Laserfiche WebLink
3. Exterior painting or refinishing of the equipment and/or surrounding surfaces. <br />4. Repair of damages from any cause other than ordinary use, including acts of God and <br />vandalism. <br />5. Repair and maintenance of water flow switches. <br />6. Replacement peripheral devices and batteries. <br />IV. PARTS AND EQUIPMENT <br />1_ Replacement <br />1.1 Company shall provide UL and ISO 9000 listed control parts necessary to repair <br />the fire alarm system control units and annunciator panels at no additional cost. <br />1.2 Company shall provide UL approved lamps, fuses and LED's at no additional <br />cost. <br />2. Inventory <br />2.1 The Company shall have in local office inventory the following UL and ISO <br />9000 listed itemsiequipment for the fire alarm systems. <br />2.1.1 One (1) complete set of circuit boards for Fire Alarm systems. <br />2.1.2 One (1) set of UL listed replacement batteries. <br />2.1.3 Complete UL listed replacement peripheral devices, three (3) complete <br />units for each type installed. <br />32 The service personnel shall have in their vehicle inventory an adequate supply <br />of replacement parts/equipment. <br />2.3 The Company shall have access to a fire alarm national parts distribution center <br />to provide repair parts within 24 hours. <br />V. DETAILS OF FIRE ALARM INSPECTIONS <br />1. Fire Control Panel <br />• All zones operate alarm <br />• All zones operate trouble <br />• Common trouble indicators operate <br />• All fuses agree with markings <br />Rev: 327/2009 <br />