<br /> <br /> Page 28 of 111 <br /> <br />Report No.: 2410B0143SHA-001 <br /> <br />TRF No. ANSI/CAN/UL 9540A_Unit <br /> <br />ANSI/CAN/UL 9540A <br />Clause Requirement – Test Result - Remark Verdict <br /> <br />b) The setup (i.e. type, quantity and positioning) of <br />equipment for initiating thermal runaway in the <br />module shall be the same as that used to initiate <br />and propagate thermal runaway within the module <br />level test (Section 8). <br />Refer to TÜV SÜD Report No.: <br />5061724026506 Pass <br />9.2.24 <br />The composition, velocity and temperature of the <br />initiating BESS unit vent gases shall be measured <br />within the calorimeter's exhaust duct as in 8.2.10. <br />Via the testing system which has <br />the sensors in the exhaust duct Pass <br /> The hydrocarbon content of the vent gas shall be <br />measured using flame ionization detection. <br />Integerated FID in the testing <br />system used Pass <br /> Hydrogen gas shall be measured with a palladium- <br />nickel thin-film solid state sensor. <br />Complied <br />See attachment 10 Pass <br />9.2.25 <br />The hydrocarbon components of the vent gas <br />composition may additionally be measured using a <br />Fourier-Transform Infrared Spectrometer with a <br />minimum resolution of 1 cm-1 and a path length of at <br />least 2 m, or an equivalent gas analyzer. <br />See attachment 10 <br />(modified by UL CRD-20200110) Pass <br />9.2.26 The test shall be terminated if: -- <br /> <br />a) Temperatures measured inside each module within <br />the initiating BESS unit return to ambient <br />temperature; <br />Complied Pass <br /> b) The fire propagates to adjacent units or to adjacent <br />walls; or Not observed N/A <br /> c) A condition hazardous to test staff or the test <br />facility requires mitigation. Not observed N/A <br />9.2.27 <br />For residential use systems, the gas collection data <br />shall be compared to the smallest room installation <br />specified by the manufacturer to determine if the <br />flammable gas collected exceeds 25% LFL in air. <br />Non-residential BS N/A <br />9.3 Test method – Outdoor ground mounted units -- <br />9.3.1 <br />Outdoor ground mounted non-residential use BESS <br />being evaluated for installation in close proximity to <br />buildings and structures. <br />(the test method described in <br />section 9.2) <br />Complied <br />Pass <br /> <br />If intended for outdoor use only installations, the smoke <br />release rate, the convective and chemical heat release <br />rate and content, velocity and temperature of the <br />released vent gases need not be measured. <br />Measured Pass <br />9.3.2 <br />Outdoor ground mounted residential use BESS being <br />evaluated for installation in close proximity to buildings <br />and structures. <br />(the test method described in <br />section 9.2) N/A <br /> Heat flux measurements for the accessible means of <br />egress. <br />(measured in accordance with <br />9.2.20) N/A