Laserfiche WebLink
ORDINANCE NO. <br />PAGE THREE <br /> <br />NS- 1903 <br /> <br />SECTION 6: That Section 8-843 of the Santa Ana Municipal <br />Code is hereby amended to read as follows: <br /> <br />Sec. 8-843. Branch circuits required (Section 220-4). <br /> <br /> Section 220-4 of the National Electrical Code is <br />amended by adding to the introductory paragraph the following: <br /> <br />There shall be a maximum of twelve (12) <br />outlets or twelve (12) lighting outlets <br />circuit. <br /> <br />receptacle <br />to any one <br /> <br />SECTION 7: That Section 8-854 of the Santa Ana Municipal <br />Code is hereby amended to read as follows: <br /> <br />Sec. 8-854. <br /> <br />Wiring methods for six hundred volts or less <br />(Section 230-43). <br /> <br /> Section 230-43 of the National Electrical Code is <br />hereby amended to read as follows: <br /> <br />Sec. 230.43. Wiring methods for six hundred (600) <br />volts or less. Service entrance conductors extending <br />along the exterior or entering buildings or other <br />structures shall be enclosed in steel rigid metal <br />conduit to the first over current device, or, for <br />circuits not exceeding six hundred (600) volts, in <br />wire ways, auxiliary gutters, or as busways. <br /> <br />SECTION 8: That Section 8-862 of the Santa Ana Municipal <br />Code is hereby amended to read as follows: <br /> <br />Sec. 8-862. Grounding electrode system (Section 250-81). <br /> <br /> Section 250-81 of the National Electrical Code is <br />hereby amended to read as follows: <br /> <br />Sec. 250-81. Grounding Electrode System. The <br />grounding electrode system shall consist of not less <br />than twenty (20) feet of bare copper not smaller than <br />No. 4 or not less than twenty (20) feet No. 4 steel <br />reinforcing bar; or not less than twenty (20) feet of <br />three-fourth (3/4) inch galvanized steel conduit, or <br />an approved equal installed as follows: The electrode <br /> <br /> <br />