<br />SHEETSHEET NAME
<br />PROJECT TITLE
<br />LOCATION:
<br />1 2 3 4 5
<br />B
<br />A
<br />C
<br />D
<br />15551 Eden Street
<br />Westminster, CA 92683
<br />Copyright. Hu Architecture Inc. 2018. All rights reserved.
<br />This drawing and its contents is copyright by Hu Architecture.
<br />Reproducing, modifying, and distributing this material without the
<br />written permission of Hu Architecture is prohibited.ST
<br />A
<br />M
<br />P
<br />CLIENT INFORMATION
<br />duchuy@huarchitecture.com
<br />(714) 476-4751
<br />NO.DATE DESCRIPTION
<br />RE
<br />V
<br />I
<br />S
<br />I
<br />O
<br />N
<br />S
<br />CONSULTANT INFORMATION
<br />B
<br />A
<br />C
<br />D
<br />duchuy@huarchitecture.com
<br />(714) 476-4751
<br />??????
<br />2025.103
<br />Laundromat 2710 W Edinger Ave | Equipment Electrical Replacement
<br />Unit A, Laundromat 2710 W Edinger Ave
<br />Santa Ana, CA 92704
<br />Owner
<br />Laundromat 2710 W Edinger Ave
<br />Santa Ana, CA 92704
<br />20
<br />2
<br />5
<br />.
<br />1
<br />0
<br />3
<br />_
<br />
<br />L
<br />a
<br />u
<br />n
<br />d
<br />r
<br />o
<br />m
<br />a
<br />t
<br />
<br />2
<br />7
<br />1
<br />0
<br />
<br />W
<br />
<br />E
<br />d
<br />i
<br />n
<br />g
<br />e
<br />r
<br />
<br />A
<br />v
<br />e
<br />
<br />|
<br />
<br />E
<br />q
<br />u
<br />i
<br />p
<br />m
<br />e
<br />n
<br />t
<br />
<br />E
<br />l
<br />e
<br />c
<br />t
<br />r
<br />i
<br />c
<br />a
<br />l
<br />
<br />R
<br />e
<br />p
<br />l
<br />a
<br />c
<br />e
<br />m
<br />e
<br />n
<br />t
<br />NO DATE DESCRIPTION
<br />Phone: (619) 736-3422
<br />Email: hello@s3da-design.com
<br />May 250102-10-26 PC COMMENT 01
<br />E 0.0GENERAL INFORMATION - ELECTRICAL
<br />1
<br />1
|